| 2006-09-11 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | COMMENTS FROM PREVIOUS LIST, NUMBERING |
| | REMAINING THE SAME FOR CONSISTENCY |
| | |
| | 1.)THE FIRST LIST REQUESTED THAT YOU |
| | SHOW COMPLIANCE WITH FBC TABLE 601, TWO |
| | BUILDINGS ON THE SAME LOT.YOUR |
| | RESPONSE LETTER STATES THAT THIS IS ONE |
| | STRUCTURE, BUT THE ELEVATION 1-S2 SHOWS |
| | TWO STRUCTURES, NOT STRUCTURALLY |
| | CONNECTED.PLEASE ADDRESS. |
| | |
| | 2.)COMMENT FROM FIRST LIST - PROVIDE |
| | INFORMATION IN REGARDS TO THE EXISTING |
| | BUILDING AND THE PROPOSED BUILDING; |
| | DECLARE THE BUILDING AREA, MINIMUM |
| | BUILDING TYPE FBC6, FIRE SPRINKLER |
| | INFORMATION, OCCUPANCY FBC3, AND ANY |
| | OTHER INFORMATION REQUIRED TO DETERMINE |
| | CODE COMPLIANCE FOR THE PROPOSED WORK. |
| | |
| | 2ND REVIEW - S1/F1 WAS DECLARED FOR |
| | OCCUPANCY.ARE PORTIONS OF THE BUILDING |
| | DIFFERENT OCCUPANCIES?STATE SQUARE |
| | FOOT AREA FOR EACH. PROVIDE MORE |
| | INFORMATION IN REGARDS TO THE USE OF THE |
| | EXISTING BUILDING AND THE ADDITION. |
| | |
| | BUILDING TYPE WAS DECLARED AS IA.SEE |
| | FBC TABLE 601.PROVIDE CALCULATED FIRE |
| | RESISTANCE OR ASSEMBLY LISTING TO SHOW |
| | THAT BOTH THE EXISTING BUILDING HAS THE |
| | FIRE RESISTANCE AS REQUIRED AND THAT THE |
| | PROPOSED ADDITION ALSO HAS FIRE |
| | RESISTANCE AS REQUIRED BY THIS TABLE. |
| | IT DOES NOT APPEAR THE THE COLUMNS HAVE |
| | A 3 HOUR FIRE RESISTANCE, ROOF DOES NOT |
| | APPEAR TO BE 1 1/2 HOUR. |
| | |
| | COMPLIANCE WITH FBC TABLE 503, ALLOWABLE |
| | HEIGHT AND BUILDING AREAS, CANNOT BE |
| | DETERMINED UNTIL CORRECT OCCUPANCY |
| | CLASSIFICATION, BUILDING TYPE, AND ISSUE |
| | OF SEPARATE BUILDINGS HAS BEEN |
| | ADDRESSED. |
| | |
| | 3.)SHOW HOW EGRESS AND ACCESSIBILITY |
| | IN THE EXISTING BUILDING AREA AFFECTED |
| | BY THIS IMPROVEMENT. |
| | |
| | 4.-5.)ADDRESSED. |
| | |
| | 6.)FLORIDA STATE PRODUCT APPROVAL WAS |
| | SUBMITTED.PLEASE HAVE THIS REVIEWED BY |
| | THE DESIGNER OF RECORD, FBC*106.3.3. |
| | |
| | 7.)ADDRESSED. |
| | |
| | NEW COMMENTS: |
| | |
| | 8.)PROVIDE INFORMATION IN REGARDS TO |
| | MATERIALS TO BE STORED. |
| | |
| | 9.)ADDITIONS ARE TO COMPLY WITH FBC EB |
| | CHAPTER 9.SEE FBC901.2, FBC902.2. |
| | |
| | 10.)ACCESSIBILITY REQUIREMENTS ARE NOT |
| | CLEAR AS YOU HAVE DECLARED F1 AND S1. |
| | SEE FBC905.1, FBC CHAPTER 11. |
| | |
| | 11.)SEE ATTACHED FS553.80(2)(B).A 4X |
| | PLAN REVIEW FEE IS REQUIRED TO BE |
| | CHARGED IF THE COMMENTS ARE NOT PROPERLY |
| | ADDRESSED A THIRD TIME. |