Plan Review Notes
Plan Review Notes For Permit 06040957
Permit Number 06040957
Review Stop P
Sequence Number 7
Notes
Date Text
2007-03-24 14:11:42PAUL SCHMITZ
 [email protected] FBC 2004 PLUMBING
 CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
  
 REVISION DENIED
  
 1) SHTS L-3, L-4IRRIGATION: NOT INCLUDED WITH THIS
 SET OF PLANS.
  
 2) CIVIL PLANS, SHTS I, THROUGH 14 SHOW LOCATION OF
 STORM DRAIN TIE IN.
  
 CONTINUE NOTES 3-26-07.DECIDED TO COME IN 3-25-07 TO
 COMPLETE REVIEW NOTES.
  
 3) SHT H2.01 FLOW DIAGRAM, REFERENCE TO COLD WATER FILL
 NO BACK FLOW PREVENTER.
  
 4) SHT P0.1, DETAIL EWH-1,2 EXPANSION TANK ON COLD
 WATER, "QUESTION IF THIS SHOULD BE ON THE HOT WATER
 LINE"
  
 5) SHT P0.3(1) WATER RISER : HYDRA-RESTER, SIOUX
 CHIEF, PROVIDE MFG TABLE FOR SIZE AND LOCATION AND WERE
 REQUIRED.
 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010.
  
 6 A)SHT P0.1 AND PUI.01 PROVIDE CALCULATIONS FOR THE
 SIZE OFOIL,SAND INTERCEPTOR.
 B)PROVIDE CALCULATIONS FOR THE SIZING OF THE GW
 SYSTEM,
 C) LOCATIION OF TD'C AND TD'B
  
 7) SHT P0.02 CAR WASH: SHOW LOCATION OF THE DRAIN AND
 CONNECTION TO OIL SEPERATOR.
 1003.4 OIL SEPARATORS REQUIRED.
 AT REPAIR GARAGES, CARWASHING FACILITIES WITH ENGINE OR
 UNDERCARRIAGE CLEANING CAPABILITY AND AT FACTORIES
 WHERE OILY AND FLAMMABLE LIQUID WASTES ARE PRODUCED,
 SEPARATORS SHALL BE INSTALLED INTO WHICH ALL
 OIL-BEARING, GREASE-BEARING OR FLAMMABLE WASTES SHALL
 BE DISCHARGED BEFORE EMPTYING IN THE BUILDING DRAINAGE
 SYSTEM OR OTHER POINT OF DISPOSAL.
 1003.4.1 SEPARATION OF LIQUIDS.
 A MIXTURE OF TREATED OR UNTREATED LIGHT AND HEAVY
 LIQUIDS WITH VARIOUS SPECIFIC GRAVITIES SHALL BE
 SEPARATED IN AN APPROVED RECEPTACLE.
 1003.4.2 OIL SEPARATOR DESIGN.
 OIL SEPARATORS SHALL BE DESIGNED IN ACCORDANCE WITH
 SECTIONS 1003.4.2.1 AND 1003.4.2.2.
 1003.4.2.1 GENERAL DESIGN REQUIREMENTS.
 OIL SEPARATORS SHALL HAVE A DEPTH OF NOT LESS THAN 2
 FEET (610 MM) BELOW THE INVERT OF THE DISCHARGE DRAIN.
 THE OUTLET OPENING OF THE SEPARATOR SHALL HAVE NOT LESS
 THAN AN 18-INCH (457 MM) WATER SEAL.
  
 8) SHT P0.3 DRAIN WASTE & VENT ISOMETRIC, DOES NOT SHOW
 THE TIE IN OF THE UGW SYSTEM,TO SANITARY SYSTEM.
  
 9) SHT P0.4 LOWER SANITARY WASTE & VENT RISER DIAGRAM:
 INDIRECT WASTE CONNECTION FROM AHU, SEE SHT H0.03
 DETAIL (24)
 NOT APPROVED TO SANITARY SYSTEM, SEPERATE SYSTEM
 REQUIRED.TERMINATE TO STORM, OUT SIDE OF THE
 BUILDING. DRY WELL OR PLANTER.
  
 10) SHTS P1.05, P1.15, P1.16, P1.17PRIMARY ROOF
 DRAINS: PROVIDE THE CALCIULATIONS FOR THS SIZING OF THE
 ROOF DRAINAGE SYSTEM, BASED ON THE FOLLOWING CODE
 SECTIONS
 1101.7 ROOF DESIGN.
 ROOFS SHALL BE DESIGNED FOR THE MAXIMUM POSSIBLE DEPTH
 OF WATER THAT WILL POND THEREON AS DETERMINED BY THE
 RELATIVE LEVELS OF ROOF DECK AND OVERFLOW WEIRS,
 SCUPPERS, EDGES OR SERVICEABLE DRAINS IN COMBINATION
 WITH THE DEFLECTED STRUCTURAL ELEMENTS. IN DETERMINING
 THE MAXIMUM POSSIBLE DEPTH OF WATER, ALL PRIMARY ROOF
 DRAINAGE MEANS SHALL BE ASSUMED TO BE BLOCKED.
 SEE TA\BLES 1106.2 AND 1106.3
 1106.4 VERTICAL WALLS.
 IN SIZING ROOF DRAINS AND STORM DRAINAGE PIPING,
 ONE-HALF OF THE AREA OF ANY VERTICAL WALL THAT DIVERTS
 RAINWATER TO THE ROOF SHALL BE ADDED TO THE PROJECTED
 ROOF AREA FOR INCLUSION IN CALCULATING THE REQUIRED
 SIZE OF VERTICAL CONDUCTORS, LEADERS AND HORIZONTAL
 STORM DRAINAGE PIPING.
 1106.5 PARAPET WALL SCUPPER LOCATION.
  
 11) SHTS P1.05, P1.15, P1.16, P1.17 SECONDARY DRAINS:
 PROVIDE THE CALCIULATIONS FOR THS SIZING OF THE
 SECONDARY ROOF DRAINAGE SYSTEM, BASED ON THE FOLLOWING
 CODE SECTIONS.
 1106.4 VERTICAL WALLS.
 IN SIZING ROOF DRAINS AND STORM DRAINAGE PIPING,
 ONE-HALF OF THE AREA OF ANY VERTICAL WALL THAT DIVERTS
 RAINWATER TO THE ROOF SHALL BE ADDED TO THE PROJECTED
 ROOF AREA FOR INCLUSION IN CALCULATING THE REQUIRED
 SIZE OF VERTICAL CONDUCTORS, LEADERS AND HORIZONTAL
 STORM DRAINAGE PIPING.
 1106.5 PARAPET WALL SCUPPER LOCATION.
 SECTION 1107
 SECONDARY (EMERGENCY) ROOF DRAINS
 1107.1 SECONDARY DRAINAGE REQUIRED.
 SECONDARY (EMERGENCY) ROOF DRAINS OR SCUPPERS SHALL BE
 PROVIDED WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS
 ABOVE THE ROOF IN SUCH A MANNER THAT WATER WILL BE
 ENTRAPPED IF THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY
 REASON.
 1107.2 SEPARATE SYSTEMS REQUIRED.
 SECONDARY ROOF DRAIN SYSTEMS SHALL HAVE THE END POINT
 OF DISCHARGE SEPARATE FROM THE PRIMARY SYSTEM.
 DISCHARGE SHALL BE ABOVE GRADE, IN A LOCATION WHICH
 WOULD NORMALLY BE OBSERVED BY THE BUILDING OCCUPANTS OR
 MAINTENANCE PERSONNEL.
 1107.3 SIZING OF SECONDARY DRAINS.
 SECONDARY (EMERGENCY) ROOF DRAIN SYSTEMS SHALL BE SIZED
 IN ACCORDANCE WITH SECTION 1106 BASED ON THE RAINFALL
 RATE FOR WHICH THE PRIMARY SYSTEM IS SIZED IN TABLES
 1106.2, 1106.3 AND 1106.6. SCUPPERS SHALL BE SIZED TO
 PREVENT THE DEPTH OF PONDING WATER FROM EXCEEDING THAT
 FOR WHICH THE ROOF WAS DESIGNED AS DETERMINED BY
 SECTION 1101.7. SCUPPERS SHALL NOT HAVE AN OPENING
 DIMENSION OF LESS THAN 4 INCHES (102 MM). THE FLOW
 THROUGH THE PRIMARY SYSTEM SHALL NOT BE CONSIDERED WHEN
 SIZING THE SECONDARY ROOF DRAIN SYSTEM.
  
 END OF COMMENTS, QUESTIONS 561-805-6692