| Plan Review Notes For Permit 06040960 |
| Permit Number |
06040960 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-08 00:00:00 | | | | | | | FAILED | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} INDICATE DISCONNECTING MEANS PER | | | 230.70. THE PANEL IS NOTED AS BEING A | | | MLO. ALSO SEE 230.71. | | | | | | 2} LOCATE THE NEW 200 AMP PANEL ON THE | | | PLAN. | | | | | | 3} PLEASE PROVIDE A PANEL SCHEDULE | | | INDICATING BRANCH CIRCUIT WIRE SIZE AND | | | OVERCURRENT PROTECTION SO THAT | | | COMPLIANCE CAN BE REVIEWED. | | | | | | 4} RECEPTACLES MUST BE ADDED TO BOTH | | | BEDROOMS FOR SPACING REQUIREMENTS PER | | | 210.52(A)(1). | | | | | | 5} PLEASE SEE THE ENGINEERS SEAL NEEDS | | | UPDATED TO COMPLY WITH 61G15-23.002.FAC. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|