Plan Review Notes
Plan Review Notes For Permit 06041140
Permit Number 06041140
Review Stop B
Sequence Number 2
Notes
Date Text
2006-09-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 COMMENTS FROM PREVIOUS LIST, NUMBERING
 REMAINING THE SAME FOR CONSISTENCY
  
 1.)THE FIRST LIST REQUESTED THAT YOU
 SHOW COMPLIANCE WITH FBC TABLE 601, TWO
 BUILDINGS ON THE SAME LOT.YOUR
 RESPONSE LETTER STATES THAT THIS IS ONE
 STRUCTURE, BUT THE ELEVATION 1-S2 SHOWS
 TWO STRUCTURES, NOT STRUCTURALLY
 CONNECTED.PLEASE ADDRESS.
  
 2.)COMMENT FROM FIRST LIST - PROVIDE
 INFORMATION IN REGARDS TO THE EXISTING
 BUILDING AND THE PROPOSED BUILDING;
 DECLARE THE BUILDING AREA, MINIMUM
 BUILDING TYPE FBC6, FIRE SPRINKLER
 INFORMATION, OCCUPANCY FBC3, AND ANY
 OTHER INFORMATION REQUIRED TO DETERMINE
 CODE COMPLIANCE FOR THE PROPOSED WORK.
  
 2ND REVIEW - S1/F1 WAS DECLARED FOR
 OCCUPANCY.ARE PORTIONS OF THE BUILDING
 DIFFERENT OCCUPANCIES?STATE SQUARE
 FOOT AREA FOR EACH. PROVIDE MORE
 INFORMATION IN REGARDS TO THE USE OF THE
 EXISTING BUILDING AND THE ADDITION.
  
 BUILDING TYPE WAS DECLARED AS IA.SEE
 FBC TABLE 601.PROVIDE CALCULATED FIRE
 RESISTANCE OR ASSEMBLY LISTING TO SHOW
 THAT BOTH THE EXISTING BUILDING HAS THE
 FIRE RESISTANCE AS REQUIRED AND THAT THE
 PROPOSED ADDITION ALSO HAS FIRE
 RESISTANCE AS REQUIRED BY THIS TABLE.
 IT DOES NOT APPEAR THE THE COLUMNS HAVE
 A 3 HOUR FIRE RESISTANCE, ROOF DOES NOT
 APPEAR TO BE 1 1/2 HOUR.
  
 COMPLIANCE WITH FBC TABLE 503, ALLOWABLE
 HEIGHT AND BUILDING AREAS, CANNOT BE
 DETERMINED UNTIL CORRECT OCCUPANCY
 CLASSIFICATION, BUILDING TYPE, AND ISSUE
 OF SEPARATE BUILDINGS HAS BEEN
 ADDRESSED.
  
 3.)SHOW HOW EGRESS AND ACCESSIBILITY
 IN THE EXISTING BUILDING AREA AFFECTED
 BY THIS IMPROVEMENT.
  
 4.-5.)ADDRESSED.
  
 6.)FLORIDA STATE PRODUCT APPROVAL WAS
 SUBMITTED.PLEASE HAVE THIS REVIEWED BY
 THE DESIGNER OF RECORD, FBC*106.3.3.
  
 7.)ADDRESSED.
  
 NEW COMMENTS:
  
 8.)PROVIDE INFORMATION IN REGARDS TO
 MATERIALS TO BE STORED.
  
 9.)ADDITIONS ARE TO COMPLY WITH FBC EB
 CHAPTER 9.SEE FBC901.2, FBC902.2.
  
 10.)ACCESSIBILITY REQUIREMENTS ARE NOT
 CLEAR AS YOU HAVE DECLARED F1 AND S1.
 SEE FBC905.1, FBC CHAPTER 11.
  
 11.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE IS REQUIRED TO BE
 CHARGED IF THE COMMENTS ARE NOT PROPERLY
 ADDRESSED A THIRD TIME.