2007-01-11 10:00:54PLANS BACK FOR PROCESSING
2006-12-09 21:05:42** UNSAT **
 PLEASE SEE SOME MINOR NOTES FOR THE FOLLOWING SHEETS.
 E-1.01, 3.03, 1.06, AND 3.07.
  
 1) NOTE: PLEASE SEE SHEET 1.01, PLEASE CLARIFY ELEVATOR
 PIT LIGHTING CONTROL, COULD NOT LOCATE SEPARATE SPACE
 CONTROL. PLEASE KNOW THAT AN OCCUPANT TYPE DEVICE WOULD
 NOT BE RECOMMENDED AND PERHAPS A 4HR TIMER?
 PLEASE SEE RETAIL SPACES #1 AND #2 AS LIGHTING CONTROL
 IS BEING SHOWN AT ONE POINT OF ENTRANCE ONLY. PLEASE
 SEE BANK AREA INDICATES CONTROLS AT BOTH POINTS OF
 INGRESS/EGRESS.
 13-415.1.ABC.1.2
  
 2) NOTE: PLEASE SEE E1.06, PLEASE CLARIFY TELEPHONE
 /DATA ROOM LIGHTING FOR FLOORS 8 AND 11?
 13-415.1.ABC.1.2
  
 3) NOTE: PLEASE SEE E3.03; PLEASE SEE WHAT APPEARS TO
 BE A MISPRINT FOR PARALLEL SWITCH GEAR LIGHTING LOADS.
 PLEASE SEE THESE ARE NOTED AT 100%, WHERE LOAD DOES
 APPEAR TO BE FIGURED AT 125%.
 215.3,230.42 ETC
 PLEASE CORRELATE.
 FBC 106.1.2 ADMIN SECTION.
  
 4) NOTE: PLEASE SEE E3.07; PLEASE SEE MISSING LOAD FOR
 "P-2" INDICATE A 600A BREAKER FOR THIS EQUIPMENT, BUT
 LOAD IS BLANK. IT IS NOTICED THE P-1 WAS ADJUSTED TO
 INDICATE 600A OCP FOR THE 200 HP LOAD.
 PLEASE ADJUST/CLARIFY IN RESPONSE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  