| 2006-11-07 07:25:44 | MEP'S, IN ELEC FOR STAMPING OF PROVISO. |
| 2006-10-31 16:06:43 | ******* PROVSIO ******* |
| | |
| | ** PLEASE KNOW A 30 DAY PROVISION FOR THE COMMENTS 1-8 |
| | ARE BEING GIVEN AT THIS TIME.PLEASE MAKE THE |
| | CORRECTIONS FOR REVIEW. COMPLIANCE MUST BE COMPLETED, |
| | REVIEWED AND STAMPED FOR THESE ITEMS BEFORE THE 30 DAY |
| | TIME PERIOD EXPIRES. |
| | 12/1/06 |
| | |
| | ** PLEASE ALSO KNOW A 90 DAY PROVSION IS BEING GRANTED |
| | FOR THE GENERATOR AND SUB-BASE FUEL TANK , SEE COMMENT |
| | #9. |
| | |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS WHICH |
| | ARE STILL IN NEED OF ADDRESSING AND NEW CHANGES WHICH |
| | NEED TO BE MADE AS CERTAIN ITEMS ARE NOT GOING TO TAKE |
| | PLACE UNDER THIS PERMIT OR PLANS. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE MULTIPLE ENERGY CALCULATIONS WERE |
| | SUBMITTED FOR BOTH METHOD "A" AND "B", AS PER |
| | CONVERSATION WITH MR. WORKS, METHOD "B" WILL BE USED |
| | AND METHOD "A" WILL BE REMOVED. |
| | |
| | 2) NOTE: PLEASE SEE THERE ARE STILL MANY AREAS/ROOMS ON |
| | PLANS WHICH ARE MISSING REQUIRED CONTROLS PER FBC 2004 |
| | 13-415.1.ABC.1.2. |
| | ** ALL ROOMS AND AREAS CONTAINING FLOOR TO CEILING |
| | HEIGHT PARTITIONS SHALL REQUIRE AND OVER-RIDE DEVICE. |
| | (MAXIMUM TIMES 4HRS FOR TIMER TYPE AND 30MINS FOR |
| | OCCUPANT SENSING TYPE.) |
| | PLEASE SEE SYMBOL LEGEND ON E0.01 SHALL INDICATE THESE |
| | TIMES ON THE DEVICES AS LISTED. |
| | MAIL ROOM, MACHINE ROOMS, CONFERENCE ROOM (6TH FLR), |
| | STORAGE ROOMS, ETC. |
| | ALL LOCATIONS GONE OVER WITH DESIGNER. |
| | |
| | 3) NOTE: PLEASE SEE NOTE ADDED TO FA SHEETS WHICH |
| | REQUIRES ALL AREAS TO BE DESIGNED FOR A MINIMUM OF 75 |
| | CANDELA PER FBC 2004 CHAPTER 11-4.28.3(4). THIS WAS NOT |
| | COMMENTED BY THIS REVIEW ON ANY PREVIOUS REVIEWS AS |
| | THIS WAS NOT IN THE ELECTRICAL PLAN REVIEW SCOPE AT |
| | THAT TIME. PLANS INDICATE 75C UNITS, HOWEVER LIGHTING |
| | LEVELS SHALL BE MAINTAINED IN "ALL" AREAS. PLEASE SEE |
| | 11-4.28.1 |
| | |
| | 4) NOTE: PLEASE SEE ALL ELECTRICAL/ ARCHITECTURAL |
| | DETAILS, DEVICES, PLANS AND SHEETS WITH REFERENCE TO |
| | THE ELEVATOR TOWER ON THE "B" BLOCK GARAGE SHALL BE |
| | REMOVED FROM SETS. |
| | PLEASE SEE RISER WHICH WILL ALSO REMOVE ALL ELECTRICAL |
| | WITH REFERENCE TO THIS. |
| | ALL LOCATIONS GONE OVER WITH DESIGNER. |
| | |
| | 5) NOTE: PLEASE SEE CIRCUITING FOR FUTURE "B" BLOCK |
| | ELEVATOR TOWER, VESTIBULE, MACHINE ROOM ETC SHALL MEET |
| | ALL CIRCUITING AS PREVIOUSLY NOTED ON OTHER REVIEWS. |
| | PLEASE SEE DEDICATED CIRCUITS REQUIRED FOR RECEPTACLES |
| | AND LIGHTS ARE REQUIRED PER 620.23 AND 620.24. PLEASE |
| | SEE RECEPTACLE CIRCUIT BEING NOTED ON PANEL SCHEDULE AS |
| | BEING AN A/C P-TAC UNIT. PLEASE SEE ELEVATOR CAB LT'S |
| | BEING SHOWN ON WITH OTHER ELECTRICAL EQUIPMENT. PLEASE |
| | KNOW A PANEL SCHEDULE WILL BE REQUIRED FOR THESE ITEMS |
| | ON FUTURE PLANS. |
| | THIS IS BEING NOTED AT THIS TIME AS THEY ARE SHOWN ON |
| | THESE DO NOT COMPLY. |
| | PLEASE SEE SHEET E2.01 SHOULD BE REMOVED ALL TOGETHER |
| | OR LEFT BLANK FOR ANY OTHER FUTURE USE. |
| | PLEASE SEE PANEL "P21N" SHOULD ALSO BE REMOVED FROM |
| | E3.07. |
| | ALL ITEMS GONE OVER WITH THE DESIGNER. |
| | |
| | 6) NOTE: PLEASE SEE MISSING PHOTO-METRICS FOR ALL |
| | EGRESS LOCATIONS AS REQUIRED PER NFPA-101 7.8.1.3, |
| | 7.9.2.2 AS NOTED ON BOTH PREVIOUS REVIEWS. |
| | PLEASE INDICATE ALL NORMAL AND EMERGENCY FOOT CANDLE |
| | LEVELS. |
| | ** PLEASE KNOW, SOME OF THESE WERE DONE AND STAIR |
| | TOWERS ARE OK. |
| | |
| | 7) NOTE: PLEASE SUBMIT COMPLETED LOAD CALCULATIONS FOR |
| | EACH SERVICE AS SHOWN AND INSTALLED. THIS WOULD BE THE |
| | 5000A SWITCH BOARD"SWBDB" ANDTHE 3000A "SWBDA". |
| | PLEASE SUBMIT AND INDICATE THE LOADS ON THE PARALLELING |
| | SWITCH GEAR/EM SIDE. |
| | PLEASE SHOW AND INDICATE CONTINUOUS LOADS ON THE LOAD |
| | CALCULATIONS AT 125%. A 1.25 FACTOR WAS ADDED TO |
| | PANELS. |
| | PLEASE SHOW AND INDICATE HOW ALL LOADS ARE BEING |
| | DERIVED AS REQUIRED IN THE NEC. |
| | PLEASE SEE PREVIOUS NOTES ON BOTH REVIEWS WHICH |
| | REFLECTED 220.3, 220.10, 220.11, 220.13, 215.3, AND |
| | 230.42 ETC. |
| | |
| | 8) NOTE: PLEASE KNOW THAT EMERGENCY LIGHTING FIXTURES |
| | OF SOME TYPE CONTAINING BATTERY BACK UP FOR A MINIMUM |
| | TIME OF 90MINS WILL BE REQUIRED IN ALL BATHROOMS BEING |
| | BUILT OUT UNDER THIS PERMIT. NFPA-101 7.8, 7.9 |
| | THIS WAS CONFIRMED WITH DESIGN TEAM, OWNERS AND CHIEF |
| | FIRE MARSHAL, AND THIS PLANS EXAMINER. |
| | |
| | ** GENERATOR PROVISO ** |
| | |
| | 9) NOTE: PLEASE KNOW AT THIS TIME THE GENERATOR AND |
| | SUB-BASE FUEL TANK IS NOT VALID UNDER THIS BUILDING |
| | PERMIT UNTIL SUCH TIME APPROVAL FROM DERM IS OBTAINED. |
| | THIS APPROVAL FROM DERM WILL BE REQUIRED TO BE REVIEWED |
| | BY THE MECHANICAL PLANS EXAMINER ANDTHE FIRE |
| | MARSHAL. PLEASE KNOW REVISED ELECTRICAL PLANS SHALL |
| | ALSO INCLUDE ALL INFORMATION AS REQUIREDFOR THE FIRE |
| | MARSHAL'S COMPLETE REVIEW OF NFPA-30, NFPA-704, |
| | NFPA-110, |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLANS EXAMINER |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |