 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
  
 1)PLEASE SEE ELECTRICAL PLAN REVIEW
 COMMENTS, WITH RESPECT TO DESIGN
 PROFESSIONAL, SIGNED AND SEALED PLANS
 AND MISSING LICENSE INFORMATION.
 2) PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT PLUMBING
 PLANS.
  
 3) SHT L-5 IRRIGATION NOTES REFERENCE TO
 PVB. SEC. 608 PROTECTION OF WATER SUPPLY
 AND TABLE 608.1 RPBFP IS REQUIRED FOR
 THIS DEGREE OF HAZARD WITH BACK PSI.
  
 4)SHT A1.06 SECTION 403
 MINIMUM PLUMBING FACILITIES
 403.1 MINIMUM NUMBER OF FIXTURES.
 PLUMBING FIXTURES SHALL BE PROVIDED FOR
 THE TYPE OF OCCUPANCY AND IN THE MINIMUM
 NUMBER SHOWN IN TABLE 403.1. TYPES OF
 OCCUPANCIES NOT SHOWN IN TABLE 403.1
 SHALL BE CONSIDERED INDIVIDUALLY BY THE
 CODE OFFICIAL. THE NUMBER OF OCCUPANTS
 SHALL BE DETERMINED BY THE FLORIDA
 BUILDING CODE, BUILDING. OCCUPANCY
 CLASSIFICATION SHALL BE DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 5) SHT.A8.71DETAIL 8 TOILET RM ELV.
 SHOW MOUNTING HEIGTHFOR LAV'S FROM FF
  
 6)SHT P0.1OIL TRAP DIAGRAM:
 CONTACT W P BEACHWATERPLANT LAB
 SUPERVISOR,INDUSTRIAL COORDINATOR.
 LYNN MASSON
 OFFICE 561-822-2271
 E-MAIL [email protected]
  
 7)SHT P0.3, P0.4 SANITARY WASTE, VENT
 STACKS.SECTION 914
 RELIEF VENTS?STACKS OF MORE THAN
 10 BRANCH INTERVALS
 914.1 WHERE REQUIRED.
 SOIL AND WASTE STACKS IN BUILDINGS
 HAVING MORE THAN 10 BRANCH INTERVALS
 SHALL BE PROVIDED WITH A RELIEF VENT AT
 EACH TENTH INTERVAL INSTALLED, BEGINNING
 WITH THE TOP FLOOR.
 914.2 SIZE AND CONNECTION.
 THE SIZE OF THE RELIEF VENT SHALL BE
 EQUAL TO THE SIZE OF THE VENT STACK TO
 WHICH IT CONNECTS. THE LOWER END OF EACH
 RELIEF VENT SHALL CONNECT TO THE SOIL OR
 WASTE STACK THROUGH A WYE BELOW THE
 HORIZONTAL BRANCH SERVING THE FLOOR, AND
 THE UPPER END SHALL CONNECT TO THE VENT
 STACK THROUGH A WYE NOT LESS THAN 3 FEET
 (914 MM) ABOVE THE FLOOR.
  
 8) SHT P0.4STACK "G", "H"
 SECTION 903.3 VENT TERMINATION.
 EVERY VENT STACK OR STACK VENT SHALL
 EXTEND OUTDOORS AND TERMINATE TO THE
 OPEN AIR.
  
 9) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT.
  
 10)PLEASE COMPLETELY REMOVE ANY
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 END OF COMMENTS, QUESTIIONS 561-805-6692
  
  
  
  
  