Plan Review Notes
Plan Review Notes For Permit 06040957
Permit Number 06040957
Review Stop E
Sequence Number 3
Notes
Date Text
2006-10-27 16:46:59**** PLEASE KNOW AS OF 10/27/06 THE CONDITION WHICH WAS
 GOING TO BE GRANTED ONLY IF ALL OTHER REVIEWS PASS, IS
 N LONGER AN OPTION. ALL ELECTRICAL CODE COMMENTS WILL
 BE REQUIRED TO BE ADDRESSED AT THIS TIME BEFORE NEXT
 RESUB.
 PLEASE PHONE CALL WAS PLACED TO MR DAVID WORKS AT
 APPROX 15:10ON TODAYS DATE AND INFORMED MR. WORKS OF
 THE STATUS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-10-21 14:08:52***** UNSAT3RD REVIEW ******
  
 10/21/06 14:08:52
  
  
  
 **** PLEASE KNOW PLANS ARE BEING PLACED INTO A FAILED
 STATUS AT THIS TIME. IF ALL OTHER ALL TRADES PASS ALL
 OTHER REVIEWS, A CONDITION KNOWN A "PROVISO" WILL BE
 GIVEN WHICH WILL GRANT ISSUANCE OFPERMIT FOR SAID
 PLANS WITH A CERATINAMOUNT OF TIME TO HAVE
 CORRECTIONS SUBMITTED.
 THIS TIME WILL BE 30 DAYS.
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS WHICH
 ARE STILL IN NEED OF ADDRESSING AND NEW CHANGES WHICH
 NEED TO BE MADE AS CERTAIN ITEMS ARE NOT GOING TO TAKE
 PLACE UNDER THIS PERMIT OR PLANS.
  
 ** SPOKE TO MR. DAVID WORKS VIA PHONE ON FRIDAY OCTOBER
 20TH, 2006
  
 1) NOTE: PLEASE SEE MULTIPLE ENERGY CALCULATIONS WERE
 SUBMITTED FOR BOTH METHOD "A" AND "B", AS PER
 CONVERSATION WITH MR. WORKS, METHOD "B" WILL BE USED
 AND METHOD "A" WILL BE REMOVED.
  
 2) NOTE: PLEASE SEE THERE ARE STILL MANY AREAS/ROOMS ON
 PLANS WHICH ARE MISSING REQUIRED CONTROLS PER FBC 2004
 13-415.1.ABC.1.2.
 ** ALL ROOMS AND AREAS CONTAINING FLOOR TO CEILING
 HEIGHT PARTITIONS SHALL REQUIRE AND OVER-RIDE DEVICE.
 (MAXIMUM TIMES 4HRS FOR TIMER TYPE AND 30MINS FOR
 OCCUPANT SENSING TYPE.)
 PLEASE SEE SYMBOL LEGEND ON E0.01 SHALL INDICATE THESE
 TIMES ON THE DEVICES AS LISTED.
 MAIL ROOM, MACHINE ROOMS, CONFERENCE ROOM (6TH FLR),
 STORAGE ROOMS, ETC.
 ALL LOCATIONS GONE OVER WITH DESIGNER.
  
 3) NOTE: PLEASE SEE NOTE ADDED TO FA SHEETS WHICH
 REQUIRES ALL AREAS TO BE DESIGNED FOR A MINIMUM OF 75
 CANDELA PER FBC 2004 CHAPTER 11-4.28.3(4). THIS WAS NOT
 COMMENTED BY THIS REVIEW ON ANY PREVIOUS REVIEWS AS
 THIS WAS NOT IN THE ELECTRICAL PLAN REVIEW SCOPE AT
 THAT TIME. PLANS INDICATE 75C UNITS, HOWEVER LIGHTING
 LEVELS SHALL BE MAINTAINED IN "ALL" AREAS. PLEASE SEE
 11-4.28.1
  
 4) NOTE: PLEASE SEE ALL ELECTRICAL/ ARCHITECTURAL
 DETAILS, DEVICES, PLANS AND SHEETS WITH REFERENCE TO
 THE ELEVATOR TOWER ON THE "B" BLOCK GARAGE SHALL BE
 REMOVED FROM SETS.
 PLEASE SEE RISER WHICH WILL ALSO REMOVE ALL ELECTRICAL
 WITH REFERENCE TO THIS.
 ALL LOCATIONS GONE OVER WITH DESIGNER.
  
 5) NOTE: PLEASE SEE CIRCUITING FOR FUTURE "B" BLOCK
 ELEVATOR TOWER, VESTIBULE, MACHINE ROOM ETC SHALL MEET
 ALL CIRCUITING AS PREVIOUSLY NOTED ON OTHER REVIEWS.
 PLEASE SEE DEDICATED CIRCUITS REQUIRED FOR RECEPTACLES
 AND LIGHTS ARE REQUIRED PER 620.23 AND 620.24. PLEASE
 SEE RECEPTACLE CIRCUIT BEING NOTED ON PANEL SCHEDULE AS
 BEING AN A/C P-TAC UNIT. PLEASE SEE ELEVATOR CAB LTS
 BEING SHOWN ON WITH OTHER ELECTRICAL EQUIPMENT. PLEASE
 KNOW A PANEL SCHEDULE WILL BE REQUIRED FOR THESE ITEMS
 ON FUTURE PLANS.
 THIS IS BEING NOTED AT THIS TIME AS THEY ARE SHOWN ON
 THESE DO NOT COMPLY.
 PLEASE SEE SHEET E2.01 SHOULD BE REMOVED ALL TOGETHER
 OR LEFT BLANK FOR ANY OTHER FUTURE USE.
 PLEASE SEE PANEL "P21N" SHOULD ALSO BE REMOVED FROM
 E3.07.
 ALL ITEMS GONE OVER WITH THE DESIGNER.
  
 6) NOTE: PLEASE SEE MISSING PHOTO-METRICS FOR ALL
 EGRESS LOCATIONS AS REQUIRED PER NFPA-101 7.8.1.3,
 7.9.2.2 AS NOTED ON BOTH PREVIOUS REVIEWS.
 PLEASE INDICATE ALL NORMAL AND EMERGENCY FOOT CANDLE
 LEVELS.
 ** PLEASE KNOW, SOME OF THESE WERE DONE AND STAIR
 TOWERS ARE OK.
  
 7) NOTE: PLEASE SUBMIT COMPLETED LOAD CALCULATIONS FOR
 EACH SERVICE AS SHOWN AND INSTALLED. THIS WOULD BE THE
 5000A SWITCH BOARD"SWBDB" ANDTHE 3000A "SWBDA".
 PLEASE SUBMIT AND INDICATE THE LOADS ON THE PARALLELING
 SWITCH GEAR/EM SIDE.
 PLEASE SHOW AND INDICATE CONTINUOUS LOADS ON THE LOAD
 CALCULATIONS AT 125%. A 1.25 FACTOR WAS ADDED TO
 PANELS.
 PLEASE SHOW AND INDICATE HOW ALL LOADS ARE BEING
 DERIVED AS REQUIRED IN THE NEC.
 PLEASE SEE PREVIOUS NOTES ON BOTH REVIEWS WHICH
 REFLECTED 220.3, 220.10, 220.11, 220.13, 215.3, AND
 230.42 ETC.
  
  
  
 ** PLEASE KNOW ALL OF THE ABOVE WERE GONE OVER WITH MR.
 WORKS ITEM BY ITEM, AND PAGE BY PAGE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
2006-10-20 21:30:11*** UNSAT****
  
  
 *** PLEASE KNOW A CALLED WAS PLACED TO MR DAVID WORKS
 AND A "MEETING" VIA THE PHONE TOOK PLACED FOR APPROX AN
 HOUR.
  
 ** PLEASE SEE REVIEW WILL BE GOING INTO A FAILED STATUS
 AND REVIEW NOTES WILL BE PLACED INTO THE COMPUTER AND
 PLACED ONLINE ON SATURDAY 10/21 AFTER APPROX 1PM EST.
2006-10-19 20:58:15*** ELECTRICALPLANS IN ELECTRICAL FOR REVIEW,,,,,