Plan Review Notes
Plan Review Notes For Permit 06040957
Permit Number 06040957
Review Stop E
Sequence Number 22
Notes
Date Text
2008-07-16 12:59:54** DENIEDREVISIONS **
  
  
 1) NOTE:AS STATED ON PREVIOUS REVIEWS, MEETINGS,
 PHONE CALLS AND E-MAILS. PLEASE BE SURE TO UPDATE
 LIGHTING ON PLANS, UPDATE FIXTURE LEGEND AND BE SURE
 ALL LIGHTING ON PLANS IS PLACED INTO THE ENERGY
 CALCULATIONS AS REQUIRED BY THE FBC CHAPTER 13. 13-400,
 13-101, 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE SOME EXAMPLES WILL BE GIVEN BELOW AS A
 BENEFIT.
 THIS IS *NOT* AN EXHAUSTED LIST.
  
 FOR EXAMPLE:
 PLEASE TAKE A LOOK AT THE FIXTURE LEGEND. PLEASE SEE
 PLANS AS THERE ARE NUMEROUS FIXTURES ON PLANS WHICH ARE
 NOT LISTED ON THE FIXTURE LEGEND ON SHEET E3.02. SOME
 OF THESE ARE LG, ED, EE, LB, LC, EA, EB ETC.
 HOW CAN A REVIEW OF ENERGY CALCULATIONS BE VERIFIED
 WHEN THE WATTAGE OF FIXTURES ARE NOT SHOWN?
  
 FOR EXAMPLE:
 PLEASE SEE SHEET E1.00. THERE ARE 250W, 400W FIXTURES.
 THERE ARE NO 400W OR 250W FIXTURES AT ALL IN THE INPUT
 DATA REPORT ON THE SUBMITTED ENERGY CALCULATIONS. THESE
 ARE NOT THE ONLY FIXTURES. PLEASE TAKE A LOOK AT THE
 EXAMPLE ABOVE.
  
 ** HOW CAN CALCULATIONS BE COMPLETE, ACCURATE AND
 VERIFIEDIF THE PLANS ARE NOT COMPLETE OR COORDINATE
 TO DATE?
  
 FOR EXAMPLE:
 IT WAS PREVIOUSLY MENTIONED BY THE MECHANICAL REVIEWER
 AND THIS REVIEW TO ALSO MAKE SURE ALL BUILDING
 COMPONENTS ON PLANS ARE PLACED INTO THE ENERGY
 CALCULATIONS. THERE WILL BE COMMENTS FROM OTHER TRADES
 AS SOME OF THESE ITEMS IN THE IDR ARE SEEN BY THIS
 REVIEWER.
  
 2) NOTE: PLEASE BE SURE ALL PERMITTED TENANT PLANS FOR
 KNOWN LOADS, LIGHTING USE ETC ARE REVISED INTO THE BASE
 BUILDING.
 FOR EXAMPLE:
 CLEVELAND CLINIC AT BOTH LOCATIONS.
 NEC 220, FBC 13-415.2
 FBC 106.1.1, 106.5 FOR CLARITY AND RECORD SETS OF
 PLANS.
  
 3) NOTE: PLEASE BE SURE THE ENGINEER RAISED SEAL IS
 PLACED TO THE FRONT ON SHEETS. THESE DOCUMENTS ARE
 SCANNED AND INFORMATION NEEDS TO FACE FORWARD TO BE
 EASILY READ AS PART OF THE RECORD PLANS. PLEASE SEE
 SHEETS E3.03.1 IN ALL THREE SETS ARE SEAL BACKWARDS.
 THIS IS NOT NECESSARILY A VIOLATION AS THE STATUTE DOES
 NOT SAY IF THE SEAL CAN BE ON THE BACK OF THE PLANS
 HOWEVER BASED ON SCANNING OF PLANS AND DOCUMENTS THESE
 NEED TO BE READ ETC.
 THE INTENT OF THE STATUTE IS THAT THE SEAL IS FACING
 THE FRONT OF PLANS ETC. THIS WAS CONFIRMED WITH THE
 BOARD OF ENGINEERS.
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717