| Date |
Text |
| 2006-08-02 00:00:00 | **** NOTE*** |
| | |
| | A RETURN PHONE CALL WAS PLACED TOMR. |
| | WORKS AND MR. JOINER AT APPROX 5:45PM TO |
| | GO OVER COMMENTS OF PLAN REVIEW. |
| | PHONE CONFERENCE LASTED TILL 7:14PM AND |
| | SHALL CONTINUE AT THE DESIGN'S TEAM NEXT |
| | AVAILBLE TIME. |
| | MOST COMMENTS WERE GONE OVER AND ANY |
| | FOLLOW UP REVIEW OF COMMENTS WILL TAKE |
| | PLACE AT A LATER DATE AND TIME. |
| 2006-07-30 00:00:00 | IN PROGRESS |
| | |
| | ******* UNSAT 2ND REVIEW ****** |
| | |
| | CITY PLACE OFFICE TOWER |
| | 525 OKEECHOBEE BLVD. |
| | |
| | ** PLEASE SEE MANY OF THE NOTES FROM THE |
| | PREVIOUS REVIEW STILL NEED TO BE |
| | ADDRESSED ALONG WITH NEW COMMENTS. |
| | PLEASE SEE NOTE BELOW ARE TAKEN DIRECTLY |
| | FROM PREVIOUS REVIEW WITH FURTHER |
| | EXPLANATION ADDED IN RESPONSE. PLEASE |
| | SEE THE NEW NOTES ARE ADDED TO THE |
| | BOTTOM OF THE FIRST REVIEW. |
| | |
| | |
| | |
| | **PLEASE KNOW PLANS AND SUBMITTED PAPER |
| | WORK IS NOT COMPLETE AT THIS TIME FOR A |
| | COMPLETE AND SUFFICIENT REVIEW. PLEASE |
| | KNOW THERE MAY BE FURTHER COMMENTS ONCE |
| | ALL INFORMATION IS SUBMITTED. |
| | |
| | 1) NOTE: NO, PLEASE SEE ALL VOIDED |
| | SHEETS WERE ADDED TO ALL THREE SETS. IF |
| | REPLACING ALL SHEETS IN SETS AND RUNNING |
| | ALL NEW SETS, PLEASE ONLY SUBMIT "ONE" |
| | ROLL OF THE "VOIDED" SHEETS SEPARATELY. |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE KNOW, BEFORE RE-SUBMITTING |
| | PLANS. PLEASE COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETED SETS FOR |
| | REVIEW AND STAMPING. PLEASE KNOW SINCE |
| | MANY OF THE COMMENTS BELOW AFFECT ALL OF |
| | THE SHEETS IN THE SETS, ONLY ONE ROLL OF |
| | OLD SETS SHOULD BE SUBMITTED FOR |
| | REFERENCE WHEN PLANS ARE BROUGHT BACK. |
| | THESE SHOULD BE LABELED "OLD/VOIDED". |
| | |
| | 2) NOTE: NO. PLEASE SEE MISSING |
| | INFORMATION ON ALL TITLE BLOCKS FOR ALL |
| | TRADES AND FOR ALL SHEETS. PLEASE KNOW |
| | THAT "ANY" ARCHITECTURAL FIRM, |
| | ENGINEERING FIRM, LANDSCAPE FIRMETC |
| | LISTED ON SAID TITLE BLOCKS ARE REQUIRED |
| | TO HAVE THEIR CERTIFICATE OF |
| | AUTHORIZATION NUMBER LISTED ON TITLE |
| | BLOCKS ALONG WITH ALL OTHER INFORMATION |
| | AS REQUIRED UNDER THE FLORIDA |
| | ADMINISTRATIVE CODES AND FLORIDA STATUES |
| | AS LISTED ON PREVIOUS REVIEW. |
| | PLEASE SEE THAT THE ENGINEERING FIRM HAS |
| | NOW ONLY LISTED THE PRINTED PE # FOR THE |
| | DESIGNER AS THE REQUIRED CA #. PLEASE |
| | SEE ARCHITECTURAL FIRM ELKUS/MANFREDI |
| | DOES NOT FIRM NUMBER LISTED. |
| | PLEASE SEE MISSING LICENSE INFORMATION |
| | FOR LANDSCAPE PLANS. A NUMBER IS LISTED |
| | ON LANDSCAPE TITLE BLOCKS BUT IT IS |
| | UNCLEAR WHAT THIS NUMBER IS AS IT DOES |
| | NOT COME UP IN THE STATE?S WEBSITE: |
| | DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION. |
| | PLEASE ALSO KNOW NUMEROUS SEARCHES UNDER |
| | DBPR?S SITE FOR OTHER FIRMS HAVE NOT |
| | DELIVERED ANY OTHER LICENSE INFORMATION. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING INFORMATION ON MANY |
| | OF THE TITLE BLOCKS ON PLANS. PLEASE SEE |
| | MISSING FIRM LICENSE NUMBERS WHICH ARE |
| | THE CERTIFICATE OF AUTHORIZATION NUMBERS |
| | FOR MORE THAN ONE FIRM. PLEASE SEE |
| | LANDSCAPE AND MEP ENGINEERING FIRMS. |
| | PLEASE ALSO SEE MANY SHEETS ARE MISSING |
| | THE PRINTED NAME AND LICENSE NUMBER FOR |
| | THE PERSON SIGNING AND SEALING SAID |
| | DOCUMENTS. |
| | PLEASE SEE MISSING THE PRINTED NAME AND |
| | PRINTED LICENSE NUMBER FOR ARCHITECT OF |
| | RECORD ON TITLE BLOCKS FOR STH. |
| | PLEASE SEE THE FLORIDA ADMINISTRATIVE |
| | CODE 61G1-16.004 AND 61G15-23.002. |
| | FLORIDA STATUES 471.023, 481.219 |
| | ** PLEASE KNOW THE ABOVE INFORMATION IS |
| | REQUIRED FOR ALL TRADES AND FOR ALL |
| | SHEETS WHETHER OR NOT COMMENTS ARE MADE |
| | BY OTHER REVIEWERS. |
| | |
| | 3) NOTE:NO, PLEASE SEE SOME SHEETS IN |
| | SETS STILL CONTAIN A "RUBBER STAMP" FOR |
| | THE REQUIRED ORIGINAL SIGNATURE OF |
| | DESIGN PROFESSIONAL. THIS COMMENT IS FOR |
| | THE "S" SHEETS AND RESPONSIBLE |
| | STRUCTURAL ENGINEER. |
| | PLEASE SEE BUILDING REVIEW NOTES ALSO |
| | UNDER FOUNDATION PERMIT AS THE "S" |
| | SHEETS FOR SECOND REVIEW ALL CONTAINED |
| | THE SAME "RUBBER STAMP". |
| | ** IMPORTANT** PLEASE SEE NEW NOTE BELOW |
| | FOR OTHER DESIGNERS OF RECORDS AND |
| | SIGNATURES NOW ON PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE OTHER SHEETS WHICH CONTAIN A |
| | "STAMP" FOR THE REQUIRED "ORIGINAL" |
| | SIGNATURE BY THE DESIGN PROFESSIONAL. |
| | PLEASE SEE "S" SHEETS. |
| | FLORIDA STATUES 471.025 |
| | PLEASE ALSO SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH RESPECT TO THE SEAL |
| | CONTAINING THE WORDING OF "CERTIFICATE" |
| | WHICH IS NOT LONGER ACCEPTED. |
| | FAC 61G1-16.001 |
| | |
| | 4) NOTE:NO, PLEASE SEE "A0.12" AS |
| | PLANS MENTIONS "EMERGENCY AND STAND-BY |
| | POWER SYSTEMS" PER NFPA-72 2002. |
| | PLEASE ADJUST AS THE EMERGENCY AND |
| | STAND-BY SYSTEMS ARE FROM NFPA-110 2002 |
| | AND NFPA-72 2002 IS A SEPARATE CODE |
| | "NATIONAL FIRE ALARM CODE". |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PLANS SHALL CONTAIN THE |
| | FOLLOWING MIN CODES REFERENCED AND |
| | LISTED ON PLANS FOR DESIGN. |
| | THE ARCHITECTURAL LISTS THE 2004 FBC. |
| | PLEASE LIST: |
| | 2002 NFPA-70 NATIONAL ELECTRICAL CODE |
| | 2003 NFPA-101 LIFE SAFETY CODE |
| | 2003 NFPA-20 FIRE PUMPS |
| | 2002 NFPA-110 EMERGENCY AND |
| | STANDBY POWER SYSTEMS. |
| | NFPA-72 2002 |
| | THESE ARE REQUIRED AT A MIN. |
| | |
| | 5) NOTE:NO, PLEASE SEE NOT ALL |
| | MANUFACTURE SPECS/CUT SHEETS WERE |
| | LOCATED ON BOOKS AND SUBMITTED PACKAGES. |
| | PLEASE SEE MISSING SPEC FOR THE |
| | "PARALLELING SWITCH GEAR". IT WAS NOTED |
| | THAT THE BOOKS CONTAIN AN ELEVATION OF |
| | THE SWITCH GEAR, HOWEVER NOTHING COULD |
| | BE LOCATED FROM MANUFACTURE ETC SHOWING |
| | LISTINGS FROM A NRTL. |
| | ** WHEN RESUBMITTING SPEC/PRODUCT BOOKS |
| | PLEASE PROVIDE TAB/LABELS FRO ALL |
| | ITEMS/EQUIPMENT LOCATED IN SAID BOOK AS |
| | WINDOWS, DOORS AND OTHERS ARE TABBED. |
| | PLEASE KNOW, THIS WILL HELP GREATLY IN |
| | THE REVIEW PROCESS TO FIND ALL ITEMS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE FOLLOWING. |
| | GENERATOR(S), ATS SWITCHES, FIRE PUMP, |
| | FIRE PUMP CONTROLLER, FUEL TANK, |
| | PARALLELING SWITCH GEAR AND OTHER |
| | ASSOCIATE SWITCHGEAR. |
| | PLEASE KNOW, NONE OF THESE WERE |
| | SUBMITTED AND UNABLE TO VERIFY MANY |
| | ITEMS FOR CODE COMPLIANCE AT THIS TIME. |
| | PLEASE BE SURE ALL EQUIPMENT SHEETS |
| | /SPECS CONTAIN LISTINGS FROM A NRTL. |
| | |
| | 6) NOTE: NO, PLEASE KNOW AS OF THE DATE |
| | OF THIS REVIEW THESE ITEMS ARE NOT PART |
| | OF THIS LEGAL ADDRESS. PLEASE KNOW THESE |
| | MUST BE A LEGAL PART OF THIS BUILDING AS |
| | THESE ARE PART OF THE LIFE SAFETY OF |
| | SAID BUILDING. PLEASE KNOW THAT THE |
| | CORRIDOR WORK AND ANY WORK LOCATED ON |
| | "B-BLOCK" PARKING GARAGE PROPERTY WILL |
| | MOST LIKELY BE REQUIRED UNDER SEPARATE |
| | PERMIT. PLEASE SEE THAT ELEVATOR IS |
| | BEING FED FROM THIS NEW BUILDING AND |
| | SHALL BE PART OF THIS LEGAL PROPERTY. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PLANS SEEM TO INDICATE THE |
| | 2000KW GENERATORS LOCATED ON A SEPARATE |
| | PROPERTY. PLEASE KNOW, PROPERTY LINES |
| | MAY CHANGE, SEPARATE PERMIT MAY BE |
| | REQUIRED ALSO IF INDEED THESE ARE ON |
| | SEPARATE PROPERTIES. THERE MAY ALSO BE |
| | THE POSSIBILITY OF EASEMENTS WHICH MAY |
| | NEED TO BE GRANTED. |
| | PLEASE ALSO SEE THE ELEVATOR TOWER BEING CONSTRUCTED |
| | NEXT TO THE PARKING GARAGE |
| | ALSO SEEM TO BE ON A SEPARATE LEGAL |
| | PROPERTY BEING FED FROM THE MAIN TOWER. |
| | PLEASE KNOW THIS MAY NOT BE POSSIBLE |
| | DEPENDING ON THE OUTCOME OR CHANGES IN |
| | PROPERTY LINES ETC. |
| | PLEASE SEE THE PROPOSED WORK IN CORRIDOR |
| | LOCATED AT THE "B" BLOCK GARAGE |
| | STRUCTURE WILL BE REQUIRED UNDER A |
| | SEPARATE PERMIT. |
| | ** PLEASE ALSO SEE BUILDING REVIEW |
| | COMMENTS FOR ABOVE AS MANY OF THESE |
| | ITEMS ARE TO BE PLACED IN BUILDING |
| | REVIEW AND MAY AFFECT PLANS SUBMITTED. |
| | |
| | 7) NOTE: OK. |
| | |
| | 8) NOTE: OK. GATES MUST CONTAIN MANUAL |
| | OPERATION UNDER POWER FAILURE. |
| | |
| | 8) NOTE: NO, PLEASE SUBMIT ALL AS |
| | REQUESTED. PLEASE SEE THAT THE "HAND |
| | DRAWN" PANEL SCHEDULES SUBMITTED IN |
| | SUBMITTAL BOOKS IS NOT ACCEPTABLE TO THE |
| | AHJAS THIS INFORMATION IS PART OF THE |
| | DESIGN OF THE BUILDING WHICH SHALLBE |
| | PLACED IN DRAFTSMAN'S LIKE QUALITY IN |
| | THE COMPLETED SETS OF PLANS SUBMITTED |
| | WITH ALL RELEVANT TITLE BLOCKS, SIGNED, |
| | DATED AND SEALED BY THE DESIGN |
| | PROFESSIONAL OF RECORD. |
| | PLEASE SEE THAT THESE PANEL SCHEDULES |
| | CONTAIN ALL ROOM/AREA DESIGNATIONS , |
| | CIRCUITS, OCP AND CONDUCTOR SIZES. |
| | FBC 106.1.3, 106.3.5.1.2, NEC 408.4, |
| | 240.4,310.16, FS 471.025, FAC |
| | 61G15-23.002 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT COMPLETED PANEL SCHEDULES |
| | FOR ALL PANELS. THE PANELS ARE INDICATED |
| | ON E3.03 ARE NOT SUFFICIENT FOR REVIEW |
| | OF ALL SAID ELECTRICAL BRANCH CIRCUITS |
| | FOR OVER CURRENT PROTECTION, CONDUCTOR |
| | SIZES ETC. |
| | 215.5 |
| | MANY ITEMS CAN NOT BE REVIEWED AT THIS |
| | TIME. |
| | AN EQUIPMENT SCHEDULE AS SUBMITTED IS |
| | OK, HOWEVER THESE ITEMS SHOULD BE LISTED |
| | ON PANEL SCHEDULES TO BE SUBMITTED. |
| | |
| | 9) NOTE: NO.RESPONSE LETTER FROM |
| | DESIGN TEAM MENTIONS THIS WAS AND IS |
| | COMPLETE AS OF FIRST REVIEW HOWEVER |
| | PLEASE SEE MANY ITEMS ON PLANS WHICH DID |
| | NOT PREVIOUSLY CONTAIN CIRCUIT #'S ETC, |
| | NOW DO.HOW PLANS ARE CIRCUITED AND |
| | WITH THE DEVICES DENOTING A NUMERICAL IDENTIFICATION |
| | AND HOW THAT CORRELATES |
| | WITH PANEL AND PANEL SCHEDULES IS KNOWN |
| | BY THIS REVIEWER/OFFICE AND WHAT COMMON |
| | PRACTICE IS AND HAS BEEN ACROSS THE |
| | COUNTRY AND THIS JURISDICTION. PLEASE |
| | KNOW THE INTENT OF THE COMMENT WAS NOT |
| | TO PLACE THE COMPLETE "SWITCH LEGS" OR |
| | TO SHOW ACTUAL "BRANCH CIRCUITING" ON |
| | SAID PLANS. |
| | PLEASE SEE NUMEROUS AREAS ON PLANS WHICH |
| | CONTAIN A NUMBER WHICH COULD CORRELATE |
| | TO MORE THAN ONE CIRCUIT AND PANEL. |
| | PLEASE SEE REDLINED PLANS FOR THESE. |
| | E1.01 ETC. |
| | PLEASE SEE ONE EXAMPLE IS THE NUMBER "4" |
| | ON 1.01. THIS COULD BE CIRCUITED TO A |
| | MINIMUM OF THREE CIRCUITS FROM THREE |
| | SEPARATE PANELS AS NOT ALL OF THE NUMBER |
| | "4"S? ARE CONNECTED, OR SEPARATED BY ANY |
| | LINE DENOTINGSEPARATE AREAS OR OTHER |
| | MEANS TO CONNECT THOSE NUMBERS TO BE ON |
| | ONE CIRCUIT. PLEASE SEE OTHERS ARE LIKE |
| | THIS ALSO. PLEASE SEE THERE ARE STILL |
| | SOME FIXTURES ETC WHICH CONTAIN A |
| | "NUMBER" HOWEVER NO CIRCUIT DESIGNATION |
| | ON THE ENTIRE SHEET CORRELATES TO THE |
| | NUMERICAL NOTATION. |
| | PLEASE SEE ONE SET OF PLANS HAS BEEN |
| | REDLINED WITH THESE AREAS AS NOTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE COMPLETE ALL THE CIRCUITING AND |
| | SWITCH LEGS ON PLANS AND LAYOUTS. PLEASE |
| | SEE MANY AREAS ARE LEFT TO FIGURE WHERE |
| | THESE DEVICES, OUTLETS, OR LIGHTING |
| | OUTLETS ARE BEING FED FROM AND/OR |
| | CONTROLLED. |
| | PLEASE CORRELATE WITH PANEL SCHEDULES TO |
| | BE SUBMITTED. |
| | 215.5 |
| | |
| | 10) NOTE: NO. PLEASE KNOW IT WAS NOT THE |
| | INTENT OF COMMENT TO COMPLETELY REMOVE |
| | CORRIDORS AS THESE ARE REQUIRED. PLEASE |
| | KNOW AS THE FUTURE TENANT LAYOUTS ARE |
| | NOT KNOWN AT THIS TIME THE CORRIDORS |
| | WILL BE REQUIRED FROM THE BASE BUILDING |
| | LAYOUT. TENANT BUILD OUTS WILL NOT |
| | INCLUDE BASE BUILDING CORRIDOR BUILD |
| | OUTS AND THE ELECTRICAL ROOMS, DATA, |
| | TELEPHONE ROOMS SHALL BE ACCESSIBLE FOR |
| | BASE BUILDING DESIGN. PLEASE ALSO SEE |
| | BUILDING REVIEW COMMENTS FOR OTHER AREAS |
| | WHICH WILL REQUIRE ACCESS TO STAIR |
| | TOWERS ETC. |
| | PLEASE SEE THESE CORRIDORS ARE REQUIRED |
| | AT THIS TIME. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CORRELATE ARCHITECTURAL PLANS |
| | WITH ELECTRICAL. PLEASE SEE FLOORS 6-14 |
| | ARE SHOWN CONTAINING A CORRIDOR TO MAIN |
| | ELECTRICAL ROOM ON EACH OF THESE FLOORS |
| | ON ELECTRICAL PLANS, HOWEVERARCH DO |
| | NOT SHOW THESE CORRIDORS OF COMMON |
| | AREAS.? |
| | PLEASE SEE FLOORS 15 AND 16 ON BOTH A |
| | AND E'S DO NOT SHOW ANY CORRIDORS AND |
| | OBTAININGACCESS TO THE ELECTRICAL ROOM |
| | ON EACH OF THOSE FLOORS ARE ONLY THROUGH |
| | THE PROPOSED FUTURE TENANT SPACE. PLEASE |
| | KNOW IT IS NOT KNOWN AT THIS TIME IF |
| | THERE WILL BE ONE, TWO THREE OR MORE |
| | TENANTS ON EACH FLOOR AND ACCESS TO EACH |
| | TENANT?S ELECTRICAL PANEL(S) AND OVER |
| | CURRENT PROTECTION DEVICES MAY NOT BE |
| | THROUGH TENANT OCCUPANCY. PLEASE ALSO |
| | KNOW THE HOUSE POWER/COMMON AREAS MAY |
| | ALSO NOT BE ACCESSED THROUGH THE |
| | TENANT?S SPACE. |
| | PLEASE KNOW, EACH CORRIDOR AS SHOWN ON |
| | FLOORS 6-14 SHALL BE THE SAME ON ALL |
| | FLOORS AND SHOULD CORRELATE AS THE SAME |
| | ON ARCHITECTURAL SHEETS. |
| | 210.25, 215.5, 240.24 |
| | |
| | 11) NOTE: OK. |
| | |
| | 12) NOTE: OK. |
| | |
| | 13) NOTE: NO, NOT ALL COULD BE VERIFIED |
| | AT THIS TIME AS THE MAINS AND LOCATIONS |
| | OF THE PARALLEL SWITCH GEAR COULD NOT BE |
| | LOCATE DON PLANS AND MAINS FOR THIS |
| | EQUIPMENT IS NOT YET VERIFIED TO CONTAIN |
| | THE MAINS ARE REQUIRED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CLARIFY ALL MAINS AND |
| | DISTRIBUTION EQUIPMENT CONTAINING ALL |
| | MAINS, GROUPING ETC PER 230.70, 230.72, |
| | 230.76, 230.79, AND 225.31-225.39 |
| | PLEASE KNOW, DUE TO THE INFORMATION OF |
| | THE SWITCH GEAR NOT SUBMITTED, SHOWN AND |
| | WHETHER OR NOT THESE CONTAIN MAINS, WITH |
| | MANUAL MEANS OF DISCONNECT LOCATED ON |
| | THE OUTSIDE OF THE EQUIPMENT, GROUPED |
| | ETC. THE LOCATIONS OF SOME SERVICE |
| | EQUIPMENT CAN NOT REVIEWED FOR LOCATIONS |
| | AT THIS TIME. |
| | |
| | 14) NOTE:NO. SAME NOTE. PLEASE KNOW |
| | THERE SEEMS TO BE SOME CONFUSION OVER |
| | THE PREVIOUS COMMENT. PLEASE SEE THE |
| | MAINS FOR THE EMERGENCY SYSTEM AND |
| | LEGALLY REQUIRED SYSTEM SHALL NOT BE |
| | LOCATED IN THE SAME ENCLOSURE AS THE |
| | NORMAL POWER IN SWBDB. |
| | PLEASE KNOW THIS OFFICE/CODE OFFICIAL |
| | WILL NOT ACCEPT THE EMERGENCY MAINS |
| | LOCATED IN THE SAME EQUIPMENT AND THERE |
| | WILL BE NO EXCEPTIONS OR SPECIAL |
| | CONDITIONS GRANTED BY THIS AHJ. |
| | NFPA-70, 700.12, 701.11, NFPA-110 |
