| 2007-03-01 11:45:45 | BUILDING PLAN REVIEW |
| | PERMIT: 06040957 |
| | ADD: 525 OKEECHOBEE BLVD |
| | CONT: CENTEX |
| | TEL: (561)629-4174 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2005 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | SUBMITTAL REVIEW: |
| | 1) REPORT FROM GEOTECHNICALENGINEER CERTIFYING |
| | AUGER-CAST PILE |
| | |
| | 2) AS BUILT SURVEY OF AUGER-CAST PILE |
| | |
| | 3) BUILDING PROVISO # 3, COMPLIED. |
| | |
| | 4)BUILDING PROVISO# 4, COMPLIED. |
| | |
| | THE BUILDING PROVISO # 2, FROM THE ISSUE DATE ********* |
| | (OVER 60 DAYS)********IS STILL MISSING CONTRACTOR |
| | SUPPLIED STATE APPROVED |
| | PRODUCT APPROVALS FOR ALOBOND PLUS THAT WILL MEET THE |
| | REQUIRED WIND RATING. TO BE REVIEWED |
| | AND APPROVED BY THE DESIGN PROFESSIONAL BEFORE |
| | SUBMITANCE TO THE CITY FOR |
| | REVIEW. REVIEWED FOR FIRE RESISTANCE UNDER FL 2661-R1/ |
| | 2001 |
| | NO REPORTS HAVE BEEN SUBMITTED FOR WIND. |
| | |
| | 1609.1.1 DETERMINATION OF WIND LOADS. |
| | WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE |
| | DETERMINED IN ACCORDANCE WITH SECTION 6 OF ASCE |
| | 7.EXCEPTION# 2 WIND TUNNEL TEST, THE MCM PANELS MAY |
| | NEED |
| | ENHANCED FASTENING FOR THE LOCATION ON THE BUILDING. |
| | THIS ISTO BE COMPLETED BY THE ENGINEER OF RECORD. |
| | |
| | WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT |
| | WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |