| Date |
Text |
| 2006-09-08 00:00:00 | *DENIED*** |
| | |
| | 1) WORK SHALL COMPLY WITH NFPA 101, 2003 |
| | EDITION CHAPTER 11 HIGHRISE BUILDINGS. |
| | |
| | 2) ANY RELOCATED FIRE HYDRANTS SHALL BE |
| | OPERATIONAL PRIOR TO, DURING AND AFTER |
| | CONSTRUCTION. |
| | |
| | 3) SHEET C-8 ILLUSTRATES AN EXISTING |
| | FIRE DEPARTMENT CONNECTION TO REMAIN. |
| | PLEASE VERIFY WHAT STRUCTURE IS BEING |
| | SERVICED BY THAT CONNECTION. |
| | |
| | 4) ELECTRONIC SWITCHES IN ADDITION TO |
| | CHAIN AND LOCK IS REQUIRED FOR DOUBLE |
| | CHECK DETECTOR ASSEMBLY. OK ON SHEET |
| | FP0.01. |
| | |
| | 5) LANDSCAPING SHALL NOT OBTSRUCT OR |
| | INTERFERE WITH FIRE PROTECTION |
| | EQUIPMENT. PROPER CLEARANCES SHALL BE |
| | MAINTAINED AT ALL TIMES. |
| | |
| | 6) CONSTRUCTION, ALTERATION AND |
| | DEMOLITION SHALL COMPLY WITH NFPA 241. |
| | |
| | 7) STAIRS TO KEEP UP WITH CONSTRUCTION. |
| | |
| | 8) TEMPORARY STANDPIPES ARE REQUIRED |
| | WHEN BUILDING REACHES (3) STORIES OR |
| | (30)' IN HEIGHT. |
| | |
| | 9) MORE DETAILS ARE REQUIRED FOR |
| | GENERATORS ICLUDING ALL MANUFACTURER |
| | SPEC SHEETS . |
| | |
| | 10) SITE PLAN ON SHEET A0.21 ONLY |
| | ILLUSRATES (1) FIRE DEPARTMENT |
| | CONNECTION. OK ON FP SHEETS. |
| | |
| | 11) LIFE SAFETY PLAN SHALL INCLUDE ALL |
| | COMMON PATHS OF TRAVEL TO EXITS. IT |
| | APPEARS THAT (1) IS SHOWN ON SHEET |
| | A0.22. |
| | |
| | 12) PLANS INDICATE THAT ROOF ACCESS IS |
| | NOT AVAILABLE TO GENERAL PUBLIC. WHAT |
| | SAFEGUARDS ARE BEING USED TO ASSURE |
| | THIS? |
| | |
| | 13) 2A-10B,C RATED FIRE EXTINGUISHERS |
| | SHALL BE MOUNTED AT DISTANCES TO SATISFY |
| | THE 75' TRAVEL DISTANCE REQUIREMENT. |
| | |
| | 14) PLEASE PROVIDE MORE DETAILS |
| | REGARDING CANOPIES. |
| | |
| | 15) PLEASE CLEARLY ILLUSTRATE EXITING |
| | FROM EXISTING PARKING GARAGE AS IT |
| | REALATES TO THE NEW STRUCTURE.WILL THE |
| | NEW STRUCTURE IMPACT EXITING FROM THE |
| | EXISTING PARKING GARAGE? |
| | |
| | 16) COOLING TOWERS TO COMPLY WITH NFPA |
| | 214. |
| | |
| | 17) NO STORAGE IS ALLOWED IN ELECTRICAL |
| | OR MECHANICAL ROOMS THAT WILL BE |
| | REQUIRED TO BE INSPECTED. |
| | |
| | 18) ADDRESS IS REQUIRED ON BUILDING, AND |
| | SHALL BE A MINIMUM OF 6" IN HEIGHT, 1" |
| | WIDTH AND CONTRASTING TO THE BACKGROUND. |
| | |
| | 19) ALL STAIRS AND RAMPS SHALL HAVE |
| | HANDRAILS ON BOTH SIDES. |
| | |
| | 20) HOW WILL THE HIGHRISE IMPACT THE |
| | EXISTING PARKING STRUCTURE SHOULD AN |
| | EMERGENCY OCCUR ON UPPER LEVELS OF THE |
| | PARKING GARAGE? |
| | |
| | 21) PLEASE INDICATE THE MINIMUM INTERIOR |
| | FINISH CLASSIFICATION FOR WALLS AND |
| | CEILING IN TERMS OF CLASS A,B OR C IN |
| | ACCORDANCE WITH NFPA 101, SECTION 10.2. |
| | |
| | 22) SEPARATE SHOP DRAWINGS AND PERMITS |
| | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE |
| | ALARM SYSTEMS. |
| | |
| | 23) FIRE ALARM SYSTEM TO COMPLY WITH |
| | SURVIVABILITY REQUIREMENTS OF NFPA 72 |
| | FOR HIGHRISE BUILDINGS. |
| | |
| | 24) PLEASE PROVIDE ALL MANUFACTURER SPEC |
| | SHEETS FOR FIRE PUMP AND ASSOCIATED |
| | EQUIPMENT. |
| | |
| | 25) FIRE ALARM SHALL BE UL CERTIFIED FOR |
| | CENTRAL STATION SERVICE. |
| | |
| | 26) FIRE ALARM TO BE CLASS A OR FULLY |
| | ADDRESSABLE. |
| | |
| | 27) DUCT SMOKE DETECTORS SHALL INITIATE |
| | A GENERAL FIRE ALARM IN ACCORDANCE WITH |
| | LOCAL REQUIREMENTS. |
| | |
| | 28) KNOX LOCKING CAPS ARE REQUIRED FOR |
| | NEW FIRE DEPARTMENT CONNECTIONS. |
| | |
| | 29) WHERE PROVIDED, SMOKE MANAGEMENT |
| | PANELS SHALL PROVIDE GRAPHIC |
| | REPRESENTAION OF THE BUILDING. HOA |
| | SWITCHES WITH NO OVERLAY OF THE BUILDING |
| | WILL NOT BE ACCEPTABLE. SHT FA1.01 |
| | |
| | 30) EXITS SIGNS SHALL BE PROVIDED WHERE |
| | ALL PARTS OF THE MEANS OF EGRESS ARE |
| | CLEAR AND OBVIOUS. IT WOULD APPEAR THAT |
| | MORE SIGNS ARE NEEDED ON THE 1ST FLOOR W |
| | SIDE OF CORRIDOR. |
| | |
| | 31) NO EMERGENCY LIGHTS CAN BE FOUND IN |
| | CORRIDORS NEAR STAIR #2. |
| | |
| | 32) MORE DETAILS REQUIRED FOR CO PANEL |
| | AND EQIPMENT IN PARKING GARAGE. |
| | |
| | 33) KNOX BOXES WILL BE REQUIRED. PLEASE |
| | CONTACT THE BUREAU OF FIRE PREVENTION AT |
| | (561) 804-4724 FOR APPLICATIONS. |
| | |
| | 34) FIRE DEPARTMENT VALVES TO BE 2 1/2"- |
| | 1 1/2" REDUCERS WITH CHAINS. |
| | |
| | 35) FP 1.15 AND FP 1.16 ARE SHOWING ALL |
| | UPRIGHT SPRINKLERS I CORE AREAS. CAN YOU |
| | PLEASE VERIFY IF THIS IS CORRECT? |
| | |
| | 36) PLEASE INDICATE WHAT ELEVATORS ARE |
| | STRETCHER ACCESSIBLE. |
| | |
| | 37) NO EQUIPMENT SHALL BE ALLOWED INSIDE |
| | OR PENETRATE EXIT ENCLOSURES UNLESS THE |
| | EXCEPTIONS OF NFPA 101, SECTION |
| | 7.1.3.2.1.(6) ARE MET. |
| | |
| | 38) NO CUTTING OR WELDING OPERATIONS TO |
| | OCCUR WITHOUT APPROVAL OF THE FIRE |
| | PREVENTION BUREAU AND COMPLIANCE WITH |
| | NFPA 51B. |
| | |
| | 39) BUILDING SHALL COMPLY WITH ALL |
| | REQUIREMENTS OF NFPA 101, 2003 EDITION |
| | SECTION 11.8 FOR HIGHRISE BUILDINGS. |
| | |
| | 40) THE ANTICIPATED STACK EFFECT WORDING |
| | NOTE SHALL BE ADDED TO MECHANICAL |
| | SHEETS. |
| | |
| | 41) WILL SECURITY GATES HAVE AN IMPACT |
| | ON MEANS OF EGRESS? SHEET A1.01. |
| | |
| | 42) ANY PROPOSED SOFFITS SHALL NOT |
| | INTERFERE WITH OR OBSTRUCT REQUIRED FIRE |
| | SPRINKLER COVERAGE. |
| | |
| | 43) PLEASE ILLUSTRATE ALL EXIT DISCHARGE |
| | LOCATIONS FROM THE BUILDING. EXIT |
| | DISHARGE LOCATIONS SHALL COMPLY WITH |
| | APPLICABLE FIRE CODE REQUIREMENTS. |
| | |
| | 44) ELEVATORS TO COMPLY WITH ASME A17.1. |
| | |
| | 45) WARNING SIGNS ARE REQUIRED IN |
| | ELEVATOR LOBBIES. |
| | |
| | 46) ALL FIRE DOORS AND WINDOWS TO COMPLY |
| | WITH NFPA 80, FIRE DOORS AND WINDOWS. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAI/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |