| 2006-05-17 00:00:00 | ***** UNSAT ****** |
| | |
| | 1) NOTE: PLEASE SEE BUIDLIGN REVIEW |
| | COMMENTS AS THE SCOPE OF WORK MAY BE |
| | REQUIRED TO BE UNDER A GC. |
| | PLEASE ALSO SEE AS THE MECHANICAL |
| | CONTRACTOR'S APPLICATION IS ATTACHED, |
| | THE VAULE FOR THE ENTIRE SCOPE OF WORK |
| | UNDER THE "PRIME PERMIT" SHALL BE |
| | INCLUSIVE OF ALL TRADES. |
| | FBC 108.3 |
| | |
| | 2) NOTE: PLEASE COORELATE ALL CODES ON |
| | ELECTRICAL SHEETS WITH THE CURRENT CODES |
| | REFLECTED ON THE ARCHITECTURAL SHEETS. |
| | PLEASE SEE CODES REF IE: SFBC 1997, 1999 |
| | NFPA-72, ETC. |
| | PLEASE ADJUST. |
| | |
| | 3) NOTE: PLEASE SEE BOTH MECHNICAL AND |
| | ELECTRICAL ENGINEERED SHEETS AS THE |
| | "SEALED", ARE NO LONGER IN USE OR |
| | ACCEPTABLE PER FAC 61G15-23.001. |
| | PLEASE KNOW, AS OF FEB 04, THE FBPE'S |
| | CHANGED SUCH RULING AS TO ADOPT THAT ALL |
| | SEALS SHALL NO LONGER CONTAIN THE |
| | WORDING "CERTIFICATE" AND ALL SEALS MUST |
| | CONTAIN THE WORDING OF "LICENSE". PLEASE |
| | KNOW, AN EXTENSION WAS GRANTED TO DEC |
| | 31ST, 2005, HOWEVER ALL PERMIT |
| | APPLICATIONS, PLANS AFTER SUCH DATE |
| | SHALL CONTAIN THE NEW UPDATED SEALS. |
| | |
| | |
| | PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |