| Date |
Text |
| 2006-10-27 12:46:07 | BUILDING PLAN REVIEW |
| | PERMIT: 06040957 |
| | ADD: 525 OKEECHOBEE BLVD |
| | CONT: CENTEX CONSTRUCTION |
| | TEL: (954)214-9415 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | ---CITY PLACE OFFICE TOWER--- |
| | |
| | 3RDREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) SHEET A0.20: |
| | 2A) NORTH ELEVATOR TOWER COMPLIANCE: |
| | COMMENT# 10A FROM THE PREVIOUS REVIEW, |
| | ALTHOUGH THE NORTH ELEVATOR TOWER IS IN |
| | THIS SET OF DOCUMENTS, A SEPERATE PERMIT |
| | WILL BE REQUIRED. |
| | |
| | 2B) SHEET A0.20 CODE COMPLIANCE NOTE# 6 |
| | FOR THE NORTH ELEVATOR TOWER INDICATES THAT THE |
| | EXISTING |
| | PARKING GARAGE IS NOT FIRE SPRINKLERED, THIS IS |
| | INCORRECT. |
| | THE B-BLOCK STORES AND PARKING GARAGE ARE CONSIDERED |
| | ONE |
| | BUILDING FOR THE AREA INCREASES TAKEN UNDER THE |
| | ORIGINAL PERMIT THIS WAS A REQUIREMENT. |
| | |
| | 3) 3RD REQUEST, COMMENT# FROM THE PREVIOUS |
| | REVIEW, A4.11 ELV 42'-0",A4.12 SOUTH WALL SECTION, |
| | EL. 66'-6",A4.13 & |
| | A4.14 INDICATES THE USE OF EFIS TRIM ON |
| | THE EXTERIOR OF THE BUILDING.1406.2.2 ARCHITECTURAL |
| | TRIM. IN BUILDINGS OF TYPE |
| | I, II, III AND IV CONSTRUCTION THAT DO |
| | NOT EXCEED THREE STORIES OR 40 FEET (12 |
| | 192 MM) IN HEIGHT ABOVE GRADE PLANE, |
| | EXTERIOR WALL COVERINGS SHALL BE |
| | PERMITTED TO BE CONSTRUCTED OF WOOD |
| | WHERE PERMITTED BY SECTION 1405.4 OR |
| | OTHER EQUIVALENT COMBUSTIBLE MATERIAL. |
| | COMBUSTIBLE EXTERIOR WALL COVERINGS, |
| | OTHER THAN FIRE-RETARDANT-TREATED WOOD |
| | COMPLYING WITH SECTION 2303.2 FOR |
| | EXTERIOR INSTALLATION, SHALL NOT EXCEED |
| | 10 PERCENT OF AN EXTERIOR WALL SURFACE |
| | AREA WHERE THE FIRE SEPARATION DISTANCE |
| | IS 5 FEET (1524 MM) OR LESS. |
| | ARCHITECTURAL TRIM THAT EXCEEDS 40 FEET |
| | (12 192 MM) IN HEIGHT ABOVE GRADE PLANE |
| | SHALL BE CONSTRUCTED OF APPROVED |
| | NONCOMBUSTIBLE MATERIALS AND SHALL BE |
| | SECURED TO THE WALL WITH METAL OR OTHER |
| | APPROVED NONCOMBUSTIBLE BRACKETS. |
| | |
| | 4A) COMMENT # 23 FROM THE PREVIOUS REVIEW, |
| | A4.1.2 PLANS INDICATE USE OF MCM |
| | ( METAL COMPOSITE MATERIALS) SEE: |
| | 1407.3 ARCHITECTURAL TRIM AND |
| | EMBELLISHMENTS. |
| | MCM USED AS ARCHITECTURAL TRIM OR |
| | EMBELLISHMENTS SHALL COMPLY WITH |
| | SECTIONS 1407.7 THROUGH 1407.13 . |
| | 1407.10 TYPE I, II, III AND IV |
| | CONSTRUCTION. |
| | WHERE INSTALLED ON BUILDINGS OF TYPE I, |
| | II, III AND IV CONSTRUCTION, MCM SYSTEMS |
| | SHALL COMPLY WITH SECTIONS 1407.10.1 |
| | THROUGH 1407.10.4 , OR 1407.11 . |
| | |
| | WE HAVE RECEIVED A COPY OF THE MIAMI-DADE NOA, WHICH |
| | INDICATES IN THERE TECHNICAL SHEETS THIS PRODUCT DOES |
| | HAVE A COMBUSTIBLE PLASTIC CENTER PANEL.THE CODE |
| | COMMENTARY READS UNDER ARTICLE 1407.3 REFERSYOU BACK |
| | TO 1406.2.2, COMBUSTIBLE TRIM ON BUILDINGS OVER 40'-0" |
| | TALL CAN NOT BE USED ABOVE 40'-0". |
| | |
| | 1407.10.1 INDICATES WHAT TYPE OF MCM PANELS ARE ALLOWED |
| | ON A TYPEI BUILDING. |
| | 1407.11.1 WHAT TYPE MCM PANELS ARE ALLOWED TO THE |
| | HEIGHT OF 40'-0". |
| | 1407.11.2 WHAT IS ALLOWABLE TO A HEIGHT OF 50'-0". |
| | |
| | 4B) DETAIL 25/ A5.47 INDICATES THE USE OF ALUMIMUM |
| | EXTRUSIONS, THIS WILL |
| | BE ALLOWABLE AS SHOWN, NOT HAVING A PLASTIC CENTER |
| | PANEL. BUILDING PROVISO: |
| | SHOP DRAWINGS WILL BE REQUIRED INDICATING SIZE AND |
| | CONDITIONS FOR ANCHORING PANELS. |
| | |
| | 5 COMMENT#24 FROM THEPREVIOUS REVIEW, THIRD REQUEST, |
| | TO DELETE THE PHRASE "SYNTHETIC TYPE DIRECTAPPLIED |
| | FINISH SYSTEM OVER GLASS MAT GYPUM SHEATHING."A4.14 |
| | DETAILS INDICATE A COVERED DROP OFF AREA WITH THE USE |
| | OF THE WORDAGE ABOVE, |
| | THIS HAS BEEN CHANGED BUT THE FINISH SYSTEM IS NOT |
| | PROVIDED. |
| | DETAIL7/ A4.21 DOES |
| | USE THE PHRASE AS STATED ABOVE, WE CONSIDER THIS AN |
| | EFIS |
| | SYSTEM, PROVIDE REPORT WITH APPROVED HORIZONTAL USEAGE. |
| | RULE 9B-72 FL |
| | ADDMINISTRATIVE COVE. WHEN USED IN A HORIZONTAL PLANE |
| | THE PRODUCT HAS TO INDICATE SUCH USAGE. |
| | |
| | 6)COMMENT 34D) FROM THE PREVIOUS REVIEW, |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG. |
| | NO REPORT WAS SUBMITTED FOR EXTERIOR |
| | HOLLOW METAL DOORS, SINGLE NOR PAIRS. |
| | |
| | EXTERIOR GLAZED DOORS:YKK DOORS NEITHER THE LARGE |
| | MISSLE OR SMALL MISSLE REPORTS HAVE |
| | THE GLASS TYPE NOR MULLIONS HIGHLIGHTED. |
| | |
| | CORNELL IRONWORKS: NONE OF THE SUBSYSTEMS |
| | ARE HIGHLIGHTED INDICATING WHICH SYSTEM WILL |
| | BE USED FOR THIS PROJECT. |
| | |
| | LOUVER : THE REPORT SUBMITTED HAS LOW |
| | PRESSURESCOMPARED |
| | |
| | TO THE WIND TUNNEL TEST. |
| | |
| | EFIS REPORT MISSING THIS REPORT TOTALLY. |
| | |
| | ROOFING ASSEMBLIES: HIGHLIGHT WHICH SUBSYSTEM YOU WILL |
| | BE INSTALLING. |
| | SEE LIMITATION# 7 IF ENHANCED FASTENING WILL BE |
| | REQUIRED. IF REQUIRED |
| | USE RAS 117 FOR CALCULATIONS. PROVIDE CALCULATIONS. |
| | THE ROOFING REPORTSUBMITTED FL 1075 SIPLAST / I COPAL |
| | THE HIGHLIGHTED SUBSYSTEM (SBS)FOR CONCRETE DECKS HAS |
| | LOW PRESSURES AND LIMITATION # 9, NO ENHANCED |
| | FASTENING. |
| | ALSO THE SUBSYSTEM FOR STEEL DECKS ALSO HAS LOW |
| | PRESSURE AND LIMITATION #9, NO ENHANCED FASTENING |
| | ALLOWED. |
| | |
| | 7) THE WIND STUDY REPORTCOMPLETED BY RWDI IS NOT A |
| | FINAL REPORT ONLY A DRAFT. |
| | THE CITY WILL NEED 3 FINAL REPORTS SIGNED AND SEALED. |
| | |
| | PLANS, SPECIFICATIONS, REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND |
| | BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 8) NOTE ALSO A COMMENT FROM FIRE DEALING WITH AREAS OF |
| | THE BUILDING THAT ARE NOT FIRE SPRINKLERED, |
| | IF THE BUILDING IS NOT EQUIPPED THROUGHOUT WITH A |
| | AUTOMATIC FIRE SPRINKLER IN ACCORDANCE WITH 903.3.1.1 |
| | THEN |
| | THE REQUIREMENTS 704.9, FIGURE 709.4.1 FOR SPANDREL |
| | GIRDERS . SUCH OPENINGS SHALL BE SEPERATED VERTICALLY |
| | AT 3 FT BY SPANDREL GIRDERS, EXTERIOR WALLS OR OTHER |
| | ASSEMBLIES THAT HAVE A FIRE RESISTANCE RATING OF AT |
| | LEAST 1 HR. |
| | WEST PALMBEACH |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |