| Date |
Text |
| 2006-05-03 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 424.2 SWIMMING POOLS |
| | |
| | PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| | SUBMITTALS TO REFLECT THE FOLLOWING |
| | INFORMATION REQUIRED FOR PLAN REVIEW: |
| | |
| | 1) FBC-2004 SEC 424.2.6.6 ENTRAPMENT |
| | PROTECTION FOR SUCTION INLETS. (DETAIL) |
| | 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE |
| | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL |
| | NUMBER AND MANUF INFO FOR VAC LOCK. |
| | (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES) |
| | 3) FBC-2004424.2.6.6.3 (1,2,3) ENTRAP- |
| | MENT AVOIDANCE. (DETAIL) |
| | 4) FBC-2004424.2.6.6.4 MINIMUM OF TWO |
| | SUCTION INLETS SHALL BE PROVIDED FOR EA |
| | PUMP. SEPARATED BY A MINIMUM OF 3 FEET |
| | OR LOCATED ON TWO DIFFERENT PLANES. |
| | (DETAIL) |
| | 5) FBC-2004424.2.6.6.5 WHERE PROVIDED, |
| | THE VACUUM OR PRESSURE CLEANER FITTING |
| | SHALL BE LOCATED AT LEAST 6" AND NOT |
| | GREATER THAN 12" BELOW THE MINIMUM OPER- |
| | ATING WATER LEVEL OR AS AN ATTACHMENT TO |
| | THE SKIMMER. (NEED MANUFACTURE CUT SHEET |
| | OF VACUUM OR PRESSURE CLEANING FITTING |
| | OR MAKE AND MODEL NUMBER ADDED TO PRINT) |
| | 6) FBC-2004 424.2.7.2 PUMPS AND |
| | EQUIPMENT SHALL BE MOUNTED ON A |
| | SUBSTANTIAL BASE IN A MANNER THAT WILL |
| | ELIMINATE STRAIN ON PIPING.SLAB SHALL |
| | BE A NOMINAL 4" THICK. (INDICATE SLAB |
| | THICKNESS ONDETAIL) |
| | 7) FBC-2004 SEC. 424.2.9 WATER SUPPLY, |
| | LOCAL ORD. #2853-95, BACKFLOW REQUIRED |
| | ON WATER SERVICE. (ADD TO NOTES) |
| | 8) FBC-2004 424.2.12.1 PRESSURE TESTS. |
| | PER MANUFACTURE RECOMMENDATIONS, NO AIR |
| | TEST SHALL BE APPROVED FOR PVC PIPE AND |
| | FITTINGS. (ADD TO NOTES) |
| | 9) FBC-2004 SEC. 424.2.13.2 JOINTS AND |
| | CONNECTIONS, FBC-2004 PLMG. SEC. 605.21, |
| | PURPLE PRIMER REQUIRED ON PVC PIPE AND |
| | FITTINGS. (ADD TO NOTES) |
| | 10) ON SHEET 2 "POOL DATA EQUIPMENT" |
| | INDICATES "QTY RETURNS:4", BUT ON SHEET |
| | 1 THERE APPEARS TO BE ONLY 3 RETURNS. |
| | PLEASE CORRELATE. |
| | |
| | NOTE: ON SHEET 2 PIPING SCHEMATIC THERE |
| | INDICATES AN "OPTIONAL HEATER" IF THERE |
| | IS A HEATER THE FOLLOWING SHALL APPLY, |
| | IF THERE ISN'T A HEATER PLEASE REMOVE |
| | OPTIONAL HEATER FROM PRINT: |
| | 11) FBC-2004 424.2.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. (MANUFACTURE |
| | CUT SHEETS REQUIRED) |
| | 12) FBC-2004 424.2.14.2 WATER RETENTION, |
| | PROVIDE A POSITIVE MEANS OF RETAINING |
| | WATER IN HEATER WHEN PUMP IS SHUT OFF. |
| | (MANUFACTURE CUT SHEETS REQUIRED) |
| | 13) FBC-2004 424.2.14.4 CONNECTIONS, ALL |
| | WATER HEATING EQUIPMENT SHALL BE |
| | INSTALLED WITH FLANGES OR UNION |
| | CONNECTIONS ADJACENT TO THE HEATER. (ADD |
| | TO NOTES) |
| | 14) FBC-2004 424.2.15 GAS PIPING SHALL |
| | COMPLY WITH FBC FUEL GAS. SEPERATE PLANS |
| | AND PERMIT REQUIRED. (ADD TO NOTES) |
| | 15) ADD HEATER TO "POOL DATA EQUIPMENT" |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |