2006-05-08 00:00:00 
  
 FAILED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE DISCONNECTING MEANS PER
 230.70. THE PANEL IS NOTED AS BEING A
 MLO. ALSO SEE 230.71.
  
 2} LOCATE THE NEW 200 AMP PANEL ON THE
 PLAN.
  
 3} PLEASE PROVIDE A PANEL SCHEDULE
 INDICATING BRANCH CIRCUIT WIRE SIZE AND
 OVERCURRENT PROTECTION SO THAT
 COMPLIANCE CAN BE REVIEWED.
  
 4} RECEPTACLES MUST BE ADDED TO BOTH
 BEDROOMS FOR SPACING REQUIREMENTS PER
 210.52(A)(1).
  
 5} PLEASE SEE THE ENGINEERS SEAL NEEDS
 UPDATED TO COMPLY WITH 61G15-23.002.FAC.
  