| 2008-07-16 12:59:54 | ** DENIEDREVISIONS ** |
| | |
| | |
| | 1) NOTE:AS STATED ON PREVIOUS REVIEWS, MEETINGS, |
| | PHONE CALLS AND E-MAILS. PLEASE BE SURE TO UPDATE |
| | LIGHTING ON PLANS, UPDATE FIXTURE LEGEND AND BE SURE |
| | ALL LIGHTING ON PLANS IS PLACED INTO THE ENERGY |
| | CALCULATIONS AS REQUIRED BY THE FBC CHAPTER 13. 13-400, |
| | 13-101, 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE SOME EXAMPLES WILL BE GIVEN BELOW AS A |
| | BENEFIT. |
| | THIS IS *NOT* AN EXHAUSTED LIST. |
| | |
| | FOR EXAMPLE: |
| | PLEASE TAKE A LOOK AT THE FIXTURE LEGEND. PLEASE SEE |
| | PLANS AS THERE ARE NUMEROUS FIXTURES ON PLANS WHICH ARE |
| | NOT LISTED ON THE FIXTURE LEGEND ON SHEET E3.02. SOME |
| | OF THESE ARE LG, ED, EE, LB, LC, EA, EB ETC. |
| | HOW CAN A REVIEW OF ENERGY CALCULATIONS BE VERIFIED |
| | WHEN THE WATTAGE OF FIXTURES ARE NOT SHOWN? |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE SHEET E1.00. THERE ARE 250W, 400W FIXTURES. |
| | THERE ARE NO 400W OR 250W FIXTURES AT ALL IN THE INPUT |
| | DATA REPORT ON THE SUBMITTED ENERGY CALCULATIONS. THESE |
| | ARE NOT THE ONLY FIXTURES. PLEASE TAKE A LOOK AT THE |
| | EXAMPLE ABOVE. |
| | |
| | ** HOW CAN CALCULATIONS BE COMPLETE, ACCURATE AND |
| | VERIFIEDIF THE PLANS ARE NOT COMPLETE OR COORDINATE |
| | TO DATE? |
| | |
| | FOR EXAMPLE: |
| | IT WAS PREVIOUSLY MENTIONED BY THE MECHANICAL REVIEWER |
| | AND THIS REVIEW TO ALSO MAKE SURE ALL BUILDING |
| | COMPONENTS ON PLANS ARE PLACED INTO THE ENERGY |
| | CALCULATIONS. THERE WILL BE COMMENTS FROM OTHER TRADES |
| | AS SOME OF THESE ITEMS IN THE IDR ARE SEEN BY THIS |
| | REVIEWER. |
| | |
| | 2) NOTE: PLEASE BE SURE ALL PERMITTED TENANT PLANS FOR |
| | KNOWN LOADS, LIGHTING USE ETC ARE REVISED INTO THE BASE |
| | BUILDING. |
| | FOR EXAMPLE: |
| | CLEVELAND CLINIC AT BOTH LOCATIONS. |
| | NEC 220, FBC 13-415.2 |
| | FBC 106.1.1, 106.5 FOR CLARITY AND RECORD SETS OF |
| | PLANS. |
| | |
| | 3) NOTE: PLEASE BE SURE THE ENGINEER RAISED SEAL IS |
| | PLACED TO THE FRONT ON SHEETS. THESE DOCUMENTS ARE |
| | SCANNED AND INFORMATION NEEDS TO FACE FORWARD TO BE |
| | EASILY READ AS PART OF THE RECORD PLANS. PLEASE SEE |
| | SHEETS E3.03.1 IN ALL THREE SETS ARE SEAL BACKWARDS. |
| | THIS IS NOT NECESSARILY A VIOLATION AS THE STATUTE DOES |
| | NOT SAY IF THE SEAL CAN BE ON THE BACK OF THE PLANS |
| | HOWEVER BASED ON SCANNING OF PLANS AND DOCUMENTS THESE |
| | NEED TO BE READ ETC. |
| | THE INTENT OF THE STATUTE IS THAT THE SEAL IS FACING |
| | THE FRONT OF PLANS ETC. THIS WAS CONFIRMED WITH THE |
| | BOARD OF ENGINEERS. |
| | |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |