2008-05-14 13:23:43REVISED ENERGY CALCULATIONS DATED 5/7/08:
  
 1. THE MAX TONNAGE SHOWN ON THE FRONT OF THE FORM IS
 SHOWN AS 80 TONS. THIS DOES NOT CORRESPOND WITH THE
 APPLIANCE SCHEDULE ON PG H0.02. THE SCHEDULE SHOWS
 PAC-3 AS 90 TONS. PLEASE COORDINATE ENERGY CALCULATIONS
 WITH BUILDING PLANS IN ACCORDANCE WITH FBCB 13-103.2.
  
 2. THE COMPLIANCE CERTIFICATION PAGE HAS NOT BEEN
 COMPLETED. EXAMPLE: THIS PAGE INDICATES THE
 CALCULATIONS WERE PREPARED BY DENNIS J STROER. THE
 BUILDING OFFICIAL SHALL REQUIRE, SUBJECT TO THE
 EXCEPTIONS IN SECTION 481.229, FLORIDA STATUTES, AND
 SECTION 471.003, FLORIDA STATUTES, THAT PLANS AND
 SPECIFICATIONS, INCLUDING THE ENERGY CODE CALCULATIONS,
 BE PREPARED BY AN ENGINEER OR ARCHITECT LICENSED TO
 PRACTICE IN THE STATE OF FLORIDA IN ACCORDANCE WITH
 FBCB 13-103.2. THERE IS NO LICENSE INFORMATION OR
 SIGNATURE AND SEAL FROM THIS PERSON SHOWING THEM TO
 MEET THESE CRITERIA. THIS PERSON HAS NOT CERTIFIED
 THESE CALCULATIONS OR THIS BUILDING TO BE IN COMPLIANCE
 WITH THE FLORIDA ENERGY EFFICIENCY CODE AS REQUIRED ON
 THE COMPLIANCE CERTIFICATION FORM. PLEASE CORRECT AND
 RESUBMIT.
  
 3. DESIGN PROFESSIONALS RESPONSIBLE UNDER FLORIDA LAW
 FOR THE DESIGN OF LIGHTING, ELECTRICAL, MECHANICAL, AND
 PLUMBING SYSTEMS AND THE BUILDING SHELL, SHALL CERTIFY
 COMPLIANCE OF THOSE BUILDING SYSTEMS WITH THE CODE BY
 SIGNING AND PROVIDING THEIR PROFESSIONAL REGISTRATION
 NUMBER ON THE ENERGY CODE FORM PROVIDED AS PART OF THE
 PLANS AND SPECIFICATIONS TO THE BUILDING DEPARTMENT.
 EXCEPTION: TYPED NAMES AND REGISTRATION NUMBERS MAY BE
 PROVIDED IN LIEU OF A SIGNATURE WHERE ALL RELEVANT
 INFORMATION HAS BEEN INCLUDED ON SIGNED AND SEALED
 PLANS.
 NEITHER OF THESE WAS PROVIDED AS REQUIRED IN ACCORDANCE
 WITH FBCB 13-103.1.1. PLEASE SEE ALL AREAS OF THE
 COMPLIANCE CERTIFICATION FORM WHICH HAVE NOT BEEN
 FILLED OUT. CORRECT AND RESUBMIT.
  
 4. THERE ARE DISCREPANCIES BETWEEN THE INPUT DATA
 REPORT (IDR) AND THE PLANS REGARDING THE COOLING
 CAPACITIES OF THE MECHANICAL APPLIANCES. EXAMPLE: PAC
 1-16 IN THE IDR, WHICH CORRESPONDS WITH PAC-3 ON THE
 APPLIANCE SCHEDULE ON PAGE H0.02, IS SHOWN TO HAVE A
 COOLING CAPACITY OF 960,000 BTU/H WHILE THE PLANS SHOW
 A CAPACITY OF 1,066,000 BTU/H.
  
 THIS IS ONLY ONE EXAMPLE. THERE ARE OTHER
 DISCREPANCIES. PLEASE VERIFY ALL VALUES ENTERED IN THE
 (IDR) CORRESPOND WITH THE MECHANICAL SYSTEMS ON THE
 PLANS, CORRECT AND RESUBMIT.
  