| Plan Review Notes For Permit 06041149 |
| Permit Number |
06041149 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-06-15 00:00:00 | | | | | | | | | | | | | | | | IF WATER HEATER ROOM IS A CONFINED | | | SPACE, OPENINGS REQUIRED PER SECTION | | | 304.5 OR SECTION 304.6 SHALL BE | | | INSTALLED. | | | MINIMUM 2,500 CUBIC FEET REQUIRED. |
|