| Plan Review Notes For Permit 06041126 |
| Permit Number |
06041126 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-01 00:00:00 | | | | DENIED | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} INDICATE FEEDER TO SUB PANEL "B" ON | | | PANEL "A" SCHEDULE. | | | | | | 2} INDICATE FEEDER "B" SIZE ON THE | | | RISER. 215.5. | | | | | | 3} THE SUB PANEL CIRCUITS #21, 23, 25, | | | AND 22 HAVE OVERCURRENT PROTECTION TOO | | | HIGH FOR THE WIRE SIZE. SEE 310.16. | | | | | | 4} ELECTRICAL NOTE #7 REFERENCES THE | | | 1996 CODE, REMOVE IT OR CORRECT IT. | | | | | | 5} A RECEPTACLE NEEDS TO BE ADDED TO THE | | | | | | BEDROOM PER 210.52(A)(1). | | | | | | 6} THE BATH CIRCUIT MUST COMPLY WITH | | | 210.11(C)(3). | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|