| Date |
Text |
| 2006-07-30 00:00:00 | PAUL SCHMITZ |
| | [email protected] |
| | FBC 2004 PLUMBING CODE PLAN REVIEW |
| | FBC2004 FUEL GAS CODEPLAN REVIEW |
| | FBC 2004 CH 11, FL ACESSIBILITY CODE |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE |
| | CHAPT.1, ADMINISTRATION, 2004 EDITION |
| | |
| | UNSAT |
| | |
| | 1)PLEASE SEE ELECTRICAL PLAN REVIEW |
| | COMMENTS, WITH RESPECT TO DESIGN |
| | PROFESSIONAL, SIGNED AND SEALED PLANS |
| | AND MISSING LICENSE INFORMATION. |
| | 2) PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT PLUMBING |
| | PLANS. |
| | |
| | 3) SHT L-5 IRRIGATION NOTES REFERENCE TO |
| | PVB. SEC. 608 PROTECTION OF WATER SUPPLY |
| | AND TABLE 608.1 RPBFP IS REQUIRED FOR |
| | THIS DEGREE OF HAZARD WITH BACK PSI. |
| | |
| | 4)SHT A1.06 SECTION 403 |
| | MINIMUM PLUMBING FACILITIES |
| | 403.1 MINIMUM NUMBER OF FIXTURES. |
| | PLUMBING FIXTURES SHALL BE PROVIDED FOR |
| | THE TYPE OF OCCUPANCY AND IN THE MINIMUM |
| | NUMBER SHOWN IN TABLE 403.1. TYPES OF |
| | OCCUPANCIES NOT SHOWN IN TABLE 403.1 |
| | SHALL BE CONSIDERED INDIVIDUALLY BY THE |
| | CODE OFFICIAL. THE NUMBER OF OCCUPANTS |
| | SHALL BE DETERMINED BY THE FLORIDA |
| | BUILDING CODE, BUILDING. OCCUPANCY |
| | CLASSIFICATION SHALL BE DETERMINED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 5) SHT.A8.71DETAIL 8 TOILET RM ELV. |
| | SHOW MOUNTING HEIGTHFOR LAV'S FROM FF |
| | |
| | 6)SHT P0.1OIL TRAP DIAGRAM: |
| | CONTACT W P BEACHWATERPLANT LAB |
| | SUPERVISOR,INDUSTRIAL COORDINATOR. |
| | LYNN MASSON |
| | OFFICE 561-822-2271 |
| | E-MAIL [email protected] |
| | |
| | 7)SHT P0.3, P0.4 SANITARY WASTE, VENT |
| | STACKS.SECTION 914 |
| | RELIEF VENTS?STACKS OF MORE THAN |
| | 10 BRANCH INTERVALS |
| | 914.1 WHERE REQUIRED. |
| | SOIL AND WASTE STACKS IN BUILDINGS |
| | HAVING MORE THAN 10 BRANCH INTERVALS |
| | SHALL BE PROVIDED WITH A RELIEF VENT AT |
| | EACH TENTH INTERVAL INSTALLED, BEGINNING |
| | WITH THE TOP FLOOR. |
| | 914.2 SIZE AND CONNECTION. |
| | THE SIZE OF THE RELIEF VENT SHALL BE |
| | EQUAL TO THE SIZE OF THE VENT STACK TO |
| | WHICH IT CONNECTS. THE LOWER END OF EACH |
| | RELIEF VENT SHALL CONNECT TO THE SOIL OR |
| | WASTE STACK THROUGH A WYE BELOW THE |
| | HORIZONTAL BRANCH SERVING THE FLOOR, AND |
| | THE UPPER END SHALL CONNECT TO THE VENT |
| | STACK THROUGH A WYE NOT LESS THAN 3 FEET |
| | (914 MM) ABOVE THE FLOOR. |
| | |
| | 8) SHT P0.4STACK "G", "H" |
| | SECTION 903.3 VENT TERMINATION. |
| | EVERY VENT STACK OR STACK VENT SHALL |
| | EXTEND OUTDOORS AND TERMINATE TO THE |
| | OPEN AIR. |
| | |
| | 9) WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE |
| | ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES |
| | CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. |
| | |
| | 10)PLEASE COMPLETELY REMOVE ANY |
| | OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | END OF COMMENTS, QUESTIIONS 561-805-6692 |
| | |
| | |
| | |
| | |
| | |