| Date |
Text |
| 2006-10-31 14:00:46 | PROVISO: |
| | THE FOLLOWING ITEMS ARE TO BE SUBMITTED AS REVISIONS |
| | |
| | RESPONSE TO COMMENT 1:PLAN SHEET H0.03 REVISED DETAIL |
| | 25 FOR THE ACCU 1 & 2. |
| | |
| | PLEASE CLARIFYTHE CONCRETE SLABFOR THE CONDENSING |
| | UNIT ON THE ROOF TOP.PLEASE SPECIFY THE ROOF MATERIAL |
| | THIS SLAB WILL BE SETTING ON.IT APPEARS THESE UNITS |
| | ARE ACTUALLY INSTALLED IN THE GARAGE AREAS. |
| | |
| | |
| | RESPONSE TO COMMENT 2:PLANS SHEET H0.03 REVISED |
| | DETAIL 26.THE RESPONSE INDICATES THE CURB WILL BE 18" |
| | HIGH. |
| | |
| | ACCORDING TO THE DETAIL THE 18" DEMINSION IS THE |
| | CLEARANCE BETWEEN THE ROOF SURFACE AND THE BOTTOM OF |
| | THE ACCU.IS THESE CURBS "PATE CURBS"WILL THE |
| | FLASHING HAVE TO EXTEND UNDERNEATH THE ACCU?PLEASE |
| | NOTE, THE CLEARANCE BETWEEN THE ROOF SURFACE AND THE |
| | BOTTOM OF ACCU IS DETERMINED BY THE WIDTH OF THE UNIT |
| | IN ACCORDANCE WITH 2004 FBE 1509.7. |
| | |
| | |
| | RESPONSE TO COMMENT 3:PLAN SHEET H1.01 INDICATES THE |
| | TERMINATION OF CIF-6 IS 10 FT ABOVE GRADE. |
| | |
| | PLEASE NOTE, THE EXHAUST FROM THIS IS FROM THE LOADING |
| | DOCK FOR THE REMOVAL OF CARBON MONOXIDE.PER 2004 FMC |
| | 401.5.1HAZAROUS OR NOXIOUS CONTAMINANT SHALL BE LOCATED |
| | A MINIMUM OF 10 FROM OPENINGS.PER 501.2 AIR REMOVED |
| | BY EVERY MECHANICAL EXHAUST SHALL DISCHARGE OUTDOORS AT |
| | A POINT WHERE IT WILL NOT CAUSE A NUISANCE.BY |
| | DEFINITION A NUISANCE IS CONSIDERED THAT WHICH IS |
| | DETRIMENTAL TO HEALTH, WHICH CARBON MONOXIDE IS. |
| | |
| | |
| | RESPONSE TO COMMENT 4 & 5 WERE ADDRESSED. |
| | |
| | COMMENT 6 WAS NOT ADDRESSED:PLAN SHEET H1.02, H1.03, |
| | & H1.05, PLEASE INDICATE IF THE CONDENSING UNITS ARE |
| | LOCATED IN SIDE THE GARAGE AREA.PLEASE PROVIDE |
| | INSTALLATION INSTRUCTIONS INDICATING THIS IS ACCEPTABLE |
| | TO THE MANUFACTURER. |
| | |
| | |
| | COMMENT 7 & 8 WERE NOT ADDRESSED:VENTILATION FOR THE |
| | STORAGE AREAS - PER OUR CONVERSATION, CO SENSORS ARE TO |
| | BE INSTALLED INTO NON-HABITABLE SPACES WHEN THE MAKE-UP |
| | AIR BEING PROVIDED IS ACHIEVED THROUGH THE GARAGE |
| | SPACE. |
| | |
| | COMMENT 9 THROUGH 14 WERE ADDRESSED. |
| | |
| | PLEASE NOTE, ADDITIONAL PERMIT REQUIRED FOR THE FUEL |
| | TANK, FUEL PIPING AND GENERATOR.PLANS FOR THE FUEL |
| | TANK NEED APPROVAL FROM DERM.PLANS MAY BE SUBMITTED |
| | TO: |
| | THE ATTENTION OF CHIP GREEN |
| | 3323 BELVEDERE RD. BUILDING #502 |
| | WEST PALM BEACH, FL |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS |
| | AT (561)805-6719 OR E-MAIL [email protected]. |
| | |
| | |
| | |