| Notes |
| Date |
Text |
| 2007-05-17 09:11:35 | ***DENIED*** | | | | | | 1) PLEASE NOTE THAT SOME SHEETS HAVE BEEN SUBMITTED FOR | | | REVISION, HOWEVER NO REVISIONS ARE SHOWN. LS A0.24 | | | | | | 2) WILL THE ACCES DOOR REMAIN LOCKED AT LEVEL-6? | | | A1.06 | | | | | | 3) AFTER THE PERMITS HAVE BEEN ISSUED, ANY | | | REVIONS/CHANGES TO FIRE PROTECTION SYSTEMS NEED TO BE | | | SUBMITTED UNDER THAT SPECIFIC PERMIT. | | | | | | 4) FIRE DEPARTMENT VALVES ARE SHOWN WITH 2 1/2" | | | CONNECTIONS. PLEASE MAKE NOTE OR ILLUSTRATE ON PLANS | | | SHOWING 1 1/2" REDUCER WITH CHAIN. | | | | | | 5) PLEASE PROVIDE CLARIFICATIONREGARDING NUMBER OF | | | (DACT) PHONE LINES FOR FA SYSTEM. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|