2007-05-07 15:33:275-7-07PES REVISIONS REVIEWIN PROGRESS.
  
 PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
  
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
  
 REVISION DATED 5-2-07 DENIED
  
 1)ALL PLUMBING COMMENTS DENIED, EXCEPT REFERENCE TO
 DOMESTIC WATER RISER, HYDRA-RESTER ( SHOCK ABSORBER)
 SHT PO.3
  
 2) MEET WITH MR DAVID ALLEN, PE.
 PLANS TO REFELECT A SEPERATE CONDENSATE DRAINAGE
 SYSTEM.
 TERMINATING OUT SIDE THE BUILDING, CONNECTINGTO THE
 STORM WATER DRAIN, WITH A RELIEF 6" ABOVE GRADE.
  
 END OF COMMENTS, QUESTIOINS 561-805-6692