Plan Review Notes
Plan Review Notes For Permit 06040957
Permit Number 06040957
Review Stop M
Sequence Number 7
Notes
Date Text
2007-04-19 16:11:36-------------------DENIED---------------------
  
 FBC 2004 CODE FAMILY W/2005 REVISIONS
 FBC CH 1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 -COMMENTS ARE ORGANIZED BY PAGE NUMBER UNLESS COMMENT
 APPLIES TO THE ENTIRE BUILDING.
 -15 PAGES WERE SUBMITTED AS A PACKAGE FOR THIS
 REVISION. THAT COMPRISES EVERY PAGE OF THE ORIGINAL
 PERMITTED SET OF PLANS.
 -EQUIPMENT CHANGES AS STATED ON REVISED PAGE H0.02 WILL
 REQUIRE REVISED ENERGY CALCULATIONS TO BE SUBMITTED
 WHEN THE FOLLOWING COMMENTS ARE ADDRESSED AND
 RESUBMITTED.
 -SUBMITTED PLANS (1 SET) HAVE BEEN MARKED WHEN
 PRACTICAL TO SHOW AREAS BEING ADDRESSED BY PLAN REVIEW
 COMMENTS.
  
 1. H0.01: THERE HAS BEEN A CHANGE TO THIS PAGE BUT THE
 CHANGED WAS NOT MARKED ON THE PLAN AS A REVISION.
  
 2. H0.02: THIS PAGE HAS BEEN MODIFIED BY REVISIONS 7
 AND 10, YET ONLY REVISION 10 HAS BEEN MARKED AS A
 CHANGE. THE LAST REVISION SUBMITTED TO THIS OFFICE
 RELATED TO THIS PAGE WAS REVISION 6 DATED 11/10/06. ANY
 CHANGES FROM THAT DATE FORWARD SHOULD BE CLEARLY MARKED
 TO FACILITATE AN ACCURATE REVIEW AS WELL AS TO MAINTAIN
 CONTINUITY OF CONSTRUCTION DOCUMENTS. FBC 106.1.3.
  
 3. H0.03 DETAIL 25: HEIGHT OF ROOFTOP EQUIPMENT IS TO
 BE DETERMINED BY FBC TABLE 1509.7. ALSO, PLEASE SHOW
 STRUCTURAL DATA (FROM STRUCTURAL ENGINEER) FOR ALL
 ROOFTOP EQUIPMENT WITH WIND LOAD CALCULATIONS PER FBC
 1603.1.4 ALONG WITH DETAILED INFORMATION RELATED TO
 ATTACHMENTS OF ALL EQUIPMENT TO STRUCTURE NEEDED TO
 MEET WIND LOAD REQUIREMENTS. THIS APPLIES TO ALL
 ROOFTOP AND OUTDOOR EQUIPMENT.
  
 4. H0.04: SEE ABOVE COMMENT REGARDING DETAIL 31,
 EXTERIOR DUCTWORK.
  
 5. H1.01 & H1.02: PLAN SHOWS SOME KIND OF SHAFT WALL IN
 MECHANICAL RM 204 FOR PAC 2 DUCTS TO REACH 1ST FLOOR.
 HOWEVER, REVISED PG A1.02 DOES NOT SHOW ANY SHAFT WALL.
 WHERE ARE THESE RATED PENETRATIONS TO TAKE PLACE? IF A
 SHAFT IS TO BE USED, OPENINGS MUST BE PROTECTED WHERE
 THE DUCTS ENTER AND LEAVE THE SHAFT. PLEASE CLARIFY AND
 COORDINATE WITH ARCHITECTURAL DRAWINGS. PERHAPS AN
 ENLARGED DRAWING OF MECHANICAL ROOMS WITH PLAN AND
 ELEVATION VIEWS ARE NEEDED TO CLEARLY SHOW THE SCOPE OF
 WORK. FBC,M 106.1.1.
  
 6. H1.01: PLEASE SHOW LOCATION OF ALL GRILLS/REGISTERS
 AS THEY ARE SHOWN ON REFLECTIVE CEILING PLAN TO SHOW
 HOW BALANCED RETURN IS TO BE ACHIEVED IN VARIOUS AREAS.
 FBC,M 601.4.
  
 7. H1.01: FRESH AIR INTAKE FOR THE LOADING DOCK SHALL
 BE A MINIMUM OF 10' AWAY FROM STREETS, ALLEYS, PARKING
 LOTS AND LOADING DOCKS PER FBC,M 401.5.1.
  
 8. H1.01 HP-3 IN LOADING DOCK: WHAT IS THE ELEVATION TO
 THE BOTTOM OF HEAT PUMP? APPLIANCES IN PUBLIC GARAGES
 OR OTHER AREAS FREQUENTED BY MOTOR VEHICLES EXCEEDING 6
 FEET IN HEIGHT SHALL BE INSTALLLED A MINIMUM OF 2 FEET
 HIGHER ABOVE THE FLOOR THAN THE HEIGHT OF THE TALLEST
 VEHICLE. FBC,M 304.5
  
 9. H1.01: 12X16 DUCT IS SHOWN PENETRATING RATED WALL AT
 RETAIL 1. PLEASE SHOW METHOD OF OPENING PROTECTIVE TO
 BE USED PER FBC,M 607.5.
  
 10. H1.01 THROUGH H1.18: A/C CONDENSATE SHALL NOT
 DISCHARGE INTO CITY WASTE WATER FACILITY PIPING PER
 W.P.B. MUNICIPAL CODE SEC 90-125(B)(5). PLUMBING PLANS
 EXAMINER MAY BE ABLE TO HELP IN DETERMINING THE BEST
 WAY TO DISPOSE OF CONDENSATE IN THE STORM WATER DRAIN
 SYSTEM.
  
 11. H1.01: WHAT IS THE SIZE OF EXHAUST DUCT BETWEEN
 CIF-6 AND THE 22X22 EXHAUST RISER DUCT? IS THERE ROOM
 FOR A 22" TALL DUCT TO CROSS THE DRIVEWAY? PLEASE SEE
 COMMENT 8 REGARDING VEHICLE HEIGHTS AND REQUIRED
 CLEARANCE.
  
 12. H1.02 STAIR 2: RISER 2 DUCT IN STAIR 2 IN 1ST FLOOR
 DOES NOT APPEAR TO BE IN A RATED ENCLOSURE AS IT IS ON
 OTHER FLOORS. THE RISER DIAGRAM SHOWS IT LEAVING THE
 SHAFT, TRAVELING THROUGH THE STAIRWAY AND INTO THE
 CEILING OF RETAIL 1. PLEASE CLARIFY.
  
 13. PLEASE SHOW HANGNG DETAIL FOR HORIZONTAL AHU'S AND
 HEAT PUMPS, SHOWING COMPLIANCE WITH FBC,M 307.2.3
 RELATED TO SECONDARY/AUXILIARY DRAIN PROTECTION.
  
 14. H1.02: LIFE SAFETY PLAN A0.22 SHOWS 1 HOUR RATED
 WALL BETWEEN STORAGE ROOM 205 AND ELEVATOR LOBBY. HOW
 WILL THIS OPENING BE PROTECTED? PLEASE SHOW COMPLIANCE
 WITH FBC,M 607.5.
  
 15. H1.02: ACCU'S IN GARAGE ARE ONLY PROTECTED FROM
 VEHICLE DAMAGE ON 2 SIDES. PLEASE SHOW PROTECTION ON 3
 SIDES. ALSO, WE HAVE STILL NOT RECEIVED DOCUMENTATION
 FROM THE EQUIPMENT MANUFACTURER REGARDING THE
 SUITABILITY OF ACCU'S BEING INSTALLED INDOORS. FBC,M
 304.5
  
 16. H1.02: WHAT IS THE HEIGHT TO THE BOTTOM OF PF-1 AND
 PF-2? APPLIANCES LOCATED IN PUBLIC GARAGES SHALL BE
 INSTALLED A MINIMUM OF 8 FEET ABOVE THE FLOOR OR 2'
 ABOVE THE HEIGHT OF ANY VEHICLE OVER 6' HIGH HAVING
 ACCESS TO THE GARAGE UNLESS PROTECTED FROM MOTOR
 VEHICLE IMPACT. FBC,M 304.5.
  
 17. H1.02: WHAT IS THE HEIGHT OF O.A. DUCT AND PIPING
 FROM RISERS 5 & 6 TO MECHANICAL RM 204? PLEASE NOTE:
 THESE RUN OVER A VAN ACCESSIBLE DISABLED PARKING
 SPACE.
  
 18. H1.02: R-1 RISER DUCT AT STAIR 1 IS SHWON OUTSIDE
 THE SHAFT ENCLOSURE. IS THIS TO BE FLAMEBAR DUCT?
 PLEASE CLARIFY PER FBC 106.1.1.
  
 19. H1.02 SECTION AA: IS IT THE INTENTION OF THE
 DESIGNER THAT PAC-2 SITS ON A BIG NEOPRENE PAD? IS THIS
 INTENDED TO BE A CONCRETE HOUSEKEEPING PAD? PLEASE
 CLARIFY PER FBC 106.1.1.
  
 20. H1.02: WHAT IS THE MEANS AND RATE OF MECHANICAL
 VENTILATIONFOR THE FOLLOWING AREAS:
 STORAGE 202
 SERVICE VESTIBULE 203
 ELECTRICAL RM 209
 STORAGE 205
 ELEVATOR LOBBIES - ALSO SEE FBC,M 404.3
 ELEVATOR MACHINE ROOM.
 NOTE: RECIRCULATION OF AIR FROM GARAGE IS PROHIBITED
 PER FBC,M 403.2.1(1).
  
 21. H1.02 AND ALL PARKING LEVELS: SF-1 SUPPLY FAN FOR
 PARKING GARAGE INTAKE IS LOCATED WITHIN THE PARKING
 GARAGE. OUTDOOR AIR IS REQUIRED PER FBC,M 403.2 AND CAN
 NOT BE DRAWN FROM WITHIN THE ENCLOSED PARKING GARAGE.
 SF-1 INTAKE OPENING SHALL BE LOCATED IN COMPLIANCE WITH
 FBC,M 401.5.1.
  
 22. H1.02 AND ALL PARKING LEVELS: SF-1 ON FAN SCHEDULE
 IS SHOWN TO PRODUCE 5,000 CFM. DESIGNER'S CALCULATIONS
 SHOW 45,000 CFM OF VENTILATION REQUIRED. VENTILATION
 SUPPLY SYSTEMS SHALL BE DESIGNED TO DELIVER THE
 REQUIRED RATE OF SUPPLY AIR (45,000 CFM) TO THE
 OCCUPIED ZONE WITHIN THE OCCUPIED SPACE. THE AMOUNT OF
 SUPPLY AIR SHALL BE APPROXIMATELY EQUAL TO THE AMOUNT
 OF EXHAUST AIR PER FBC,M 403.1.
  
 23. H1.03: SEE REVIEW COMMENT 20 REGARDING
 VENTILATION.
  
 24. H1.03: SEE REVIEW COMMENT 16 REGARDING
 ELEVATION/PROTECTION OF GARAGE FANS.
  
 25. H1.03 & H1.05: PLEASE INDICATE ON PLANS WHETHER R-1
 RISER DUCT IS TO BE ENCLOSED IN A RETED ENCLOSURE OR
 CONSTRUCTED OF FLAMEBAR. FBC 106.1.1.
  
 26. H1.03: LIFE SAFETY PLAN A0.22 SHOWS STORAGE RM 304
 TO BE ONE-HOUR RATED AND 405 TO BE TWO-HOUR RATED.
 PLEASE SHOW HOW DUCT PENETRATIONS ARE TO BE PROTECTED
 PER FBC,M 607.5.
  
 27. H1.03: EMERGENCY ELECTRICAL RM 405: 400 CFM OF
 MAKE-UP AIR IS NEEDED FOR CIF-3. WHAT IS THE SOURCE?
 FBC 403.2.1.
  
 28. H1.05PLAN SHOWS DUCTS PENETRATING STORAGE RM 502 &
 504. PLEASE SHOW HOW DUCT PENETRATIONS ARE TO BE
 PROTECTED PER FBC,M 607.5.
  
 29. H1.05: PLEASE SHOW FIRE/SMOKE DAMPER WHERE R-4 DUCT
 LEAVES SHAFT PER FBC,M 607.5.5.1.
  
 30. H1.05: R-1 RISER DUCT SHOWS A FIRE DAMPER WHERE
 DUCT LEAVES THE SHAFT AND ENTERS ELECTRICAL ROOM. WHERE
 A FIRE DAMPER WILL INTERFERE WITH THE OPERATIONOF A
 REQUIRED SMOKE CONTROL SYSTEM (SUCH AS STAIRWELL
 PRESSURIZATION), APPROVED ALTERNATIVE PROTECTION SHALL
 BE UTILIZED. FBC,M 607.2.1
  
 31. H1.05: WHAT IS BOTTOM ELEVATION OF GARAGE FANS?
 PLEASE SEE REVIEW COMMENT 16 REGARDING
 ELEVATION/PROTECTION IN PUBLIC GARAGES.
  
 32. H1.05: PLEASE SEE REVIEW COMMENT 20 REGARDING
 VENTILATION.
  
 33. SMOKE CONTROL: BUILDINGS REQUIRED BY THIS CODE TO
 HAVE A SMOKE CONTROL SYSTEM SHALL HAVE SUCH SYSTEMS
 DESIGNED IN ACCORDANCE WITH THE APPLICABLE REQUIREMENTS
 OF FBC SECTION 909 AND THE GENERALLY ACCEPTED AND
 WELL-ESTABLISHED PRINCIPLES OF ENGINEERING RELEVANT TO
 THE DESIGN. THE CONSTRUCTION DOCUMENTS SHALL INCLUDE
 SUFFICIENT INFORMATION AND DETAIL TO DESCRIBE
 ADEQUATELY THE ELEMENTS OF THE DESIGN NECESSARY FOR THE
 PROPER IMPLEMENTATION OF THE SMOKE CONTROL SYSTEMS.
 THESE DOCUMENTS SHALL BE ACCOMPANIED WITH SUFFICIENT
 INFORMATION AND ANALYSIS TO DEMONSTRATE COMPLIANCE WITH
 THESE PROVISIONS. FBC,M 513.2
  
 34. H1.01 THRU H1.05: PROVIDE SIZE OF CEILING ACCESS
 DOORS FOR HEAT PUMPS AND ACCU'S ABOVE HARD CEILINGS.
 SHOW COMPLIANCE WITH FBC,M 306.1.
  
 35. H1.06 HVAC ALTERNATE #1 NOTES: PLEASE CHOOSE A
 METHOD OF DUCT CONSTRUCTION AND SPECIFY PER FBC
 106.1.1. ALSO, FUTURE TENANT SUPPLY DUCT SHOULD EITHER
 BE INCLUDED IN THIS SCOPE OF WORK FOR REVIEW AS A
 REVISION OR SHOULD BE REMOVED FROM THIS PLAN AND BE
 SHOWN ON TENANT BUILD-OUT PLANS AT THE TIME OF
 APPLICATION.
  
 36. H1.06: THIS PLAN SHEET IS TITLED FOR 6TH FLOOR
 ONLY. THERE ARE INDICATIONS ON THIS SHEET OF WORK TO BE
 DONE ON OTHER FLOORS (7-14). THERE ARE SIGNIFICANT
 ARCHITECTURAL AND MECHANICAL DIFFERENCES ON THESE
 FLOORS. PLEASE PROVIDE SEPARATE PLANS FOR FLOORS WHEN
 THEY ARE NOT TYPICAL TO FACILITATE A COMPLETE REVIEW
 AND TO ALLOW FOR PROPER INSPECTION IN THE FUTURE. FBC
 106.1.1. THERE MAY BE ADDITIONAL COMMENTS ONCE THE
 PLANS FOR FLOORS 7-14 ARE SEPARATED FROM THIS SHEET.
  
 37. H1.06: FLEX RUNOUTS ARE LIMITED TO 3 FEET IN LENGTH
 ON H0.03 DETAIL. ALSO, THE VAV MANUFACTURER MAY HAVE
 LIMITS TO THE ALLOWABLE LENGTHS OF FLEX DUCT FOR MEDIUM
 PRESSURE SYSTEMS. PLEASE PROVIDE MANUFACTURER'S
 INSTRUCTIONS TO SHOW MAXIMUM ALLOWABLE LENGTH OF FLEX
 AND INCLUDE THAT INFORMATION IN THE VAV DETAIL ON
 H0.03.
  
 38. MECHANICAL RM 605: THIS ROOM IS A RETURN AIR
 PLENUM. RETURN AIR PLENUMS SHALL BE SEALED WITH AN
 APPROVED CONTINUOUS AIR BARRIER. AN OPEN FLOOR DRAIN
 CAN NOT BE LOCATED IN A RETURN AIR PLENUM. FBC CH
 13-410.1.ABC.3.7
  
 39. H1.06: WHAT TYPE OF COOKING OR HEATING APPLIANCES
 WILL BE IN CATERING RM 615? PLEASE VERIFY THAT THERE
 WILL BE NO APPLIANCES REQUIRING A HOOD IN ACCORDANCE
 WITH FBC,M 507.2.
  
 40. H1.06: EF-6 IS LOCATED IN A RETURN AIR PLENUM.
 EXHAUST DUCTS UNDER POSITIVE PRESSURE SHALL NOT BE
 LOCATED IN A PLENUM PER FBC,M 601.3.
  
 41. H1.06: CONFERENCE CENTER 613 IS RECEIVING 2500 CFM
 OF SUPPLY AIR. THERE IS ONE RETURN GRILL AND ONE
 TRANSFER DUCT. THE TRANSFER DUCT SIZING SCHEDULE ON
 H0.03 ONLY GIVES SIZES FOR TRANSFER DUCTS UP TO 1300
 CFM. PLEASE SHOW HOW BALANCED RETURN IS TO BE ACHIEVED
 IN THIS AREA PER FBC,M 601.4.
  
 42. H1.06: ALL WALLS AROUND ROOMS 613,614 AND 615 ARE
 SHOWN TO BE FIRE RATED TYPE 6A WALLS AS SHWON ON A2.06
 AND A0.31. PLEASE SHOW HOW DUCT PENETRATIONS ARE TO BE
 PROTECTED PER FBC,M 607.5.
  
 43. H1.15: PLEASE SEE REVIEW COMMENTS 35 AND 38 FOR
 CORRECTIONS NEEDED ON THIS PAGE.
  
 44. H1.16: PLEASE SEE REVIEW COMMENTS 35 AND 38 FOR
 CORRECTIONS NEEDED ON THIS PAGE.
  
 45. H1.15 AND H1.16: DRAWING NOTE #4 IS SHWON ON FLOOR
 PLAN BUT IS NOT EXPLAINED IN NOTES. PLEASE CORRECT. FBC
 106.1.1
  
 46. H1.17: OAF-1 DUCT AND HOISTWAY RELIEF LOUVERS ARE
 SHWON TO BE PENETRATING TWO-HOUR RATED WALLS. PLEASE
 SHOW OPENING PROTECTIVES PER FBC,M 607.5.
  
 47. H1.18: HOISTWAY VENT SHOWN PENETRATING TWO-HOUR
 RATED WALL. PLEASE SHOW OPENING PROTECTIVES PER FBC,M
 607.5.
  