| 2006-10-26 14:10:01 | 1. REQUIRED FIRE PROTECTION SYSTEMS # 10 NOTE NEEDS TO |
| | BE REVISED ON PAGE A0.20. STANDPIPE VALVES WILL NOT BE |
| | ACCEPTED ON INTERMEDIATE FLOORS BUT AT VERY FLOOR LEVEL |
| | WITHIN STAIRWELLS. |
| | 2. B GARAGE IS A SPRINKLER PROTECTED BUILDING. ITEM # 6 |
| | ON PAGE A0.20. STATES THAT IT IS NOT. |
| | 3. PLEASE DECLARE HOW ACCESS IS ACHEIVED TO THE SIAMESE |
| | CONNECTION FOR THE B BLOCK GARAGE STANDPIPE SYSTEM. |
| | 4. REVIEWED DATA FOR THE SECURITY TURNSTILE PLANNED FOR |
| | USE. PLEASE INDICATE ON THE PLANS THAT NO INTERFERENCE |
| | WITH EXITING WILL OCCUR BY USING THESE DEVICES. |
| | 5. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| | FOR THE TENSION CABLES SHOWN ON PAGE A4.03. |
| | 6. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR |
| | LOCATIONS. |
| | 7. PLEASE EXPLAIN HOW THE ELEVATOR LOBBIES ARE BEING |
| | SEPARATED FROM THE REMAINDER OF THE BUILDINGS FLOORS |
| | 6-14 ON PAGE A1.06. |
| | 8. IT APPEARS THAT THE COMMON BATHROOMS ARE EQUIPPED |
| | WITH LF1 FIXTURES. IN THE EVENT OF LOSS OF POWER THESE |
| | ROOMS POSSIBLE BE DARK. |
| | 9. ON PAGE FP1.01 SEVERAL ROOMS ARE PLANNED TO BE |
| | EXCLUDED FROM FIRE SPRINKLER PROTECTION. WHAT |
| | ALTERNATIVE FIRE PROTECTION IS PLANNED FOR THSES AREAS. |
| | HIGH-RISE BUILDINGS ARE TO BE COMPLETELY PROTECTED BY |
| | AUTOMATIC FIRE SPRINKLER SYSTEMS. |
| | 10. FUTURE TENANT SPACES WILL BE REQUIRED TO BE |
| | EQUIPPED WITH EXIT SIGNS AND EMERGENCY LIGHTING WHEN |
| | COMPLETED. |
| | 11. SMOKE DETECTORS APPEAR TO BE MISSING FROM SEVERAL |
| | STORAGE ROOMS ON THE FIRE ALARM DRAWINGS. |
| | 12. PLEASE EXPLAIN EXHAUST LOVER LOCATED NEXT TO STAIR |
| | # 1 EXIT DOOR ON PAGE H1.01. |
| | 13. PLEASE EXPLAIN SF1 ON PAGE H1.03 LOCATED ADJACENT |
| | TO GARAGE PROPER. |
| | 14. CO DETECTORS APPEAR TO BE LOCATED IN TENANT SPACES. |
| | PLEASE EXPLAIN. SOME DETECTORS CONTAIN MORE DETECTORS |
| | THAN OTHER ONES. |
| | 15. ALL FIRE DAMPERS SHALL BE DROP TESTED TO ENSURE |
| | PROPER OPERATION AFTER INSTALLATION. |
| | 16. THE SYMBOLS FOR SMOKE DETECTORS ARE IDENTICAL TO |
| | ONES USED FOR EXIT SIGNS. A REVIEW WAS CONFUSING AS THE |
| | SYMBOL USED IS UNIVERSALLY USED FOR EXIT SIGNS WHICH |
| | CAUSES CONFUSION. |
| | 17. THE PROPOSED FUEL TANK WILL PROBABLY NEED TO BE |
| | REGISTERED WITH PBC DERM DUE TO FACT THAT THE SIZE |
| | EXCEEDS 550 GALLONS. PLEASE CONTACT THEM IMMEDIATELY. |
| | 18. THE PHOENIX DRAWING FOR THE FUEL TANK FOR THE |
| | GENERATOR FAILS TO DISPLAY ANY LISTINGS OR APPROVALS. |
| | 19. PLEASE CONTACT THIS OFFICE AT 804-4709 TO DISCUSS |
| | THE FUEL TANK INSTALLATION. |
| | 20. HOW IS ACCESS ACHEIVED TO THE TWO EXITS SHOWN ON |
| | PAGE A1.02. AT LEAST FOUR SECURITY DEVICES ARE LOCATED |
| | ADJACENT TO THE AUTO DETAILING AREA. |
| | 21. NATURAL GAS INSTALLATION TO COMPLY WITH THE |
| | APPROPRIATE NFPA STANDARDS. |
| | |
| | |