| 2007-07-02 09:43:39 | FBC 2004 CODE FAMILY W/2005 REVISIONS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS FOR THE PURPOSE OF |
| | CONTINUITY. |
| | |
| | 1. OK |
| | |
| | 2. REVISION 6 IS THE LAST REVISION THAT WAS STAMPED AND |
| | FILED AT THIS OFFICE, BUT THE SUBMITTED PLANS HAVE |
| | DELTAS FOR LATER REVISIONS WHICH ARE NOT CLEARLY MARKED |
| | (NO CLOUDS). PLEASE CLEARLY INDICATE ON PLANS EVERY |
| | CHANGE WHICH HAS TAKEN PLACE AFTER REVISION 6 |
| | (11-10-06). ALSO, SF-2 ON FAN SCHEDULE INDICATES REMARK |
| | #1 APPLIES. HOWEVER, SF-2 DOES NOT OCCUR ON FLOORS 2, |
| | 3, 4 AND 5 AS REMARK #1 STATES. IT IS ONLY ON THE 5TH |
| | FLOOR. SEF-1A AND SEF-1B DO NOT APPEAR ON FLOOR PLANS |
| | OR RISER DIAGRAM (H1.17 AND H2.04), RATHER, THERE IS |
| | ONLY ONE SEF 1 SHOWN. PLEASE CLARIFY AND COORDINATE |
| | FLOOR PLANS WITH SCHEDULES. |
| | |
| | 3. PLEASE REMOVE THE ?18? MIN.? NOTATION FROM DETAIL |
| | 25. IT MAY OR MAY NOT BE CODE COMPLIANT DEPENDING ON |
| | THE WIDTH OF THE EQUIPMENT. PERHAPS A NOTE REFERENCING |
| | DETAIL 50 ON H0.04 FOR REQUIRED EQUIPMENT HEIGHTS WOULD |
| | BE MORE APPROPRIATE. ALSO, NO INFORMATION OR DETAIL |
| | COULD BE FOUND IN REVISION 15 STRUCTURAL PLANS |
| | REGARDING WIND LOADS AS WAS INDICATED IN THE COMMENT |
| | RESPONSE LETTER. |
| | |
| | 4. NO INFORMATION COULD BE FOUND ON REVISION 15 |
| | STRUCTURAL PLANS REGARDING WIND LOADS OR ATTACHMENT |
| | DETAILS RELATED TO ROOFTOP DUCTWORK. ALSO, A NOTE |
| | REFERENCING DETAIL 50 FOR REQUIRED CLEARANCES WOULD BE |
| | APPROPRIATE. |
| | |
| | COMMENTS 5 THROUGH 8: OK |
| | |
| | 9. THE12X16 DUCT WHICH WAS REVISED TO 18X8 IS STILL |
| | MISSING A FIRE DAMPER IN THE DUCT RUNNING FROM |
| | ELECTRICAL ROOM (105) INTO RETAIL 1 (106). PLEASE SHOW |
| | OPENING PROTECTIVE AS REQUIRED BY FBC,M 607.5. |
| | |
| | 10. H1.06 THROUGH H1.16 STILL SHOW A NOTE STATING THAT |
| | A 2? CONDENSATE DRAIN IS TO BE ROUTED TO AND DISCHARGE |
| | INTO A FLOOR DRAIN. PLEASE CLARIFY AND COORDINATE WITH |
| | PLUMBING PLANS. |
| | |
| | COMMENTS 11 THROUGH 19: OK |
| | |
| | 20.THE DUCT RELATED TO SF-2 FOR ELEVATOR LOBBIES |
| | TRAVELS FROM THE 5TH FLOOR DOWN TO THE 2ND FLOOR. AS |
| | SUCH, A SHAFT ENCLOSURE IS REQUIRED PER FBC 707.2. ALL |
| | SHAFT PENETRATIONS SHALL BE PROTECTED PER FBC,M |
| | 607.5.5.1. THE INTAKE LOCATION FOR SF-2 SHALL BE |
| | LOCATED A MINIMUM OF 10 FEET FROM ANY HAZARDOUS OR |
| | NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING |
| | VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS? |
| | FBC,M 401.5.1 |
| | |
| | COMMENTS 21 AND 22: OK |
| | |
| | 23. PLEASE SEE COMMENT #20 RELATED TO ELEVATOR LOBBY |
| | VENTILATION. |
| | |
| | COMMENTS 24 THROUGH 31: OK |
| | |
| | 32. PLEASE SEE COMMENT #20 REGARDING ELEVATOR LOBBY |
| | VENTILATION. |
| | |
| | 33. SMOKE CONTROL SYSTEM: |
| | NOTE: THE ADDITION OF THE SMOKE CONTROL SYSTEM DOES NOT |
| | ONLY PROVIDE COMPLIANCE WITH FBC 909, IT ALSO PROVIDES |
