Plan Review Notes
Plan Review Notes For Permit 06041126
Permit Number 06041126
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-01 00:00:00 
 DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE FEEDER TO SUB PANEL "B" ON
 PANEL "A" SCHEDULE.
  
 2} INDICATE FEEDER "B" SIZE ON THE
 RISER. 215.5.
  
 3} THE SUB PANEL CIRCUITS #21, 23, 25,
 AND 22 HAVE OVERCURRENT PROTECTION TOO
 HIGH FOR THE WIRE SIZE. SEE 310.16.
  
 4} ELECTRICAL NOTE #7 REFERENCES THE
 1996 CODE, REMOVE IT OR CORRECT IT.
  
 5} A RECEPTACLE NEEDS TO BE ADDED TO THE
  
 BEDROOM PER 210.52(A)(1).
  
 6} THE BATH CIRCUIT MUST COMPLY WITH
 210.11(C)(3).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  