2007-05-17 09:11:35***DENIED***
  
 1) PLEASE NOTE THAT SOME SHEETS HAVE BEEN SUBMITTED FOR
 REVISION, HOWEVER NO REVISIONS ARE SHOWN. LS A0.24
  
 2) WILL THE ACCES DOOR REMAIN LOCKED AT LEVEL-6?
 A1.06
  
 3) AFTER THE PERMITS HAVE BEEN ISSUED, ANY
 REVIONS/CHANGES TO FIRE PROTECTION SYSTEMS NEED TO BE
 SUBMITTED UNDER THAT SPECIFIC PERMIT.
  
 4) FIRE DEPARTMENT VALVES ARE SHOWN WITH 2 1/2"
 CONNECTIONS. PLEASE MAKE NOTE OR ILLUSTRATE ON PLANS
 SHOWING 1 1/2" REDUCER WITH CHAIN.
  
 5) PLEASE PROVIDE CLARIFICATIONREGARDING NUMBER OF
 (DACT) PHONE LINES FOR FA SYSTEM.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW