Plan Review Notes
Plan Review Notes For Permit 06041053
Permit Number 06041053
Review Stop M
Sequence Number 1
Notes
Date Text
2006-05-03 00:00:00*** DENIED ***
 1) ARCHITECT SEAL IS MISSING FROM
 MECHANICAL PLAN PAGE M-1, SEE FAC
 61G1-16.003 USE OF SEAL.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved