Plan Review Notes For Permit 06040989
Permit Number 06040989
Review Stop P
Sequence Number 1
Notes
Date Text
2006-05-18 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW FOR A PERMIT:
  
 1. INDICATE ON SHEET A-1 AND SHEET A-2
 THE OUTSIDE SHOWER DRAIN PIPE, DRAIN
 PIPE SIZE AND WHERE IT IS DRAINING TO.
 2. ON SHEET A-6 PLUMBING RISER DIAGRAM
 THERE INDICATES A FUTURE OUTDOOR SINK.
 PLEASE INDICATE ON SHEET A-2 THE
 LOCATION OF THE FUTURE OUTDOOR SINK.
 3. ON SHEET A-6 PLUMBING RISER DIAGRAM
 THE FOLLOWING IS REQUIRED FOR THE FUTURE
 OUTDOOR SINK.
 (A) 704.4 FUTURE FIXTURES. DRAINAGE
 PIPING FOR FUTURE FIXTURES SHALL
 TERMINATE WITH AN APPROVED CAP OR PLUG.
 (B) 905.6 VENT FOR FUTURE FIXTURES.
 WHERE THE DRAINAGE PIPING HAS BEEN
 ROUGHED-IN FOR FUTURE FIXTURES, A
 ROUGH-IN CONNECTION FOR A VENT SHALL BE
 INSTALLED. THE VENT SIZE SHALL BE NOT
 LESS THAN ONE-HALF THE DIAMETER OF THE
 ROUGH-IN DRAIN TO BE SERVED. THE VENT
 ROUGH-IN SHALL CONNECT TO THE VENT
 SYSTEM, OR SHALL BE VENTED BY OTHER
 MEANS AS PROVIDED FOR IN THIS CHAPTER.
 THE CONNECTION SHALL BE IDENTIFIED TO
 INDICATE THAT IT IS A VENT.
 4. ON SHEET A-6 PLUMBING RISER DIAGRAM
 THE BRANCH DRAIN AND THE DRAINAGE STACK
 ARE SIZED INCORRECTLY FOR THE WASHING
 MACHINE, THE FOLLOWING IS REQUIRED FOR
 THE SIZING OF THE WASHING MACHINE.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE
 INDIVIDUALLY TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING (NOTE: THE INDICATION OF THE
 STAND PIPE ON CORRECTED PLBG. RISER
 DIAGRAM)
 5. PLEASE NOTE THE CORRECTED CLEANOUT
 LOCATIONS ON A-6 PLBG. RISER DIAGRAM AND
 THE FOLLOWING CODE REQUIREMENTS FOR
 CLEANOUTS
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
 (B) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM).
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.(NOTE THE
 LOCATION OF THE WASHING MACHINE
 CLEANOUT)
 6. PLEASE NOTE THE FOLLOWING WILL BE
 REQUIRED FOR THE GAS DRYER AND GAS WATER
 HEATER.
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL INSPECTION.
  
 END OF COMMENTS:
  