Plan Review Notes
Plan Review Notes For Permit 06040957
Permit Number 06040957
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2006-09-08 00:00:00*DENIED***
  
 1) WORK SHALL COMPLY WITH NFPA 101, 2003
 EDITION CHAPTER 11 HIGHRISE BUILDINGS.
  
 2) ANY RELOCATED FIRE HYDRANTS SHALL BE
 OPERATIONAL PRIOR TO, DURING AND AFTER
 CONSTRUCTION.
  
 3) SHEET C-8 ILLUSTRATES AN EXISTING
 FIRE DEPARTMENT CONNECTION TO REMAIN.
 PLEASE VERIFY WHAT STRUCTURE IS BEING
 SERVICED BY THAT CONNECTION.
  
 4) ELECTRONIC SWITCHES IN ADDITION TO
 CHAIN AND LOCK IS REQUIRED FOR DOUBLE
 CHECK DETECTOR ASSEMBLY. OK ON SHEET
 FP0.01.
  
 5) LANDSCAPING SHALL NOT OBTSRUCT OR
 INTERFERE WITH FIRE PROTECTION
 EQUIPMENT. PROPER CLEARANCES SHALL BE
 MAINTAINED AT ALL TIMES.
  
 6) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 7) STAIRS TO KEEP UP WITH CONSTRUCTION.
  
 8) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN BUILDING REACHES (3) STORIES OR
 (30)' IN HEIGHT.
  
 9) MORE DETAILS ARE REQUIRED FOR
 GENERATORS ICLUDING ALL MANUFACTURER
 SPEC SHEETS .
  
 10) SITE PLAN ON SHEET A0.21 ONLY
 ILLUSRATES (1) FIRE DEPARTMENT
 CONNECTION. OK ON FP SHEETS.
  
 11) LIFE SAFETY PLAN SHALL INCLUDE ALL
 COMMON PATHS OF TRAVEL TO EXITS. IT
 APPEARS THAT (1) IS SHOWN ON SHEET
 A0.22.
  
 12) PLANS INDICATE THAT ROOF ACCESS IS
 NOT AVAILABLE TO GENERAL PUBLIC. WHAT
 SAFEGUARDS ARE BEING USED TO ASSURE
 THIS?
  
 13) 2A-10B,C RATED FIRE EXTINGUISHERS
 SHALL BE MOUNTED AT DISTANCES TO SATISFY
 THE 75' TRAVEL DISTANCE REQUIREMENT.
  
 14) PLEASE PROVIDE MORE DETAILS
 REGARDING CANOPIES.
  
 15) PLEASE CLEARLY ILLUSTRATE EXITING
 FROM EXISTING PARKING GARAGE AS IT
 REALATES TO THE NEW STRUCTURE.WILL THE
 NEW STRUCTURE IMPACT EXITING FROM THE
 EXISTING PARKING GARAGE?
  
 16) COOLING TOWERS TO COMPLY WITH NFPA
 214.
  
 17) NO STORAGE IS ALLOWED IN ELECTRICAL
 OR MECHANICAL ROOMS THAT WILL BE
 REQUIRED TO BE INSPECTED.
  
 18) ADDRESS IS REQUIRED ON BUILDING, AND
 SHALL BE A MINIMUM OF 6" IN HEIGHT, 1"
 WIDTH AND CONTRASTING TO THE BACKGROUND.
  
 19) ALL STAIRS AND RAMPS SHALL HAVE
 HANDRAILS ON BOTH SIDES.
  
 20) HOW WILL THE HIGHRISE IMPACT THE
 EXISTING PARKING STRUCTURE SHOULD AN
 EMERGENCY OCCUR ON UPPER LEVELS OF THE
 PARKING GARAGE?
  
 21) PLEASE INDICATE THE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILING IN TERMS OF CLASS A,B OR C IN
 ACCORDANCE WITH NFPA 101, SECTION 10.2.
  
 22) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 23) FIRE ALARM SYSTEM TO COMPLY WITH
 SURVIVABILITY REQUIREMENTS OF NFPA 72
 FOR HIGHRISE BUILDINGS.
  
 24) PLEASE PROVIDE ALL MANUFACTURER SPEC
 SHEETS FOR FIRE PUMP AND ASSOCIATED
 EQUIPMENT.
  
 25) FIRE ALARM SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE.
  
 26) FIRE ALARM TO BE CLASS A OR FULLY
 ADDRESSABLE.
  
 27) DUCT SMOKE DETECTORS SHALL INITIATE
 A GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 28) KNOX LOCKING CAPS ARE REQUIRED FOR
 NEW FIRE DEPARTMENT CONNECTIONS.
  
 29) WHERE PROVIDED, SMOKE MANAGEMENT
 PANELS SHALL PROVIDE GRAPHIC
 REPRESENTAION OF THE BUILDING. HOA
 SWITCHES WITH NO OVERLAY OF THE BUILDING
 WILL NOT BE ACCEPTABLE. SHT FA1.01
  
 30) EXITS SIGNS SHALL BE PROVIDED WHERE
 ALL PARTS OF THE MEANS OF EGRESS ARE
 CLEAR AND OBVIOUS. IT WOULD APPEAR THAT
 MORE SIGNS ARE NEEDED ON THE 1ST FLOOR W
 SIDE OF CORRIDOR.
  
 31) NO EMERGENCY LIGHTS CAN BE FOUND IN
 CORRIDORS NEAR STAIR #2.
  
 32) MORE DETAILS REQUIRED FOR CO PANEL
 AND EQIPMENT IN PARKING GARAGE.
  
 33) KNOX BOXES WILL BE REQUIRED. PLEASE
 CONTACT THE BUREAU OF FIRE PREVENTION AT
 (561) 804-4724 FOR APPLICATIONS.
  
 34) FIRE DEPARTMENT VALVES TO BE 2 1/2"-
 1 1/2" REDUCERS WITH CHAINS.
  
 35) FP 1.15 AND FP 1.16 ARE SHOWING ALL
 UPRIGHT SPRINKLERS I CORE AREAS. CAN YOU
 PLEASE VERIFY IF THIS IS CORRECT?
  
 36) PLEASE INDICATE WHAT ELEVATORS ARE
 STRETCHER ACCESSIBLE.
  
 37) NO EQUIPMENT SHALL BE ALLOWED INSIDE
 OR PENETRATE EXIT ENCLOSURES UNLESS THE
 EXCEPTIONS OF NFPA 101, SECTION
 7.1.3.2.1.(6) ARE MET.
  
 38) NO CUTTING OR WELDING OPERATIONS TO
 OCCUR WITHOUT APPROVAL OF THE FIRE
 PREVENTION BUREAU AND COMPLIANCE WITH
 NFPA 51B.
  
 39) BUILDING SHALL COMPLY WITH ALL
 REQUIREMENTS OF NFPA 101, 2003 EDITION
 SECTION 11.8 FOR HIGHRISE BUILDINGS.
  
 40) THE ANTICIPATED STACK EFFECT WORDING
 NOTE SHALL BE ADDED TO MECHANICAL
 SHEETS.
  
 41) WILL SECURITY GATES HAVE AN IMPACT
 ON MEANS OF EGRESS? SHEET A1.01.
  
 42) ANY PROPOSED SOFFITS SHALL NOT
 INTERFERE WITH OR OBSTRUCT REQUIRED FIRE
 SPRINKLER COVERAGE.
  
 43) PLEASE ILLUSTRATE ALL EXIT DISCHARGE
 LOCATIONS FROM THE BUILDING. EXIT
 DISHARGE LOCATIONS SHALL COMPLY WITH
 APPLICABLE FIRE CODE REQUIREMENTS.
  
 44) ELEVATORS TO COMPLY WITH ASME A17.1.
  
 45) WARNING SIGNS ARE REQUIRED IN
 ELEVATOR LOBBIES.
  
 46) ALL FIRE DOORS AND WINDOWS TO COMPLY
 WITH NFPA 80, FIRE DOORS AND WINDOWS.
  
  
 MIKE WENNERGREN, CAPTAI/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  