| Plan Review Notes For Permit 06041137 |
| Permit Number |
06041137 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-02 00:00:00 | **** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED | | | BY PREPARER AND OWNER/AGENT. | | | | | | 2) PLEASE SUBMIT TWO COPYS OF ALL PAPER | | | WORK. | | | | | | 3) MANUAL J CALCULATIONS ARE CALLING FOR | | | A 5 TON A/C SYSTEM, PLEASE RE-CALCULATE | | | THE MANUAL J CAL'S.. | | | | | | 4) BY PASSIVE RETURN DO YOU MEAN RETHRN | | | AIR TRANSFER GRILLS OR RETURN AIR | | | TRANSFER DUCTS (IF DUCTS SHOW SIZE OF | | | DUCT ALSO), PLEASE CORRECT. | | | | | | 5) PLEASE PROVIDE RETURN AIR FOR BEDROOM | | | #3. | | | | | | 6)NEED TO FILE A NOTICE OF COMMENCEMENT, | | | PER F. S. 713.13 . | | | | | | 7) CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY. PER 2004 FBC 106.1.1 | | | . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|