Plan Review Notes
Plan Review Notes For Permit 06040989
Permit Number 06040989
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-25 00:00:00*********** UNSAT 2ND REVIEW **********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES DUE TO CHANGES
 AND ITEMS REVIEWED ON PLANS.
  
  
 1) NOTE: PLEASE SEE RISER SHOWS NEW 150A
 FEED TO CABANA NOW BEING FED DIRECTLY
 FROM THE EXISTING METER. PLEASE SEE
 MAINS ARE NOT GROUPED AS REQUIRED. PLANS
 SHOWS A MAIN AT THE CABANA AND A MCB
 PANEL???
 PLEASE KNOW, THE MCB IS REQUIRD AT
 CABANA, HOWEVER THE 150A MAIN DISCONNECT
 IS REQUIRED TO BE GROUPED WITH THE
 EXISTING MCB 200A PANEL.
 230.72.
 PLEASE SEE THE 150A DISCONNECT IS SHOWN
 AS WP ON RISER AND PLANS INDICATE AN
 ADDITIONAL DISCONNECT IN THE LAUNDRY RM
 WITH THE MCB PANEL.
  
 2) NOTE: PLEASE INDICATE THE SIZE OF THE
 NEW METER CAN AS THE EXISTING 200A METER
 CAN NO LONGER BE USED.
 215.5
  
 3) NOTE: PLEASE KNOW, BSAED ON THE
 INCREASE IN SERVICE SIZE AND THE
 INCREASED SEC'S, THE EXISTING GROUNDING
 ELECTRODE CONDUCTOR SHALL BE INCREASED
 PER 310.15B6,250.66 (#2 MIN).
  
 4) NOTE: PLEASE SEE MISSING GROUNDING
 ELECTRODE SYSTEM REQUIRED AT DETACHED
 BUILDING/CABANA. 250.32. NEW FOOTER
 STEEL, CWP ETC.
 250.50
  
 5) NOTE: PLEASE SEE RISER SHOWS
 "EQUIPMENT GROUNDING CONDUCTOR(S)" FROM
 THE METER TO THE FIRST MEANS OF
 DISCONNECT(S). PLEASE SEE 250.6,250.24B,
 AS THE EUP GRNDS ARE ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISC.
  
 6) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT.
 110.9,215.5
  
 7) NOTE: PLEASE SEE A DISCONNECTING
 MEANS FOR THE LTS IN OUTSIDE LOGGIA
 AREA. THE POWER FOR THESE LTS BEING
 SHOWN ON A 3-WAY FROM MAIN HOUSE SHALL
 ORIGINATE FROM CABANA PANEL.
 225.31,225.34
  
 8) NOTE: PLEASE SEE MISSING DISCONNECT
 FOR CU #1, 440.11
  
 9) NOTE: PLEASE SEE MISSING REQUIRED GFI
 RECEPT FOR CU. 210.63,210.8
  
 10) NOTE: PLEASE SEE MIN OCP FOR 10KW
 AHU SHALL BE SIZED AT A MIN OF 125%.
 424.3B
 PLEASE SEE THE EXISTING IN MAIN HOUSE
 SHALL BE VERIFIED AND CORRECTED IF NOT
 60A MIN.
 NFPA-73
  
 11) NOTE: PLEASE SEE LOAD CALCULATIONS
 INDICATES THE CU LOADS AS FIGURED IN,
 WHEN THIS SHOULD DICTATE THE AHU/HEAT
 LOADS.
 PLEASE CORRECT.220.31B, 220.21, ETC
  
 12) NOTE: PLEASE SEE THE "STUDIO" RM
 SHALL CONTAIN A SMOKE DETECTOR INSIDE
 AND OUTSIDE THIS ROOM. THIS IS
 CONSIDERED ADN ADAPTABLE SLEEPING RM.
 NFPA-72 11.5.1.1
  
 13) NOTE: PLEASE SEE 210.12B AND NOTE
 THE ARC FAULT PROTECTION WILL ALSO BE
 REQUIRED FOR THE "STUDIO RM", AS THIS IS
 ALSO CONSIDERED AN ADAPTABLE SLEEPING
 RM.
  
 14) NOTE: PLEASE SEE THE MIN LOAD/KW TO
 BE FIGAURED FOR DRYERS SHALL BE 5KW PER
 220.18. PLEASE ADJUST CABANA PANEL, MAIN
 HOUSE AND LOAD CALCS.
 215.5
  
 15) NOTE: PLEASE SEE PLANS INDICATE A
 "ON-DEMAND" WATER HEATER AT CABANA, YET
 THE LOAD INDICATED IS SHOWN AS 4.5KW ON
 PANEL SCHEDULE. PLEASE VERIFY SIZE OF
 UNIT BEING INSTALLED AND SUBMIT
 MANUFACTURE SPEC/CUT SHEETS FOR UNIT
 BEING INSTALLED. PLEASE KNOW THIS UNIT
 SHALL BE LISTED BY A NRTL.
 215.5
 FBC 106.1.2 ADMIN SECT.
  
 16) NOTE: PLEASE SEE FS 471.025, NO HAND
 DRAWN CHANGES MAY BE DONE ON PLANS WHICH
 ARE ALREADY SIGNED,DATED AND SEALED BY
 THE ENGINEER OF RECORD.
 (RISER, 100A TO 150A.)
  
 17) NOTE: PLEASE SEE BUIDLING REVIEW
 COMMENTS TO FOLLOW AS THE SUBMITTED
 "TRUSS" PACKAGE CONTAINS A "RUBBER
 STAMP"AND MANY OTHER SHEETS ARE SEALED
 "PHOTO-COPIES" OF THE "RUBBER STAMPED
 SIGNATURE" IN LEIU OF THE REQUIRED
 ORIGINAL SIGNATURE AND DATE FROM THE
 ENGINEER. FS 471.025
 PLEASE ALSO SEE SEAL IS NO LONGER
 ACCELTABLE PER FAC 61G15-23.001. THE
 WORDING IN SAID SEAL SHALL CONTAIN THE
 WORDING OF "LICENSE" AS "CERTIFICATE"
 CAN NOT BE USED.
 THIS RULE WAS PASSED IN FEB 04 AND THE
 EXTENSION GIVEN TO ENGINEERS WAS ONLY TO
 DEC 31ST, 2005.
  
 **THIS IS REQUIRED**
  
 18) NOTE: PLEASE SEE FS553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS. THIS IS ONLY
 A NOTE AT THIS TIME.
  
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 OR COMMENTS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]