| 2006-12-07 10:53:23 | BUILDING PLAN REVIEW |
| | PERMIT: 06040957 |
| | ADD: 525 OKEECHOBEE BLVD. |
| | CONT: CENTEX |
| | TEL: (561)653-8307 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | BUILDING REVISIONREVIEW |
| | ACTION: PROVISO |
| | |
| | 1) THE ARCHITECTURAL PLANS SUBMITTED APPEAR TO BE CODE |
| | COMPLIANT. THE BUILDING PROVISO FROM THE ISSUE DATE IS |
| | STILL |
| | MISSING CONTRACTOR SUPPLIED STATE APPROVED PRODUCT |
| | APPROVALS FOR ALOBOND PLUS THAT WILL MEET THE REQUIRED |
| | FIRE |
| | RATING AND WIND RATING. TO BE REVIEWED AND APPROVED BY |
| | THE DESIGN PROFESSIONAL BEFORE SUBMITANCE TO THE CITY |
| | FOR |
| | REVIEW. |
| | |
| | 1407.10 TYPE I, II, III AND IV CONSTRUCTION. |
| | WHERE INSTALLED ON BUILDINGS OF TYPE I, II, III AND IV |
| | CONSTRUCTION, MCM SYSTEMS SHALL COMPLY WITH SECTIONS |
| | 1407.10.1 THROUGH 1407.10.4 , OR 1407.11 . |
| | |
| | 1407.10.1 SURFACE-BURNING CHARACTERISTICS. |
| | MCM SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 |
| | AND A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450 WHEN |
| | TESTED AS AN ASSEMBLY IN THE MAXIMUM THICKNESS INTENDED |
| | FOR USE IN ACCORDANCE WITH ASTM E 84. |
| | |
| | 1609.1.1 DETERMINATION OF WIND LOADS. |
| | WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE |
| | DETERMINED IN ACCORDANCE WITH SECTION 6 OF ASCE |
| | 7.EXCEPTION# 2 WIND TUNNEL TEST, THE MCM PANELS MAY |
| | NEED |
| | ENHANCED FASTENING FOR THE LOCATION ON THE BUILDING. |
| | THIS ISTO BE COMPLETED BY THE ENGINEER OF RECORD. |
| | |
| | WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT |
| | WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |