| 2006-06-25 00:00:00 | *********** UNSAT 2ND REVIEW ********** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES DUE TO CHANGES |
| | AND ITEMS REVIEWED ON PLANS. |
| | |
| | |
| | 1) NOTE: PLEASE SEE RISER SHOWS NEW 150A |
| | FEED TO CABANA NOW BEING FED DIRECTLY |
| | FROM THE EXISTING METER. PLEASE SEE |
| | MAINS ARE NOT GROUPED AS REQUIRED. PLANS |
| | SHOWS A MAIN AT THE CABANA AND A MCB |
| | PANEL??? |
| | PLEASE KNOW, THE MCB IS REQUIRD AT |
| | CABANA, HOWEVER THE 150A MAIN DISCONNECT |
| | IS REQUIRED TO BE GROUPED WITH THE |
| | EXISTING MCB 200A PANEL. |
| | 230.72. |
| | PLEASE SEE THE 150A DISCONNECT IS SHOWN |
| | AS WP ON RISER AND PLANS INDICATE AN |
| | ADDITIONAL DISCONNECT IN THE LAUNDRY RM |
| | WITH THE MCB PANEL. |
| | |
| | 2) NOTE: PLEASE INDICATE THE SIZE OF THE |
| | NEW METER CAN AS THE EXISTING 200A METER |
| | CAN NO LONGER BE USED. |
| | 215.5 |
| | |
| | 3) NOTE: PLEASE KNOW, BSAED ON THE |
| | INCREASE IN SERVICE SIZE AND THE |
| | INCREASED SEC'S, THE EXISTING GROUNDING |
| | ELECTRODE CONDUCTOR SHALL BE INCREASED |
| | PER 310.15B6,250.66 (#2 MIN). |
| | |
| | 4) NOTE: PLEASE SEE MISSING GROUNDING |
| | ELECTRODE SYSTEM REQUIRED AT DETACHED |
| | BUILDING/CABANA. 250.32. NEW FOOTER |
| | STEEL, CWP ETC. |
| | 250.50 |
| | |
| | 5) NOTE: PLEASE SEE RISER SHOWS |
| | "EQUIPMENT GROUNDING CONDUCTOR(S)" FROM |
| | THE METER TO THE FIRST MEANS OF |
| | DISCONNECT(S). PLEASE SEE 250.6,250.24B, |
| | AS THE EUP GRNDS ARE ONLY INSTALLED |
| | AFTER THE FIRST MEANS OF DISC. |
| | |
| | 6) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT. |
| | 110.9,215.5 |
| | |
| | 7) NOTE: PLEASE SEE A DISCONNECTING |
| | MEANS FOR THE LTS IN OUTSIDE LOGGIA |
| | AREA. THE POWER FOR THESE LTS BEING |
| | SHOWN ON A 3-WAY FROM MAIN HOUSE SHALL |
| | ORIGINATE FROM CABANA PANEL. |
| | 225.31,225.34 |
| | |
| | 8) NOTE: PLEASE SEE MISSING DISCONNECT |
| | FOR CU #1, 440.11 |
| | |
| | 9) NOTE: PLEASE SEE MISSING REQUIRED GFI |
| | RECEPT FOR CU. 210.63,210.8 |
| | |
| | 10) NOTE: PLEASE SEE MIN OCP FOR 10KW |
| | AHU SHALL BE SIZED AT A MIN OF 125%. |
| | 424.3B |
| | PLEASE SEE THE EXISTING IN MAIN HOUSE |
| | SHALL BE VERIFIED AND CORRECTED IF NOT |
| | 60A MIN. |
| | NFPA-73 |
| | |
| | 11) NOTE: PLEASE SEE LOAD CALCULATIONS |
| | INDICATES THE CU LOADS AS FIGURED IN, |
| | WHEN THIS SHOULD DICTATE THE AHU/HEAT |
| | LOADS. |
| | PLEASE CORRECT.220.31B, 220.21, ETC |
| | |
| | 12) NOTE: PLEASE SEE THE "STUDIO" RM |
| | SHALL CONTAIN A SMOKE DETECTOR INSIDE |
| | AND OUTSIDE THIS ROOM. THIS IS |
| | CONSIDERED ADN ADAPTABLE SLEEPING RM. |
| | NFPA-72 11.5.1.1 |
| | |
| | 13) NOTE: PLEASE SEE 210.12B AND NOTE |
| | THE ARC FAULT PROTECTION WILL ALSO BE |
| | REQUIRED FOR THE "STUDIO RM", AS THIS IS |
| | ALSO CONSIDERED AN ADAPTABLE SLEEPING |
| | RM. |
| | |
| | 14) NOTE: PLEASE SEE THE MIN LOAD/KW TO |
| | BE FIGAURED FOR DRYERS SHALL BE 5KW PER |
| | 220.18. PLEASE ADJUST CABANA PANEL, MAIN |
| | HOUSE AND LOAD CALCS. |
| | 215.5 |
| | |
| | 15) NOTE: PLEASE SEE PLANS INDICATE A |
| | "ON-DEMAND" WATER HEATER AT CABANA, YET |
| | THE LOAD INDICATED IS SHOWN AS 4.5KW ON |
| | PANEL SCHEDULE. PLEASE VERIFY SIZE OF |
| | UNIT BEING INSTALLED AND SUBMIT |
| | MANUFACTURE SPEC/CUT SHEETS FOR UNIT |
| | BEING INSTALLED. PLEASE KNOW THIS UNIT |
| | SHALL BE LISTED BY A NRTL. |
| | 215.5 |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 16) NOTE: PLEASE SEE FS 471.025, NO HAND |
| | DRAWN CHANGES MAY BE DONE ON PLANS WHICH |
| | ARE ALREADY SIGNED,DATED AND SEALED BY |
| | THE ENGINEER OF RECORD. |
| | (RISER, 100A TO 150A.) |
| | |
| | 17) NOTE: PLEASE SEE BUIDLING REVIEW |
| | COMMENTS TO FOLLOW AS THE SUBMITTED |
| | "TRUSS" PACKAGE CONTAINS A "RUBBER |
| | STAMP"AND MANY OTHER SHEETS ARE SEALED |
| | "PHOTO-COPIES" OF THE "RUBBER STAMPED |
| | SIGNATURE" IN LEIU OF THE REQUIRED |
| | ORIGINAL SIGNATURE AND DATE FROM THE |
| | ENGINEER. FS 471.025 |
| | PLEASE ALSO SEE SEAL IS NO LONGER |
| | ACCELTABLE PER FAC 61G15-23.001. THE |
| | WORDING IN SAID SEAL SHALL CONTAIN THE |
| | WORDING OF "LICENSE" AS "CERTIFICATE" |
| | CAN NOT BE USED. |
| | THIS RULE WAS PASSED IN FEB 04 AND THE |
| | EXTENSION GIVEN TO ENGINEERS WAS ONLY TO |
| | DEC 31ST, 2005. |
| | |
| | **THIS IS REQUIRED** |
| | |
| | 18) NOTE: PLEASE SEE FS553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS. THIS IS ONLY |
| | A NOTE AT THIS TIME. |
| | |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |