| 2006-08-10 00:00:00 | ******DENIED 2ND TIME****** |
| | REFERENCE: FBC-2004 SEC. 424.2 OR |
| | FBRC-2004 SEC.4101 SWIMMING POOLS. |
| | FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING INFORMATION IS STILL |
| | REQUIRED FOR PLUMBING PLAN REVIEW: |
| | |
| | 1. THE SHEETS SUBMITTED NEED THE |
| | FOLLOWING PER FLORIDA ADMINISTRATIVE |
| | CODE AND STATE STATUTE. |
| | A PROFESSIONAL ENGINEER SHALL SIGN HIS |
| | NAME AND AFFIX HIS SEAL TO ALL PLANS, |
| | SPECIFICATIONS, REPORTS AND FINAL BID |
| | DOCUMENTS PROVIDED TO THE OWNER OR THE |
| | OWNER'S REPRESENTATIVE, OR OTHER DOCU- |
| | MENTS PREPARED OR ISSUED BY SAID REGIS- |
| | TRANT AND BEING FILED FOR PUBLIC RECORD. |
| | THE DATE THAT THE SIGNATURE AND SEAL IS |
| | AFFIXED AS PROVIDED HEREIN SHALL BE EN- |
| | TERED ON SAID PLANS, SPECIFICATIONS, RE- |
| | PORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL |
| | ENGINEER, FAC 61G15-23.002(1) |
| | FS 471.025 |
| | EACH SHEET OF PLANS AND PRINTS WHICH |
| | MUST BE SEALED UNDER THE PROVISIONS OF |
| | CHAPTER 471 SHALL BE SEALED, SIGNED AND |
| | DATED BY THE PROFESSIONAL ENGINEER IN |
| | RESPONSIBLE CHARGE. FAC 61G15-23.002(2) |
| | FS 471.025 |
| | ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| | SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| | EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME AND LICENSE NUMBER, AS WELL |
| | AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. A TITLE BLOCK |
| | WILL SATISFY THIS REQUIREMENT. FAC |
| | 61G15-23.002(2) - FS 471.025 |
| | 2. PLEASE SUBMIT POOL SPECIFICATIONS |
| | WITH PRINT. PLEASE REFERENCE THE |
| | ATTACHED EXAMPLE OF POOL SPECIFICATIONS |
| | FOR RESUBMITTAL. |
| | 3. PER FBC-2004 SEC. 424.6.6 OR FBC-2004 |
| | RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT |
| | PROTECTION FOR SUCTION INLETS. PLEASE |
| | SUBMIT AN ENGINEERED TABLE FOR "VENT |
| | PIPE MAXIMUM LENGTH" INDICATING PUMP |
| | SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH |
| | OF THE 1", 1-1/2" PVC VENT PIPE, FROM |
| | WHERE IT STARTS TO WHERE IT ENDS UP, |
| | COMPLYING WITH THE THREE SECOND RELEASE. |
| | PLEASE REFERENCE THE ATTACHED EXAMPLE OF |
| | A VENT TABLE FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | 4. FBC-2004 SEC. 424.2.7.2, OR FBCR-2004 |
| | SEC. R4101.7.2 PUMPS AND EQUIPMENT SHALL |
| | BE MOUNTED ON A SUBSTANTIAL BASE IN A |
| | MANNER THAT WILL ELIMINATE STRAIN ON |
| | PIPING.SLAB SHALL BE A NOMINAL 4" |
| | THICK. (DETAIL REQUIRED PLEASE ADD TO |
| | PRINT) |
| | 5. FBC-2004 SEC. 424.2.9, OR FBCR-2004 |
| | SEC. R4101.9 WATER SUPPLY, LOCAL ORD. |
| | #2853-95, BACKFLOW REQUIRED ON WATER |
| | SERVICE.(ADD TO NOTES) |
| | 6. FBC-2004 SEC. 424.2.12.1, OR |
| | FBCR-2004 SEC. R4101.12.1 PRESSURE |
| | TESTS. PER MANUFACTURE RECOMMENDATIONS, |
| | NO AIR TEST SHALL BE APPROVED FOR PVC |
| | PIPE AND FITTINGS. (ADD TO NOTES) |
| | 7. FBC-2004 SEC. 424.2.13.2, OR |
| | FBCR-2004 SEC.R4101.13.2 JOINTS AND |
| | CONNECTIONS, FBC PLMG SEC 605.21, PURPLE |
| | PRIMER REQUIRED ON PVC PIPING.(ADD TO |
| | NOTES) |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |