Plan Review Notes
Plan Review Notes For Permit 06040957
Permit Number 06040957
Review Stop E
Sequence Number 9
Notes
Date Text
2007-07-05 14:47:082007-07-05 14:47:08
 ** UNSAT**
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
 PLEASE ALSO SEE NEW COMMENTS.
  
 1) NOTE: PLEASE SEE THE NEW LANDSCAPE PLANS SUBMITTED
 IN FACT CONTAIN A RAISED SEAL OVER A PHOTO-COPIED
 SIGNATURE ON ALL THREE SETS. PLEASE SEE FS 481.221.
 THIS COMMENT HAS BEEN MADE MANY TIMES WITH DIFFERENT
 DESIGNERS ON THIS PROJECT YET PLANS CONTINUE TO COME IN
 WITH THESE SAME VIOLATIONS UNDER FLORIDA STATUTES. **
 PLANS ARE BEING RETAINED AND WILL BE PLACED WITH
 PREVIOUS PLANS RETAINED BY THIS OFFICE FOR THE SAME
 COMMENT.
 ** PLANS MAY BE TURNED OVER TO THE STATES LEGAL COUNSEL
 TO THE BOARD OF ARCHITECTS OR FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS.
 THIS COMMENT SHOULD HAVE TO BE REPEATED.
 PLEASE BE SURE ALL PLANS WHEN SUBMITTED CONTAIN AN
 ORIGINAL, SIGNATURE, DATE AND RAISED SEAL.
  
 2) NOTE: PLEASE SEE NO REVISED ENERGY CALCULATIONS WERE
 SUBMITTED AS PREVIOUSLY REQUESTED DUE TO THE NUMEROUS
 CHANGES TO PLANS AND LIGHTING.
 FBC CHAPTER 13 13-415.1.A,
 13-103.1.1.1
  
 3) NOTE: PLEASE REVISE AND COORDINATE ALL ELECTRICAL
 PLANS FOR EACH FLOOR WITH THATOF THE SHEETS FOR
 BUILD-OUT PERMITS AND PLANS.
 PLEASE SEE THERE ARE TOO MANY ITEMS TO LIST AT THIS
 TIME BASED ON THE MULTIPLE SETS OF PLANS/ REVISIONS AND
 RESUBMITTED PLANS.
 FBC 106.1.2 ADMIN SECTION FOR COORDINATION.
  
 4) NOTE: PLEASE SEE REVISED SUBMITTALS FOR THE
 ATS/GENERATORS ETC WERE NOT SUBMITTED.
 PLEASE SEE THE SUPPORTING SHEET WHICH WAS THE ONLY
 SHEET SUBMITTED CONTAINS THREE STATEMENTS FROM THE
 GENERATOR MANUFACTURE AND ALL THREE STATEMENTS CONTAINS
 THE WORDING *HOWEVER* AND THEN GOES ON TO STATE
 WARRANTY MAY BE AFFECT BY CHANGES ETC TO EQUIPMENT.
 PLEASE PROVIDE THE DOCUMENTATION/LISTING STANDARD FROM
 WHICH THIS GENERATOR IS MANUFACTURED. PLEASE PROVIDE
 LETTERS AND SUPPORTING DOCUMENTATION FROM MANUFACTURES
 WITH RESPECT TO ADDING SPECIFIC AFTERMARKET EQUIPMENT
 AND SUPPORTING DOCUMENTATION FROM LISTING AGENCY WHICH
 ALLOWS THIS.
 THESE ARE LEGALLY REQUIRED AND LIFE SAFETY REQUIRED
 UNITS.
 110.3, 90.7, 700, 701 ETC.
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE THE UNDERGROUND FEEDERS NOW
 INDICATE *CLEAN FILL* IN LIEU OF THE ALL PREVIOUS PLANS
 WHICH INDICATED THE REQUIRED CONCRETED ENCASEMENT OF
 THE FEEDERS.
 PLEASE SEE 700.9D(1)5. THIS OFFICE DOES NOT HAVE AN
 ISSUE WITH THE FEEDERS UNDER THE BUILDING WHICH ARE
 PROTECTED, HOWEVER THE FEEDERS FROM BUILDING TO
 GENERATOR ARE AND WILL BE REQUIRED TO BE ENCASED IN
 CONCRETE. THIS LOCATION HAS ALREADY HAD CONDUITS DUG UP
 AND DAMAGE FROM ON-SITE CONSTRUCTION. THESE ARE
 CONDUITS WHICH ARE REQUIRED FOR LIFE SAFETY AND ARE
 SHOWN ONLY AT A DEPTH OF 30INCHES.
 PLEASE REVISE PLANS TO INDICATE CONCRETE ENCASEMENT FOR
 ANY OF THESE CONDUITS.
 PLEASE CLARIFY DEPTH OF THE AA-AA BANK WHICH IS BEING
 SHOWN AT 22INCHES. 300.5
  
 6) NOTE: PLEASE SEE THERE ARE SEVERAL SHEETS WHICH
 CONTAIN REVISION WHICH ARE ONLY REVISION 15, YET
 REVISION 10 IS NOT INDICATED ON SHEETS. PLEASE SEE
 REVISION 15 IS LABELED ON NUMEROUS SHEETS AS *BUILDING
 DEPT COMMENTS* WHEN THERE ARE NUMEROUS REVISIONS TO
 PLANS WHICH THIS DEPARTMENT HAD NO COMMENTS AND DID NOT
 ASK FOR THESE CHANGES. PLEASE REVISE ALL TITLE BLOCKS
 AND PLEASE INDICATE THE REVISIONS ON PLANS INCLUDING
 PREVIOUS REVISION IDENTIFICATIONS WHICH ARE NOT ON
 RECORD PLANS.
 FBC 106.1.2, 106.3.5.1.2
 SHEETS: E101A,102, 103,104,105,106 ETC. COORDINATE 115
 ETC.
  
 7) NOTE: PLEASE SEE SITE LIGHTING ON THIS LEGAL
 PROPERTY WHICH STILL DOES NOT INDICATE CIRCUITING.
 PLEASE SEE E1.00 AS ANY EXISTING LIGHTING POLES WHICH
 ARE NOW PART OF THIS SEPARATE LEGAL PROPERTY WILL BE
 REQUIRED TO BE CIRCUITED TO THIS BUILDING.
 FBC 106.1.2, 106.3.5.1.2
 408.4, 310.16.
  
 8) NOTE: PLEASE PROVIDE VD FOR CIRCUITS ON ROOF AND
 15TH FLOOR WHICH ARE BEING SHOWN FED FROM FIRST FLOOR
 LIGHTING PANEL.
 PLEASE CLARIFY CIRCUITS SL41A-16, 14 ETC WHICH FEED THE
 ROOF TOP LIGHTING AND LIGHTING FOR BUILDING
 ILLUMINATION.
 13-413.1. ABC.1.2
 ** SUPPORTS ON THESE VERTICAL RUNS ARE STILL REQUIRED.
 300.19
  
 9) NOTE: PLEASE KNOW AS STATED ON PREVIOUS REVIEW: THE
 REVIEWS OF REVISIONS TO PLANS OTHER THAN THAT OF ITEMS
 PREVIOUSLY NOTED FOR CORRECTION WOULD BE MADE EASIER IF
 INDEED A LETTER OR FORM OF IDENTIFYING CHANGES MADE TO
 PLANS WAS SUBMITTED. EXAMPLE: PLEASE SEE REVISION #10
 TO E0.01, WHICH NOW INCLUDES A DIMMER, YET THIS DEVICE
 IS NOT EASILY REVISED OR LOCATED ON SHEETS SUBMITTED.
 FBC 106.1.2 PLEASE CLARIFY.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-05 07:04:592007-07-05 07:04:59
 REVIEW IN PROGRESS
2007-07-04 12:37:472007-07-04 12:37:47
 1-ROLL OF PLANS REMOVED FROM INCOMING IN ELECTRICAL FOR
 REVIEW. PLANS WILL BE RETURNED TO INCOMING WAITING FOR
 COMM BOARD ONCE ELECTRICAL REVIEW IS COMPLETED.