| | COORDINATION WITH THE PERMIT SET OF FIRE ALARM PLANS |
| | WHICH HAVE CALLED FOR A SMOKE CONTROL PANEL WITH HOA IN |
| | THE FIRE COMMAND ROOM (SEE FA1.01) SINCE AT LEAST |
| | REVISION #6 (DATED 11-10-06). THE FOLLOWING ARE |
| | COMMENTS RELATED TO THE SMOKE CONTROL SYSTEM AS |
| | SUBMITTED: |
| | |
| | 1) THE 3 COPIES OF THE SMOKE CONTROL SYSTEM NARRATIVE |
| | REPORT SHALL BE SIGNED AND SEALED BY THE DESIGNER(S) OF |
| | RECORD. |
| | 2) SUBMITTAL OF THE SMOKE CONTROL NARRATIVE IS NOTED. |
| | HOWEVER, PLEASE INCLUDE SEQUENCE OF OPERATIONS AND |
| | CONTROL DETAILS ON HVAC AND FIRE ALARM PLANS AS NEEDED |
| | TO CLEARLY DEMONSTRATE THE SCOPE OF WORK REQUIRED FOR A |
| | FULLY FUNCTIONAL AND CODE COMPLIANT SMOKE CONTROL |
| | SYSTEM. FBC 106.1.1 AND 106.3.5.1.1 |
| | |
| | A: FLOORS 6-16 |
| | |
| | (B) STAIR PRESSURIZATION SHALL BE MINIMUM 0.15? WC AND |
| | A MAXIMUM OF 0.35? WC IN THE SHAFT RELATIVE TO THE |
| | BUILDING MEASURED WITH ALL STAIRWAY DOORS CLOSED UNDER |
| | MAXIMUM ANTICIPATED STACK PRESSURES. THE NOTE ON STAIR |
| | 1 RELIEF DAMPER (H1.18) WILL ALSO NEED TO BE CORRECTED. |
| | STAIR 2 RELIEF DAMPER COULD NOT BE LOCATED ON PLANS. BY |
| | WHAT MEANS IS THE PRESSURE TO BE BALANCED IN THIS |
| | SHAFT? |
| | (D) PLEASE INDICATE IN SEQUENCE SPECIFICALLY WHICH FSD |
| | WILL OPEN WHEN ALL OTHER FSD?S WILL CLOSE. |
| | (F) PLEASE SEE COMMENT #2 REGARDING SEF-1 DESIGNATION |
| | ON EQUIPMENT SCHEDULE (H0.02). |
| | |
| | B: FIRST FLOOR MAIN LOBBY |
| | |
| | (B) PLEASE INDICATE IN SEQUENCE SPECIFICALLY WHICH FSD |
| | WILL OPEN WHEN ALL OTHER FSD?S WILL CLOSE. THERE IS NO |
| | FSD SHOWN ON SEF-2 DUCT WHERE IT EXITS THE SHAFT ON |
| | FLOOR PLAN (H1.01) OR RISER 9 DIAGRAM (H2.04). WHAT IS |
| | THE PURPOSE OF OPENING THE MOTORIZED DAMPER FOR SEF-1 |
| | IN THIS PART OF THE SEQUENCE? IT ONLY SERVES THE UPPER |
| | FLOORS. |
| | (C) NO ASSOCIATED FSD IS SHOWN ON PLANS. SEF-2 ACCESS |
| | DOOR (H1.05), IS THERE A STEEL GIRDER OR BEAM WHICH |
| | WILL INTERFERE WITH ACCESS? SEF-2 DISCHARGES ADJACENT |
| | TO THE SIDE OF THE PARKING GARAGE WHICH IS OPEN TO THE |
| | OUTDOORS. WHAT WILL THE STATUS OF GARAGE EXHAUST FANS |
| | (PF-1 THROUGH PF-12 AND SF-1) BE WHEN SEF-2 IS ACTIVE |
| | (SINCE THAT LOCATION IS THE SOURCE OF MAKE-UP AIR FOR |
| | THESE FANS)? ARE THERE PROVISIONS TO ENSURE PF?S AND |
| | SF-1 WILL NOT DRAW SMOKE INTO PARKING GARAGE? SEF-2 |
| | INTAKE ON H2.04 RISER DIAGRAM IS SHOWN ABOVE THE |
| | CEILING IN RETAIL 1 AREA. THIS DOES NOT CORRELATE WITH |
| | FLOOR PLAN AND IS NOT FUNCTIONAL FOR PROVIDING SMOKE |
| | CONTROL TO THE MAIN LOBBY AREA. |
| | (D) SEQUENCE INDICATES DOORS WILL OPEN FOR SMOKE |
| | EXHAUST MAKE-UP AIR, BUT PLAN SHOWS LOUVERS WITH |
| | MOTORIZED DAMPERS ABOVE THE DOORS ADDED IN THIS |
| | REVISION. IS THIS IN ADDITION TO THE LOBBY DOORS OR |
| | INSTEAD OF THEM? PLEASE CLARIFY. IF THE LOUVERS AND |
| | MOTORIZED DAMPER ARE TO BE USED, PLEASE ADJUST SEQUENCE |
| | ACCORDINGLY. |
| | |