Plan Review Notes
Plan Review Notes For Permit 06041126
Permit Number 06041126
Review Stop P
Sequence Number 1
Notes
Date Text
2006-05-08 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR A PLUMBING PERMIT:
  
 1. PER SECTION 708.3.4, CLEANOUTS SHALL
 BE LOCATED AT THE BASE OF EACH WASTE OR
 SOIL STACK. PLEASE SEE CORRECTED
 PLUMBING SHEET 2/2FOR RESUBMITTAL
 REFERENCE.
 2. PER SECTION 708.3.5, THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND BUILDING SEWER.
 PLEASE SEE CORRECTED PLUMBING SHEET 2/2
 FOR RESUBMITTAL REFERENCE.
 3. PER SECTION 501.4 WATER HEATER
 LOCATION. WATER HEATERS SHALL BE LOCATED
 AND CONNECTED SO AS TO PROVIDE ACCESS
 FOR OBSERVATION, MAINTENANCE, SERVICING,
 AND REPLACEMENT. PLEASE PROVIDE A DETAIL
 OF WATER HEATER SIZE AND HOW THE ABOVE
 GOING TO HAPPEN INSIDE A CABINET WITH A
 SINK.
 4. PER SECTION 504.7 REQUIRED PAN. WHERE
 WATER HEATERS ARE INSTALLED ABOVE THE
 GROUND FLOOR SPACE A PAN SHALL BE
 INSTALLED FOR WATER HEATER. PLEASE
 INDICATE THIS ON PRINT. PER SECTION
 504.7.1 PAN DRAIN SIZE SHALL BE MINIMUM
 3/4" AND PER SECTION 504.7.2 SHALL
 TERMINATE NOT LESS THAN 6" AND NOT MORE
 THAN 24" ABOVE THE ADJACENT GROUND OF
 THE EXTERIOR OF BUILDING. PLEASE
 INDICATE THIS ON PRINT. PER SECTION
 504.6.1 INDICATE THE DISCHAREGE OF THE
 WATER HEATER RELIEF VALVE EITHER INTO
 THE HEATER PAN OR OUTSIDE OF THE
 BUILDING.
 5. ON SHEET 2/2 PLEASE NOTE THE 2" PVC
 UNDER SINK VENT CHANGED TO 2" PVC AIR
 ADMINTANCE VALVE PER SECTION 917. PLEASE
 SEE CORRECTED PLUMBING SHEET 2/2 FOR
 REFERENCE FOR RESUBMITTAL.
  
 END OF COMMENTS:
  