Plan Review Notes
Plan Review Notes For Permit 06040989
Permit Number 06040989
Review Stop E
Sequence Number 4
Notes
Date Text
2007-08-13 09:46:36 
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1}A GROUNDING ELECTRODE CONDUCTOR IS REQUIRED AT THE
 SEPARATE STRUCTURE (CABANA)PER 250.32, SIZED PER
 250.66 AND TIED TO FOOTER STEEL PER 250.53(A)(3). THE
 PERMIT SET OF PLANS HAD THIS SHOWN CORRECTLY, BUT HAS
 BEEN DELETED FROM THE REVISED PLAN SUBMITTED.
  
 2} THE PANEL AT THE CABANA IS REQUIRED TO HAVE A
 DISCONNECTING MEANS PER 225.31, LOCATED PER 225.32. THE
 CABANA PANEL NOW IS LISTED AS A "MAIN LUG" PANEL, NOT
 IN COMPLIANCE, UNLESS ANOTHER DISCONNECTING MEANS IS
 INSTALLED AS PER THE ABOVE LISTED ARTICLES. THE
 DISCONNECT MUST BE LOCATED ON THE PLAN AND ON THE RISER
 DIAGRAM.
  
 3} THERE IS NO OVERCURRENT PROTECTION FOR THE POOL
 PANEL FEEDER SHOWN IN THE METER/MAIN PANEL. INDICATE
 THE SIZE OF THE OCP PER 310.16 OR 310.15(B)(6).
  
 4} THE 10 K AHU LISTED ON THE PANEL SCHEDULE IS SHOWN
 ON A 50 AMP CIRCUIT BREAKER, AND DOES NOT COMPLY WITH
 THE REQUIREMENT FOR THE BRANCH CIRCUIT RATING OF 125%,
 424.3(B). THIS WAS A REDLINED ITEM ON THE PERMIT SET,
 NOW MUST BE CORRECTED AS THIS REVISION IS INTENDED AS
 THE LAST FOR RECORD RETENTION.
  
 5} GIVEN THE LOCATION OF THE AHU IN THE ATTIC,ALSO
 SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A)
 (3).
  
 6} THE LOAD CALCULATION FORMAT HAS BEEN CHANGED FROM
 THE ORIGINAL PERMITTED SET. PROVIDE LOAD CALCULATIONS
 PER ARTICLE 220 PART II, STANDARD OR PART III OPTIONAL,
 INDICATE METHOD USED.
  
 7} THE POOL EQUIPMENT LOAD HAS BEEN MOVED FROM THE
 CABANA PANEL TO THE HOUSE PANEL. THIS IS CONTRARY TO
 THE RISER WHICH NOW SHOWS A POOL PANEL. PLEASE PROVIDE
 A PANEL SCHEDULE FOR THE POOL PANEL SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC
 AS AMENDED.
  
 8} THE 200 AMP EXISTING HOUSE PANEL HAS NOW BEEN LISTED
 AS A MAIN LUG PANEL ON THE RISER. THAT PANEL IS LISTED
 AS A 200 AMP MAIN BREAKER PANEL ON THE PERMIT SET OF
 DRAWINGS. IF THAT PANEL WAS CHANGED IT WAS DONE OUTSIDE
 OF THE SCOPE OF THIS PERMIT. PLANS AND ANOTHER
 APPLICATION OR REVISION INDICATING THE INCREASED VALUE
 FOR LABOR AND MATERIAL, MUST BE SUBMITTED. 105.14 FBC
 AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  