Plan Review Notes
Plan Review Notes For Permit 06040957
Permit Number 06040957
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2006-10-26 14:10:011. REQUIRED FIRE PROTECTION SYSTEMS # 10 NOTE NEEDS TO
 BE REVISED ON PAGE A0.20. STANDPIPE VALVES WILL NOT BE
 ACCEPTED ON INTERMEDIATE FLOORS BUT AT VERY FLOOR LEVEL
 WITHIN STAIRWELLS.
 2. B GARAGE IS A SPRINKLER PROTECTED BUILDING. ITEM # 6
 ON PAGE A0.20. STATES THAT IT IS NOT.
 3. PLEASE DECLARE HOW ACCESS IS ACHEIVED TO THE SIAMESE
 CONNECTION FOR THE B BLOCK GARAGE STANDPIPE SYSTEM.
 4. REVIEWED DATA FOR THE SECURITY TURNSTILE PLANNED FOR
 USE. PLEASE INDICATE ON THE PLANS THAT NO INTERFERENCE
 WITH EXITING WILL OCCUR BY USING THESE DEVICES.
 5. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR THE TENSION CABLES SHOWN ON PAGE A4.03.
 6. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR
 LOCATIONS.
 7. PLEASE EXPLAIN HOW THE ELEVATOR LOBBIES ARE BEING
 SEPARATED FROM THE REMAINDER OF THE BUILDINGS FLOORS
 6-14 ON PAGE A1.06.
 8. IT APPEARS THAT THE COMMON BATHROOMS ARE EQUIPPED
 WITH LF1 FIXTURES. IN THE EVENT OF LOSS OF POWER THESE
 ROOMS POSSIBLE BE DARK.
 9. ON PAGE FP1.01 SEVERAL ROOMS ARE PLANNED TO BE
 EXCLUDED FROM FIRE SPRINKLER PROTECTION. WHAT
 ALTERNATIVE FIRE PROTECTION IS PLANNED FOR THSES AREAS.
 HIGH-RISE BUILDINGS ARE TO BE COMPLETELY PROTECTED BY
 AUTOMATIC FIRE SPRINKLER SYSTEMS.
 10. FUTURE TENANT SPACES WILL BE REQUIRED TO BE
 EQUIPPED WITH EXIT SIGNS AND EMERGENCY LIGHTING WHEN
 COMPLETED.
 11. SMOKE DETECTORS APPEAR TO BE MISSING FROM SEVERAL
 STORAGE ROOMS ON THE FIRE ALARM DRAWINGS.
 12. PLEASE EXPLAIN EXHAUST LOVER LOCATED NEXT TO STAIR
 # 1 EXIT DOOR ON PAGE H1.01.
 13. PLEASE EXPLAIN SF1 ON PAGE H1.03 LOCATED ADJACENT
 TO GARAGE PROPER.
 14. CO DETECTORS APPEAR TO BE LOCATED IN TENANT SPACES.
 PLEASE EXPLAIN. SOME DETECTORS CONTAIN MORE DETECTORS
 THAN OTHER ONES.
 15. ALL FIRE DAMPERS SHALL BE DROP TESTED TO ENSURE
 PROPER OPERATION AFTER INSTALLATION.
 16. THE SYMBOLS FOR SMOKE DETECTORS ARE IDENTICAL TO
 ONES USED FOR EXIT SIGNS. A REVIEW WAS CONFUSING AS THE
 SYMBOL USED IS UNIVERSALLY USED FOR EXIT SIGNS WHICH
 CAUSES CONFUSION.
 17. THE PROPOSED FUEL TANK WILL PROBABLY NEED TO BE
 REGISTERED WITH PBC DERM DUE TO FACT THAT THE SIZE
 EXCEEDS 550 GALLONS. PLEASE CONTACT THEM IMMEDIATELY.
 18. THE PHOENIX DRAWING FOR THE FUEL TANK FOR THE
 GENERATOR FAILS TO DISPLAY ANY LISTINGS OR APPROVALS.
 19. PLEASE CONTACT THIS OFFICE AT 804-4709 TO DISCUSS
 THE FUEL TANK INSTALLATION.
 20. HOW IS ACCESS ACHEIVED TO THE TWO EXITS SHOWN ON
 PAGE A1.02. AT LEAST FOUR SECURITY DEVICES ARE LOCATED
 ADJACENT TO THE AUTO DETAILING AREA.
 21. NATURAL GAS INSTALLATION TO COMPLY WITH THE
 APPROPRIATE NFPA STANDARDS.
  
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER
 804-4709
  