Plan Review Notes
Plan Review Notes For Permit 06040960
Permit Number 06040960
Review Stop B
Sequence Number 1
Notes
Date Text
2006-05-23 00:00:00 
  
 DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC. PERMIT FEES
 WILL BE ADJUSTED ACCORDINGLY
  
 3) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 4) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
  
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
 NOTE: REQUIRED FOR WINDOWS, DOORS,
 ROOFING, SHUTTERS WHERE OPENINGS ARE NOT
 IMPACT RATED AND WOOD CONNECTOR/STRAPS
  
 5) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 6) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION
  
 7) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 8) SUBMIT A SIGNED AND SEALED COPY OF
 SURVEY PER 106.3.4 FBC* THAT IS LESS
 THAN 1 YR OLD ALSO PROVIDE A SITE PLAN
 WITH THE DRAWINGS PER 106.3.5 FBC*
  
 9) SUBMIT A SOIL REPORT PER R401.4 WHERE
 SOILS ARE DEEMED TO BE QUESTIONABLE
  
 10) CORRECT TABLE REFERENCES ON PAGE 1,
 ALSO COMPONANT AND CLADDING PRESSURE
 SCHEDULE HAS 2 END ZONES
  
 11) SEE SIMPSON STRAP SCHEDULE ON PAGE 4
  
 OUTLOOKER HANGER IS SPEC'D AS LUS310
 THAT HANGER IS FOR 3X10 PLEASE CLARIFY
  
 12) SHOW/STATE VENTILATION METHOD FOR
 ROOF SYSTEM ON 1/5 PAGE 5
  
 13) CONFIRM DEPTH OF TRUSS AND OUTLOOKER
 MATCH UP FOR HANGER AND WALL ATTACHMENT
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  