Plan Review Notes
Plan Review Notes For Permit 06040969
Permit Number 06040969
Review Stop P
Sequence Number 1
Notes
Date Text
2006-05-03 00:00:00******DENIED******
 REFERENCE: FBC-2004 424.2 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATION REQUIRED FOR PLAN REVIEW:
  
 1) FBC-2004 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 3) FBC-2004424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL)
 4) FBC-2004424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL)
 5) FBC-2004424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER. (NEED MANUFACTURE CUT SHEET
 OF VACUUM OR PRESSURE CLEANING FITTING
 OR MAKE AND MODEL NUMBER ADDED TO PRINT)
 6) FBC-2004 424.2.7.2 PUMPS AND
 EQUIPMENT SHALL BE MOUNTED ON A
 SUBSTANTIAL BASE IN A MANNER THAT WILL
 ELIMINATE STRAIN ON PIPING.SLAB SHALL
 BE A NOMINAL 4" THICK. (INDICATE SLAB
 THICKNESS ONDETAIL)
 7) FBC-2004 SEC. 424.2.9 WATER SUPPLY,
 LOCAL ORD. #2853-95, BACKFLOW REQUIRED
 ON WATER SERVICE. (ADD TO NOTES)
 8) FBC-2004 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 9) FBC-2004 SEC. 424.2.13.2 JOINTS AND
 CONNECTIONS, FBC-2004 PLMG. SEC. 605.21,
 PURPLE PRIMER REQUIRED ON PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 10) ON SHEET 2 "POOL DATA EQUIPMENT"
 INDICATES "QTY RETURNS:4", BUT ON SHEET
 1 THERE APPEARS TO BE ONLY 3 RETURNS.
 PLEASE CORRELATE.
  
 NOTE: ON SHEET 2 PIPING SCHEMATIC THERE
 INDICATES AN "OPTIONAL HEATER" IF THERE
 IS A HEATER THE FOLLOWING SHALL APPLY,
 IF THERE ISN'T A HEATER PLEASE REMOVE
 OPTIONAL HEATER FROM PRINT:
 11) FBC-2004 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 CUT SHEETS REQUIRED)
 12) FBC-2004 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN HEATER WHEN PUMP IS SHUT OFF.
 (MANUFACTURE CUT SHEETS REQUIRED)
 13) FBC-2004 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO THE HEATER. (ADD
 TO NOTES)
 14) FBC-2004 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPERATE PLANS
 AND PERMIT REQUIRED. (ADD TO NOTES)
 15) ADD HEATER TO "POOL DATA EQUIPMENT"
  
 END OF COMMENTS:
  