2008-07-25 11:28:45REVIEW OF CALCS WAS PLACED ON HOLD PENDING CONFERENCE
 CALL WITH AHA DESIGN TEAM WHICH TOOK PLACE 7/25/08 AT
 APPROX. 8:15 AM.
  
 CLARIFICATION IS REQUIRED TO COORDINATE THE INPUT DATA
 REPORT (IDR) WITH THE PLANS. THE FOLLOWING ISSUES SHALL
 BE ADDRESSED:
  
 1. PAGE 104 OF THE IDR SHOWS A SYSTEM 7 WITH HP-3. THIS
 SYSTEM ON THE PLANS CALLS FOR A 3 TON SYSTEM WHILE THE
 IDR CALS FOR A 5 TON SYSTEM. PLEASE COODINATE THIS
 SYSTEM ON BOTH DOCUMENTS.
  
 2. PAGE 105 OF THE IDR SHOWS A SYSTEM 9 WITH HP-1. THIS
 SYSTEM ON BASE BUILDING PLANS HAS BEEN DELETED. PLEASE
 IDENTIFY WHERE THIS SYSTEM IS LOCATED AND PROVIDE A
 DESIGNATION WHICH IDENTIFIES ITS LOCATION IF NOT PART
 OF THE BASE BUILDING.
  
 3. PAGE H0.02 OF THE BASE BUILDING PLANS SHOWS AN HP-2
 ON THE HEAT PUMP SCHEDULE. THIS SYSTEM IS NOT
 REPRESENTED IN THE ENERGY CALCULATIONS AND COULD NOT BE
 FOUND IN THE IDR. PLEASE COORDINATE THIS SYSTEM ON BOTH
 DOCUMENTS.
  
 ALL OTHER LISTED SYSTEM COMPONENTS ARE IN COMPLIANCE
 AND REQUIRE NO FURTHER ACTION.
  