| Date |
Text |
| 2006-10-27 16:46:59 | **** PLEASE KNOW AS OF 10/27/06 THE CONDITION WHICH WAS |
| | GOING TO BE GRANTED ONLY IF ALL OTHER REVIEWS PASS, IS |
| | N LONGER AN OPTION. ALL ELECTRICAL CODE COMMENTS WILL |
| | BE REQUIRED TO BE ADDRESSED AT THIS TIME BEFORE NEXT |
| | RESUB. |
| | PLEASE PHONE CALL WAS PLACED TO MR DAVID WORKS AT |
| | APPROX 15:10ON TODAYS DATE AND INFORMED MR. WORKS OF |
| | THE STATUS. |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2006-10-21 14:08:52 | ***** UNSAT3RD REVIEW ****** |
| | |
| | 10/21/06 14:08:52 |
| | |
| | |
| | |
| | **** PLEASE KNOW PLANS ARE BEING PLACED INTO A FAILED |
| | STATUS AT THIS TIME. IF ALL OTHER ALL TRADES PASS ALL |
| | OTHER REVIEWS, A CONDITION KNOWN A "PROVISO" WILL BE |
| | GIVEN WHICH WILL GRANT ISSUANCE OFPERMIT FOR SAID |
| | PLANS WITH A CERATINAMOUNT OF TIME TO HAVE |
| | CORRECTIONS SUBMITTED. |
| | THIS TIME WILL BE 30 DAYS. |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS WHICH |
| | ARE STILL IN NEED OF ADDRESSING AND NEW CHANGES WHICH |
| | NEED TO BE MADE AS CERTAIN ITEMS ARE NOT GOING TO TAKE |
| | PLACE UNDER THIS PERMIT OR PLANS. |
| | |
| | ** SPOKE TO MR. DAVID WORKS VIA PHONE ON FRIDAY OCTOBER |
| | 20TH, 2006 |
| | |
| | 1) NOTE: PLEASE SEE MULTIPLE ENERGY CALCULATIONS WERE |
| | SUBMITTED FOR BOTH METHOD "A" AND "B", AS PER |
| | CONVERSATION WITH MR. WORKS, METHOD "B" WILL BE USED |
| | AND METHOD "A" WILL BE REMOVED. |
| | |
| | 2) NOTE: PLEASE SEE THERE ARE STILL MANY AREAS/ROOMS ON |
| | PLANS WHICH ARE MISSING REQUIRED CONTROLS PER FBC 2004 |
| | 13-415.1.ABC.1.2. |
| | ** ALL ROOMS AND AREAS CONTAINING FLOOR TO CEILING |
| | HEIGHT PARTITIONS SHALL REQUIRE AND OVER-RIDE DEVICE. |
| | (MAXIMUM TIMES 4HRS FOR TIMER TYPE AND 30MINS FOR |
| | OCCUPANT SENSING TYPE.) |
| | PLEASE SEE SYMBOL LEGEND ON E0.01 SHALL INDICATE THESE |
| | TIMES ON THE DEVICES AS LISTED. |
| | MAIL ROOM, MACHINE ROOMS, CONFERENCE ROOM (6TH FLR), |
| | STORAGE ROOMS, ETC. |
| | ALL LOCATIONS GONE OVER WITH DESIGNER. |
| | |
| | 3) NOTE: PLEASE SEE NOTE ADDED TO FA SHEETS WHICH |
| | REQUIRES ALL AREAS TO BE DESIGNED FOR A MINIMUM OF 75 |
| | CANDELA PER FBC 2004 CHAPTER 11-4.28.3(4). THIS WAS NOT |
| | COMMENTED BY THIS REVIEW ON ANY PREVIOUS REVIEWS AS |
| | THIS WAS NOT IN THE ELECTRICAL PLAN REVIEW SCOPE AT |
| | THAT TIME. PLANS INDICATE 75C UNITS, HOWEVER LIGHTING |
| | LEVELS SHALL BE MAINTAINED IN "ALL" AREAS. PLEASE SEE |
| | 11-4.28.1 |
| | |
| | 4) NOTE: PLEASE SEE ALL ELECTRICAL/ ARCHITECTURAL |
| | DETAILS, DEVICES, PLANS AND SHEETS WITH REFERENCE TO |
| | THE ELEVATOR TOWER ON THE "B" BLOCK GARAGE SHALL BE |
| | REMOVED FROM SETS. |
| | PLEASE SEE RISER WHICH WILL ALSO REMOVE ALL ELECTRICAL |
| | WITH REFERENCE TO THIS. |
| | ALL LOCATIONS GONE OVER WITH DESIGNER. |
| | |
| | 5) NOTE: PLEASE SEE CIRCUITING FOR FUTURE "B" BLOCK |
| | ELEVATOR TOWER, VESTIBULE, MACHINE ROOM ETC SHALL MEET |
| | ALL CIRCUITING AS PREVIOUSLY NOTED ON OTHER REVIEWS. |
| | PLEASE SEE DEDICATED CIRCUITS REQUIRED FOR RECEPTACLES |
| | AND LIGHTS ARE REQUIRED PER 620.23 AND 620.24. PLEASE |
| | SEE RECEPTACLE CIRCUIT BEING NOTED ON PANEL SCHEDULE AS |
| | BEING AN A/C P-TAC UNIT. PLEASE SEE ELEVATOR CAB LTS |
| | BEING SHOWN ON WITH OTHER ELECTRICAL EQUIPMENT. PLEASE |
| | KNOW A PANEL SCHEDULE WILL BE REQUIRED FOR THESE ITEMS |
| | ON FUTURE PLANS. |
| | THIS IS BEING NOTED AT THIS TIME AS THEY ARE SHOWN ON |
| | THESE DO NOT COMPLY. |
| | PLEASE SEE SHEET E2.01 SHOULD BE REMOVED ALL TOGETHER |
| | OR LEFT BLANK FOR ANY OTHER FUTURE USE. |
| | PLEASE SEE PANEL "P21N" SHOULD ALSO BE REMOVED FROM |
| | E3.07. |
| | ALL ITEMS GONE OVER WITH THE DESIGNER. |
| | |
| | 6) NOTE: PLEASE SEE MISSING PHOTO-METRICS FOR ALL |
| | EGRESS LOCATIONS AS REQUIRED PER NFPA-101 7.8.1.3, |
| | 7.9.2.2 AS NOTED ON BOTH PREVIOUS REVIEWS. |
| | PLEASE INDICATE ALL NORMAL AND EMERGENCY FOOT CANDLE |
| | LEVELS. |
| | ** PLEASE KNOW, SOME OF THESE WERE DONE AND STAIR |
| | TOWERS ARE OK. |
| | |
| | 7) NOTE: PLEASE SUBMIT COMPLETED LOAD CALCULATIONS FOR |
| | EACH SERVICE AS SHOWN AND INSTALLED. THIS WOULD BE THE |
| | 5000A SWITCH BOARD"SWBDB" ANDTHE 3000A "SWBDA". |
| | PLEASE SUBMIT AND INDICATE THE LOADS ON THE PARALLELING |
| | SWITCH GEAR/EM SIDE. |
| | PLEASE SHOW AND INDICATE CONTINUOUS LOADS ON THE LOAD |
| | CALCULATIONS AT 125%. A 1.25 FACTOR WAS ADDED TO |
| | PANELS. |
| | PLEASE SHOW AND INDICATE HOW ALL LOADS ARE BEING |
| | DERIVED AS REQUIRED IN THE NEC. |
| | PLEASE SEE PREVIOUS NOTES ON BOTH REVIEWS WHICH |
| | REFLECTED 220.3, 220.10, 220.11, 220.13, 215.3, AND |
| | 230.42 ETC. |
| | |
| | |
| | |
| | ** PLEASE KNOW ALL OF THE ABOVE WERE GONE OVER WITH MR. |
| | WORKS ITEM BY ITEM, AND PAGE BY PAGE. |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLANS EXAMINER |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| 2006-10-20 21:30:11 | *** UNSAT**** |
| | |
| | |
| | *** PLEASE KNOW A CALLED WAS PLACED TO MR DAVID WORKS |
| | AND A "MEETING" VIA THE PHONE TOOK PLACED FOR APPROX AN |
| | HOUR. |
| | |
| | ** PLEASE SEE REVIEW WILL BE GOING INTO A FAILED STATUS |
| | AND REVIEW NOTES WILL BE PLACED INTO THE COMPUTER AND |
| | PLACED ONLINE ON SATURDAY 10/21 AFTER APPROX 1PM EST. |
| 2006-10-19 20:58:15 | *** ELECTRICALPLANS IN ELECTRICAL FOR REVIEW,,,,, |