| 2006-05-16 00:00:00 | |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} SHEET E-1.1 SHOWS A NEW 350 AMP |
| | SERVICE. SHEET E-1.2 RISER HAS A 200 AMP |
| | SERVICE, PLEASE CORRELATE. SEE 225.31 |
| | FOR REQUIREMENTS FOR THE DISCONNECT AT |
| | THE CABANA, AND 250.32 FOR GROUNDING |
| | REQUIREMENTS OF SAME. |
| | |
| | 2} THE #6 FEEDERS TO THE INTENDED 100 |
| | AMP CABANA PANEL ARE TOO SMALL AND MUST |
| | COMPLY WITH THE MINIMUM SIZE IN TABLE |
| | 310.15(B)(6). |
| | |
| | 3} THE PANEL LOCATION IN THE CABANA IS |
| | IN VIOLATION OF 110.26. THE WASHER IS IN |
| | THE CLEAR WORK SPACE. |
| | |
| | 4} THE BATHROOM MUST COMPLY WITH |
| | 210.52(D), 3' SPACING, AND 210.11(C)(3), |
| | DEDICATED CIRCUIT. |
| | |
| | 5} IF THE SMALL APPLIANCE CIRCUIT IS |
| | INDICATING THERE IS A KITCHEN IN THE |
| | CABANA, THEN IT MUST HAVE TWO, PER |
| | 210.11(C)(1), AND ENTERED INTO THE |
| | CALCULATIONS. |
| | |
| | 6} THE GENERAL LIGHTING CIRCUITS IN THE |
| | CABANA PANEL SCHEDULE LIST # 14 |
| | CONDUCTORS ON A 20 AMPERE BREAKER IN |
| | VIOLATION OF 310.16. |
| | |
| | 7} THE RISER INDICATES THAT THE CABANA |
| | PANEL IS BEING FED FROM THE HOUSE PANEL, |
| | BUT IT IS NOT LISTED IN THE HOUSE PANEL |
| | SCHEDULE. |
| | |
| | 8} PLEASE USE THE LARGER LOAD WHEN |
| | COMPUTING THE HEAT-A/C LOADS, THEPER |
| | 220.21. ALSO SEE 220.30 OR 220.31(B), |
| | INDICATE WHICH ARTICLE IS USED FOR THE |
| | CALCULATIONS. |
| | |
| | 9} SEE ARTICLE 210.8(A)(7) FOR GFI |
| | REQUIREMENTS AT WET BAR/SINK. |
| | |
| | 10} THE ENGINEER OF RECORD SEALED THE |
| | PLANS WITH ASEAL THAT IS NO LONGER |
| | VALID. SEE 61G15-23.002 FAC. |
| | |
| | PLEASE PROVIDE WRITTEN RESPONSES TO ALL |
| | COMMENTS TO EXPEDITE PLAN REVIEW OF THE |
| | RESUB. |
| | |
| | IF THERE ARE QUESTIONS , PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |