| 2007-01-11 10:00:54 | PLANS BACK FOR PROCESSING |
| 2006-12-09 21:05:42 | ** UNSAT ** |
| | PLEASE SEE SOME MINOR NOTES FOR THE FOLLOWING SHEETS. |
| | E-1.01, 3.03, 1.06, AND 3.07. |
| | |
| | 1) NOTE: PLEASE SEE SHEET 1.01, PLEASE CLARIFY ELEVATOR |
| | PIT LIGHTING CONTROL, COULD NOT LOCATE SEPARATE SPACE |
| | CONTROL. PLEASE KNOW THAT AN OCCUPANT TYPE DEVICE WOULD |
| | NOT BE RECOMMENDED AND PERHAPS A 4HR TIMER? |
| | PLEASE SEE RETAIL SPACES #1 AND #2 AS LIGHTING CONTROL |
| | IS BEING SHOWN AT ONE POINT OF ENTRANCE ONLY. PLEASE |
| | SEE BANK AREA INDICATES CONTROLS AT BOTH POINTS OF |
| | INGRESS/EGRESS. |
| | 13-415.1.ABC.1.2 |
| | |
| | 2) NOTE: PLEASE SEE E1.06, PLEASE CLARIFY TELEPHONE |
| | /DATA ROOM LIGHTING FOR FLOORS 8 AND 11? |
| | 13-415.1.ABC.1.2 |
| | |
| | 3) NOTE: PLEASE SEE E3.03; PLEASE SEE WHAT APPEARS TO |
| | BE A MISPRINT FOR PARALLEL SWITCH GEAR LIGHTING LOADS. |
| | PLEASE SEE THESE ARE NOTED AT 100%, WHERE LOAD DOES |
| | APPEAR TO BE FIGURED AT 125%. |
| | 215.3,230.42 ETC |
| | PLEASE CORRELATE. |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 4) NOTE: PLEASE SEE E3.07; PLEASE SEE MISSING LOAD FOR |
| | "P-2" INDICATE A 600A BREAKER FOR THIS EQUIPMENT, BUT |
| | LOAD IS BLANK. IT IS NOTICED THE P-1 WAS ADJUSTED TO |
| | INDICATE 600A OCP FOR THE 200 HP LOAD. |
| | PLEASE ADJUST/CLARIFY IN RESPONSE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |