Plan Review Notes
Plan Review Notes For Permit 06040989
Permit Number 06040989
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-16 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SHEET E-1.1 SHOWS A NEW 350 AMP
 SERVICE. SHEET E-1.2 RISER HAS A 200 AMP
 SERVICE, PLEASE CORRELATE. SEE 225.31
 FOR REQUIREMENTS FOR THE DISCONNECT AT
 THE CABANA, AND 250.32 FOR GROUNDING
 REQUIREMENTS OF SAME.
  
 2} THE #6 FEEDERS TO THE INTENDED 100
 AMP CABANA PANEL ARE TOO SMALL AND MUST
 COMPLY WITH THE MINIMUM SIZE IN TABLE
 310.15(B)(6).
  
 3} THE PANEL LOCATION IN THE CABANA IS
 IN VIOLATION OF 110.26. THE WASHER IS IN
 THE CLEAR WORK SPACE.
  
 4} THE BATHROOM MUST COMPLY WITH
 210.52(D), 3' SPACING, AND 210.11(C)(3),
 DEDICATED CIRCUIT.
  
 5} IF THE SMALL APPLIANCE CIRCUIT IS
 INDICATING THERE IS A KITCHEN IN THE
 CABANA, THEN IT MUST HAVE TWO, PER
 210.11(C)(1), AND ENTERED INTO THE
 CALCULATIONS.
  
 6} THE GENERAL LIGHTING CIRCUITS IN THE
 CABANA PANEL SCHEDULE LIST # 14
 CONDUCTORS ON A 20 AMPERE BREAKER IN
 VIOLATION OF 310.16.
  
 7} THE RISER INDICATES THAT THE CABANA
 PANEL IS BEING FED FROM THE HOUSE PANEL,
 BUT IT IS NOT LISTED IN THE HOUSE PANEL
 SCHEDULE.
  
 8} PLEASE USE THE LARGER LOAD WHEN
 COMPUTING THE HEAT-A/C LOADS, THEPER
 220.21. ALSO SEE 220.30 OR 220.31(B),
 INDICATE WHICH ARTICLE IS USED FOR THE
 CALCULATIONS.
  
 9} SEE ARTICLE 210.8(A)(7) FOR GFI
 REQUIREMENTS AT WET BAR/SINK.
  
 10} THE ENGINEER OF RECORD SEALED THE
 PLANS WITH ASEAL THAT IS NO LONGER
 VALID. SEE 61G15-23.002 FAC.
  
 PLEASE PROVIDE WRITTEN RESPONSES TO ALL
 COMMENTS TO EXPEDITE PLAN REVIEW OF THE
 RESUB.
  
 IF THERE ARE QUESTIONS , PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026