| Date |
Text |
| 2007-04-15 18:08:44 | ** UNSAT ** |
| | |
| | REVISIONS. |
| | |
| | 1) NOTE: PLEASE SEE THAT LETTER OF SUBMITTED CHANGE OR |
| | INFORMATION ON CHANGES MADE WOULD BE HELPFUL IN THE |
| | REVIEW OF DOCUMENTS FOR CHANGES MADE. |
| | PLEASE KNOW THAT ALL CHANGES WHICH AFFECT THE BASE |
| | BUILDING UNDER THE TENANT BUILD OUTS WILL BE REQUIRED |
| | TO BE REVISED ON BASE BUILDING PLANS. |
| | THIS IS FOR ALL BUILD OUT AFFECTING BASE PLANS BEFORE |
| | CO OF MAIN BUILDING. |
| | PLEASE BE SURE TO COORDINATE WITH ANY ELECTRICAL |
| | REQUIREMENTS AND CHANGES REQUIRED FOR TENANT FIT UPS. |
| | FBC 106.3.5.1.2 |
| | |
| | 2) NOTE: PLEASE SUBMIT ALL MANUFACTURE SPECS/CUT SHEETS |
| | FOR ALL NEW REVISED ATS AND GENERATOR EQUIPMENT. |
| | PLEASE KNOW IT HAS COME TO ATTENTION THAT THE ADDITION |
| | OF THE BI-FUEL DEVICES ON THE GENERATOR UNITS MAY |
| | INDEED CAUSE ANY LISTINGS TO BE VOIDED AND ALSO VOID |
| | ANY WARRANTY ON THE UNITS. |
| | THE WARRANTY IS NOT THE CONCERN OF THIS OFFICE, HOWEVER |
| | VOIDING ANY LISTINGS OF LEGALLY REQUIRED AND EMERGENCY |
| | STAND-BY SYSTEMS REQUIRED FOR LIFE SAFETY IS OF |
| | CONCERN. |
| | THIS MATTER WILL BE LOOKED INTO FURTHER AND INFORMATION |
| | FORWARD TO THE LISTING AGENCY AS LISTED ON EQUIPMENT |
| | SUBMITTED UNDER THE INITIAL BASE BUILDING PERMITTED |
| | PACKAGE. PLEASE SEE THE SIZE OF THE GENERATOR HAS |
| | INCREASED HOWEVER THE OCP DEVICES HAVE NOT CHANGED ON |
| | UNIT? |
| | PLEASE ALSO SUBMIT THE SPECS FOR THE PARALLELING SWITCH |
| | GEAR AS REVISED. |
| | PLEASE CLARIFY. |
| | 110.3, 90.7 |
| | |
| | 3) NOTE: PLEASE CORRELATE RISER AND PARALLELING SWITCH |
| | GEAR AS THESE NO LONGER MATCH DUE TO CHANGES FOR ATS-1. |
| | THE ATS- IS NOW SHOWN BEING FED FROM A 3200AMP ON THE |
| | PS GEAR AND THE RISER HAS NOT CHANGED ALONG WITH THE |
| | EQUIPMENT? |
| | PLEASE PROVIDE MORE INFORMATION. |
| | EQUIPMENT MAY NOT BE FED FROM 3200A OCP WHEN ONLY RATED |
| | FOR 3000AMPS> |
| | |
| | 4) NOTE: PLEASESUBMIT A SELECTIVE COORDINATION STUDY |
| | NOW THAT EQUIPMENT SHOULD ALL BE SELECTED. |
| | 240.12, 700.27, 701.18. NEC |
| | NFPA-110 6.5.1 |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE CLARIFY THE NEW MAINS NOW BEING SHOWN |
| | FOR THE EMERGENCY SYSTEMS AND LEGALLY REQUIRED SYSTEMS |
| | WHICH INDICATE GF PROTECTION? |
| | PLEASE SEE 240.13, 230.95, AND NEC 700.7D |
| | |
| | 6) NOTE: PLEASE SEE RISER HAS NOW CHANGED TO INDICATE |
| | THE SWBDB TO BE A 4000AMP RATED MAIN, YET NOTE FOR THIS |
| | STILL INDICATES THIS AS A 5000AMP SWITCH BOARD? |
| | PLEASE CORRELATE. |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE THE PLANS HAVE HAD SEVERAL LIGHTING |
| | FIXTURES REVISED ALONG WITH THE NUMBER AND LOCATIONS OF |
| | FIXTURES. PLEASE SUBMIT REVISED ENERGY CALCULATIONS FOR |
| | BUILDING PER 13-415.1.AB.1.1. |
| | |
| | 8) NOTE: PLEASE SEE THE FIXTURE LEGEND HAS BEEN REVISED |
| | AND THERE ARE FIXTURES WHICH ARE SHOWN ON PLANS WITH |
| | DESIGNATIONS WHICH ARE NOT LISTED ON FIXTURE LEGEND. |
| | (CCE, NL ETC) |
| | PLEASE SHOW ALL FIXTURES AND COORDINATE WITH LEGEND AND |
| | REVISED ENERGY CALCULATIONS. |
| | FBC 106.1.2 |
| | |
| | 9) NOTE: PLEASE SEE ELEVATOR MOTORS 1,2 AND 3 WHICH HAS |
| | NOW INCREASED ALONG WITH THE FEEDING FROM LSPA, YET THE |
| | OCP FROM LSPA HAS ACTUALLY GONE DOWN?? |
| | PLEASE SEE THE LOAD HAS INCREASED WHICH NO EXCEEDS THE |
| | RATING OF THE NEW LOWER 200AMP BREAKER? |
| | PLEASE VERIFY ALL LOADS ON MOTORS PER 430 TABLES AND |
| | VERIFY THE LOADS ON EACH. |
| | PLEASE SUBMIT REVISED SCHEDULES FOR THIS. |
| | PLEASE REVISED ANY LOAD CALCULATIONS. |
| | FBC 106.1.2 |
| | NEC 240, 430, 220 |
| | |
| | 10) NOTE: PLEASE SEE NEW LIGHTING ON E-100 SEEM TO BE |
| | LOCATED OUTSIDE PROPERTY LINE OF THE BUILDING. PLEASE |
| | CLARIFY AND PROVIDE DOCUMENTATION OF ANY CHANGES. |
| | |
| | 11) NOTE: PLEASE SUPPLY REVISED VOLTAGE DROP |
| | INFORMATION FOR DECREASED OF CONDUCTORS AND BRANCH |
| | CIRCUITS ON PLANS FOR SITE LIGHTING WHICH IS NOT |
| | LOCATED LONGER RUNS THAN PREVIOUS PLANS AND SMALLER |
| | CONDUCTORS. |
| | 13-413.1.ABC.1 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-04-15 16:07:07 | IN PROGRESS |
| 2007-04-14 16:02:49 | ONE ROLL IN ELEC FOR REVIEW. |