| | CHAPTER 7, 7.2 ETC |
| | IF A MEETING IS BEING REQUESTED THIS IS |
| | WILL AND SHOULD BE DONE ONCE ALL REVIEWS |
| | ARE DONE. IF THE DESIGNER OF RECORD AND |
| | DESIGN ENGINEER WOULD LIKE TO DISCUSS |
| | THIS OVER THE PHONE, PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE AS |
| | DONE ON NUMEROUS OCCASIONS BEFORE THESE |
| | PLANS WERE SUBMITTED FOR INITIAL REVIEW. |
| | THIS OFFICE HAS CONSULTED WITH A MR. |
| | DAVID WORKS ON MANY ITEMS BEFORE |
| | SUBMITTING PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THE EMERGENCY SYSTEMS ARE |
| | BEING SHOWN IN THE SAME EQUIPMENT AS THE |
| | NORMAL MAINS. PLEASE KNOW THESE SHALL |
| | NOT BE LOCATED IN THE SAME EQUIPMENT AND |
| | SERVED BY THE SAME SERVICE. |
| | PLEASE REVISE SERVICE AS SHOWN. 701.1, |
| | NFPA-110 CHAPTER 7 ETC. |
| | |
| | 15) NOTE: OK. |
| | |
| | 16) NOTE: OK. |
| | |
| | 17) NOTE: OK. |
| | |
| | 18) NOTE:OK, PLEASE HOWEVER SUBMIT |
| | THIS ELEVATION FROM THE "SLOSH" CHARTS. |
| | THIS SHOULD BE OBTAINED FOR RECORD SETS |
| | OF PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | THE PLEASE PROVIDE THE ELEVATION OF THE |
| | EM DISTRIBUTION SYSTEM AND EQUIPMENT. |
| | PLEASE SEE NFPA-110 7.2.3* WHICH |
| | REQUIRES THE ELEVATION TO MEET THE |
| | "SLOSH" PREDICTION LEVELS BASED ON A |
| | CATEGORY 4 STORM. |
| | THE ELEVATION FOR PROPERTY SHOULD BE OK, |
| | HOWEVER THIS ELEVATION IS REQUIRED TO BE |
| | STATED ON PLANS AND VERIFICATION THAT |
| | ALL REQUIRED EMERGENCY SYSTEMS IS ABOVE. |
| | |
| | 19) NOTE: NO, PLEASE KNOW THE LIGHTING |
| | SUBMITTAL PACKAGE MAY BE SUBMITTED AT A |
| | LATER DATE ALSO. PLEASE KNOW HOWEVER ALL |
| | FIXTURES AND DETAILED INFORMATION FOR |
| | SAID FIXTURES WILL BE REQUIRED ON THE |
| | RECORD SET OF PLANS AT THIS TIME. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE COMPLETE FIXTURE SCHEDULES AND |
| | PLEASE CORRELATE ALL FIXTURES AS SHOWN |
| | ON PLANS WITH THE FIXTURES SCHEDULES |
| | SUBMITTED. |
| | 215.5 |
| | |
| | 20) NOTE: OK, HOWEVER PLEASE SEE GF |
| | PROTECTION IS STILL BEING SHOWN FOR 225A |
| | AND 800A MAINS IN SWBDB. PLEASE SEE |
| | PREVIOUS COMMENT ABOVE #14 AS THESE WILL |
| | BE REQUIRED TO BE REMOVED FROM THE |
| | SWBDB. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE RISER IS SHOWING GFI |
| | PROTECTION FOR SOME MAINS??? |
| | PLEASE SEE GF (GROUND FAULT) PROTECTION |
| | IS REQUIRED PER 240.13, 230.95 ETC, |
| | HOWEVER PLEASE SEE GFI PROTECTION IS |
| | PERSONNEL PROTECTION. |
| | PLEASE SEE PROTECTION IS ALSO BEING |
| | SHOWN ON ALL SECONDARY OVER CURRENT |
| | PROTECTION?? |
| | PLEASE KNOW, THIS IS NOT REQUIRED FOR |
| | THIS STRUCTURE, CLASS AND OCCUPANCY, BUT |
| | HOWEVER IS PERMITTED. |
| | PLEASE ALSO SEE GF SEEMS TO BE SHOWN ON |
| | THE EM SIDE OF THE DISTRIBUTION |
| | SYSTEM(S) WHICH IS UNCLEAR. PLEASE SEE |
| | 700.7D, 700.26, NFPA-110 |
| | PLEASE SEE THE CODE IS CLEAR WHEN GROUND |
| | FAULT PROTECTION IS REQUIRED AND WHEN |
| | SENSING OF SUCH GROUND FAULTS ARE |
| | REQUIRED , HOWEVER PLEASE KNOW GROUND |
| | FAULT PROTECTION IS NOT IDEALON THE |
| | EMERGENCY SIDE DUE TO THE NATURE OF THE |
| | EMERGENCY DISTRIBUTIONSYSTEM AND THE |
| | NEED OF MAINTAINING CERTAIN SYSTEMS ON |
| | DURING AN EMERGENCY.PLEASE KNOW, |
| | SENSING OF THE GROUND FAULT WOULD BE |
| | NEEDED TO CORRECT ANY SITUATION IN SUCH |
| | EQUIPMENT. PLEASE KNOW IT HAS BEEN |
| | DETERMINED BY THIS AHJ THAT THE GF |
| | PROTECTION ON THE REQUIRED EM SYSTEMS |
| | SHOULD NOT BE PROVIDED AND ONLY SENSING |
| | FOR THE PURPOSE AS STATED AND REQUIRED. |
| | |
| | 21) NOTE:OK, GROUNDING FOR SEPARATELY |
| | DERIVED SYSTEM HAS NOW BEEN ADDED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW, 4-POLE ATS SWITCHES ARE |
| | BEING SHOWN AS REQUIRED TO ACHIEVE THE |
| | CORRECT GROUND FAULT SENSING, HOWEVER |
| | THE GENERATORS DO NOT SEEM TO BE |
| | INDICATED A SEPARATELY DERIVED AS |
| | REQUIRED. |
| | 250.30, 250.50. |
| | |
| | 22) NOTE: OK. |
| | |
| | 23) NOTE:NO, PLEASE PLACE NOTE ON |
| | PLANS FOR ROOF TOP SHEETS. |
| | SPEC BOOKS WERE REVIEWED FOR THIS NOTE |
| | AND INFORMATION IN SPECS IS OK. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE A NOTE ON PLANS MENTIONS THAT |
| | A LIGHTNING PROTECTION SYSTEM WILL BE |
| | REQUIRED. |
| | PLEASE KNOW, THIS SYSTEM MAY ONLY BE |
| | INSTALLED BY A CERTIFIED LIGHTNING |
| | PROTECTION CONTRACTOR WHO CAN CERTIFY |
| | SUCH A SYSTEM UNDER UL 96 AND NFPA-780. |
| | THIS SHALL BE A SEPARATE PERMIT, WITH |
| | PLANS AND FEES. |
| | PLEASE KNOW HOWEVER A NOTE SHALL BE |
| | PLACE ON THESE ELECTRICAL PLANS ON ROOF |
| | TOP PLANS STATING; "ALL OR ANY LIGHTNING PROTECTION |
| | SYSTEMS SHALL BE INSTALLED |
| | PER NFPA-780 AND LISTED PER UL 96." THIS |
| | WORDING SHOULD BE TO THAT SAME AFFECT, |
| | BUT NOT REQUIRED TO BE STATED AS ABOVE. |
| | PLEASE KNOW, THIS AHJ DOES NOT ACCEPT |
| | ANY OTHER SYSTEM NOT ACCEPTED BY |
| | NFPA-780. PLEASE KNOW THERE ARE MANY |
| | SYSTEMS ON THE MARKET WHICH CLAIM TO |
| | "PREVENT" OR "DISSIPATE" LIGHTNING ETC |
| | WHICH ARE NOT PERMITTED. |
| | |
| | 24) NOTE: NO, PLEASE SEE NOTE ABOVE WITH |
| | RESPECT TO COMPLETED PANEL SCHEDULES. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 620.23 ABC AND 620.24 ABC |
| | FOR REQUIRED CIRCUITS AND CONTROLS. |
| | PLEASE SEE ALL CAN NOT BE VERIFIED AT |
| | THIS TIME. |
| | |
| | 25) NOTE: NO, COULD NOT LOCATE |
| | INFORMATION ON CALCULATIONS AND |
| | PERMITTED WATTAGE USAGE AND LIGHTING |
| | POWER DENSITIES. |
| | PLEASE SEE 13-415.1.AB.1, |
| | 13-415.2.ABC.1, SEE TABLES 415.2.C.1 AND 415.2.B.1. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 2004 FBC CHAPTER 13. |
| | PLEASE SEE 13-413.1.ABC.1 FOR A WORST |
| | CASE SCENARIO TO BE PROVIDED FOR FEEDERS |
| | AND BRANCH CIRCUITS. |
| | PLEASE SEE 13-413.1.ABC.2.2. |
| | PLEASE SEE 13-415.1.ABC.1.1, |
| | 13-415.1.ABC.1.2, 13-415.1.ABC.1.3 FOR |
| | LIGHTING AND CONTROLS FOR ALL AREAS. |
| | PLEASE SEE SOME EXCEPTIONS ARE |
| | PERMITTED. |
| | PLEASE SEE OUTSIDE AREAS , TANDEM WIRING |
| | ETC. |
| | |
| | 26) NOTE: NO, PLEASE SEE FIRST FLOOR |
| | FUTURE RETAIL SPACES AS MINIMAL FIXTURES |
| | COULD NOT BE LOCATED. THIS WAS CONFIRMED |
| | ONCE AGAIN WITH THE FIRE MARSHAL'S |
| | OFFICE AND FIRE PREVENTION CHIEF. |
| | PLEASE SEE ALL AREAS ON OTHER FLOORS |
| | WERE DONE TO PROVIDE THE MINIMAL |
| | LIGHTING. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE MINIMUM LIGHTING FOR EGRESS |
| | ETC WILL BE REQUIRED INSIDE THE FUTURE |
| | TENANT BUILD OUT SPACES. THIS HAS ALSO |
| | BEEN CONFIRMED ALSO WITH THE FIRE |
| | MARSHAL?S OFFICE AND WILL BE REQUIRED. |
| | THESE SHOULD BE WIRED INTO THE HOUSE |
| | PANELS AT THIS TIME AND CAN BE REMOVED |
| | ONCE TENANT OCCUPANCY TAKES PLACE. |
| | PLEASE ALSO SEE EXIT LIGHTS. |
| | IF THESE AREAS ARE OCCUPIED AT ANYTIME |
| | FOR ANY REASON BEFORE A BUILD OUT HAS |
| | TAKEN PLACE AND THE POWER GOES OUT, |
| | MINIMUM LIGHTING SHALL BE PROVIDED TO |
| | DIRECT ANY SAID OCCUPANTS TO THE EXIT. NFPA-101,7.8, |
| | 7.9. |
| | |
| | 27) NOTE:OK, SPECS WERE SUBMITTED |
| | HOWEVER STILL NEED TO VERIFY THE MANUAL |
| | MEANS OF DISCONNECT LOCATED ON THE |
| | OUTSIDE OF EQUIPMENT ALONG WITH |
| | ISOLATING SWITCH ETC. PLEASE SEE THE |
| | SPECS SUBMITTED DO NOT SEEM TO CONTAIN |
| | THESE? |
| | NFPA-20 10.4.2, 2003. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PREVIOUS NOTES ABOVE WHICH |
| | REQUESTED THE MANUFACTURES SPEC/CUT |
| | SHEETS FOR THE FIRE PUMP AND FIRE PUMP |
| | CONTROLLER. PLEASE KNOW, THE PLANS SHALL |
| | INDICATE THE OCP AND LOCKED ROTOR OCP. |
| | PLEASE SEE RISER NOW SEEMS TO INDICATE |
| | THE FPC TO BE LISTED ETC. PLEASE KNOW, |
| | IF THE FCP MEETS NFPA-20 FOR THE |
| | DISCONNECT MEANS RATED FOR THE LOAD |
| | SERVED LOCATE ON THE OUTSIDE OF THE |
| | EQUIPMENT AND CONTAINS THE OVER CURRENT |
| | PROTECTION SET AT LOCKED ROTOR AS |
| | REQUIRED BY 695.4B1 AND NFPA-20 |
| | 10.4.2,10.4.2.2, 10.3.6, 10.4.4 ETC. |
| | PLEASE SEE RISER SHOWS AN ADDITIONAL |
| | 800A DISCONNECT LOCATED AHEAD OF THE |
| | LISTED FPC? PLEASE VERIFY AND CLARIFY |
| | THIS. |
| | |
| | 28) NOTE:NO, PLEASE SEE RESPONSE |
| | LETTER MENTIONS TO SEE SPECS 2.18 FOR |
| | THIS , HOWEVER SHEETS IN SPEC BOOKS SEEM |
| | TO CONTAIN A MISSED SHEET OR MISPRINT AS |
| | THIS SECTION FOR THIS INFORMATION FOR |
| | NUMERICAL RESPONSE NOTED ABOVE COULD NOT |
| | BE LOCATED. PLEASE KNOW IN EITHER CASE |
| | THE AMOUNT OF FUEL SHALL BE STATED ON |
| | PLANS ALONG WITH THE GPH AND TIME FOR |
| | ALL LOADS AT 100%. THESE TIMES ARE |
| | REQUIRED ON THE PLANS. |
| | FBC 106.1.2 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FUEL IS REQUIRED PER NFPA-20 |
| | FOR A MINIMUM OF 8HRS AT 100% FOR FIRE |
| | PUMP AND ALL OTHER ASSOCIATED LOADS, |
| | INCLUDING ETC. |
| | 6-6.2 |
| | |
| | 29) NOTE: OK. SUB BASE TANK IS PART OF |
| | THE GEN. |
| | |
| | 30) NOTE: OK AS NOTED. |
| | |
| | 31) NOTE: NO, PLEASE SEE PLANS NOW |
| | MENTION CONDUITS AND MI CABLES AS |
| | OPTIONS. ?? PLEASE KNOW THE ACTUAL |
| | INSTALLATION SHALL BE SPECIFIED AT THIS |
| | TIME. REVISIONS TO THIS MAY BE DONE AT |
| | LATER DATE ONCE THE PERMIT IS ISSUED. |
| | PLEASE SEE 700.9D1 AS MENTIONED WHEN |
| | REQUIRED. PLEASE SEE THIS BUILDING IS |
| | 100% SPRINKLED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE VERIFY "MI" CABLES BEING SHOWN |
| | ON PLANS AND RISER IN MANY LOCATIONS. |
| | PLEASE KNOW, THIS IS ONLY A NOTE AS THIS INSTALLATION |
| | FOR MI CABLE IS NOT COMMON |
| | FOR THIS TYPE OF CABLE. THIS IS |
| | PERMITTED AND IS IN NO WAY A NOTE FOR |
| | CORRECTION. THIS IS ONLY NOTED, AS IF |
| | SHOWN ON PLANS, THIS WILL BE REQUIRED |
| | AND IN LIEU OF REVISING PLANS AT A LATER |
| | DATE CHANGES CAN BE MADE IF THESE ARE |
| | NOT INTENDED. |
| | PLEASE INDICATE THE CABLE DEGREE |
| | RATINGS. |
| | |
| | 32) NOTE:OK, AS MAINS ARE NOW SHOWN ON GENERATORS AND |
| | GROUNDING RISER DETAILS |
| | SD SYSTEM. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE EQUIPMENT GROUNDING |
| | CONDUCTORS ARE BEING SHOWN FROM THE |
| | GENERATORS. |
| | 250.30 |
| | |
| | 33) NOTE:OK, THIS INFORMATION ON PLANS |
| | IS NOW BEING SHOWN. PLEASE KNOW, SPEC |
| | WERE NOTE ORIGINALLY SUBMITTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE THE OCP AT THE |
| | GENERATORS. |
| | 215.5 |
| | |
| | 34) NOTE:OK, THE SIZES OF THE |
| | CONDUCTORS ARE NOW VERIFIED AT THIS |
| | REVIEW AS THE OVER CURRENT PROTECTION IS |
| | NOW BEING SHOWN ON THE GENERATORS. THIS |
| | COULD NOT VERIFIED ON PREVIOUS REVIEW AS |
| | THE OCP WAS NOT SHOWN ON GENERATORS AND |
| | SPEC BOOKS WERE NOT SUBMITTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 445.13 FOR MIN SIZES OF THE |
| | FEEDERS FROM THE GENERATORS. |
| | |
| | 35) NOTE: NO, PLEASE SEE COMPLETED |
| | PANELS HAVE NOT BEEN SUBMITTED IN SETS |
| | FOR REVIEW. PLEASE ALSO SEE CALCULATIONS |
| | PROVIDED ARE UNCLEAR AS LOADS SHOWN CAN |
| | NOT BE VERIFIED WITH NEC. PLEASE LOADS |
| | AS SHOWN DO NOT DETAIL HOW LOADS WERE |
| | DERIVED. PLEASE ALSO SEE CONTINUOUS |
| | LOADS AND LARGEST MOTOR LOADS AT 125% |
| | COULD NOT BE LOCATED. |
| | WATTS PER SQ FT, KNOWN LOADS ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT COMPLETE LOAD |
| | CALCULATIONS FOR THE BUILDING SERVICES |
| | AND PANELS. |
| | PLEASE SEE 220,220.3, 220.10, 220.11, |
| | 220.13 ETC. |
| | PLEASE ALSO INDICATE ALL CONTINUOUS |
| | LOADS AND LARGEST MOTOR LOADS AT 125%. |
| | 215.3, 230.42 ETC. |
| | |
| | 36) NOTE: NO, PLEASE PROVIDE MINIMUM |
| | GUTTER SIZE(S) AT THIS TIME. THIS MAY BE |
| | REVISED ONCE CONDUITS ENTRIES ARE KNOW |
| | OR IF THEY ARE CHANGED AT A LATER DATE. |
| | THIS IS AND WILL BE REQUIRED ON PLANS BY |
| | THE RESPONSIBLE DESIGNER OF RECORD. |
| | FBC 106.1.2 |
| | |
| | * PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE THE GUTTER SIZES ON |
| | RISER. THIS IS REQUIRED AT THIS TIME |
| | BASED ON THE MINIMUM DIMENSIONS REQUIRED |
| | FOR TURNING RADIUS AND BASED ON THE CONDUCTORS/FEEDERS |
| | ARE SHOWN ON RISER. |
| | 368,215.5 |
| | |
| | 37) NOTE: NO. RESPONSE LETTER MENTIONS |
| | TO SEE TRANSFORMER SCHEDULE WHICH WAS ON |
| | PREVIOUS PLANS. PLEASE KNOW THE |
| | GROUNDING ELECTRODE SIZES AS NOTED ON |
| | TRANSFORMER SCHEDULE WAS NOT PART OF |
| | THIS NOTE. THE RISER SHOULD SHOW OR NOTE |
| | THE ATTACHMENT LOCATIONS. PLEASE ALSO |
| | CORRELATE WITH THE NEXT COMMENT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE AND SHOW ALL ATTACHMENT |
| | LOCATIONS FOR THE TRANSFORMERS AS SHOWN |
| | ON RISER. PLEASE SEE 250.50,250.30, |
| | 250.66 ETC. |
| | |
| | 38) NOTE: NO. RESPONSE MENTIONS TO SEE |
| | GROUND RISER ON 3.04, HOWEVER THIS |
| | DETAIL IS FOR THE GROUNDING ELECTRODE |
| | SYSTEM. PLEASE SEE PREVIOUS NOTE AS THIS |
| | WAS TO PROVIDE A "GROUND RISER". THIS IS |
| | ONE FOR THE ENTIRE BUILDING THROUGH ALL |
| | FLOORS ETC. PLEASE KNOW THE MINIMUM SIZE |
| | WILL BE 3/0. PLEASE KNOW, THIS CAN BE |
| | DONE ON A SEPARATE SHEET AND EXISTING |
| | RISER DIAGRAM SHEET CAN NOTE TO SEE THIS |
| | SHEET OR THIS MAY BE PLACED ON THE RISER |
| | SHEETS IN LIGHT GRAY. |
| | FBC 106.1.2, NEC 250.58, 250.50 ETC |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE A ONE-LINE GROUND RISER |
| | ON RISER DIAGRAM OR SEPARATE SHEET. |
| | 250.58, 215.5 |
| | |
| | 39) NOTE: NO. RESPONSE MENTIONS THIS |
| | REVIEW AND MODIFIED IF NECESSARY. PLEASE |
| | KNOW THIS IS PART OF THE REVIEW BY THIS |
| | OFFICE AND IS REQUIRED AT THIS TIME. |
| | PLEASE ALSO SEE NEW NOTES FOR CHANGES IN |
| | PLANS FROM FIRST REVIEW. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CORRELATE ALL OCP DEVICES FOR |
| | PANELS ON RISER AND PANELS SCHEDULE WHEN SUBMITTED. |
| | PLEASE SEE SOME OF THIS ON |
| | RISER DOES NOT CORRELATE AT THIS TIME |
| | WITH PANELS AS NOTED. |
| | 215.5 |
| | |
| | 40) NOTE:NO. RESPONSE MENTIONS 250% |
| | FOR PRIMARY PLUS SECONDARY ETC. PLEASE |
| | SEE TABLE IN 450.3 WHICH CONTAINS |
| | (NOTES). PLEASE SEE NOTE BELOW TABLE IN |
| | ORDER TO USE THE250% ETC. |
| | PLEASE SEE THE NOTE #3 WHICH IS NEXT TO |
| | THE 250% IS ATTACHED TO THIS REVIEW. |
| | THIS IS TAKEN DIRECTLY FROM THE NEC: |
| | 3. A TRANSFORMER EQUIPPED WITH |
| | COORDINATED THERMAL OVERLOAD PROTECTION |
| | BY THE MANUFACTURER AND ARRANGED TO |
| | INTERRUPT THE PRIMARY CURRENT SHALL BE |
| | PERMITTED TO HAVE PRIMARY OVERCURRENT |
| | PROTECTION RATED OR SET AT A CURRENT |
| | VALUE THAT IS NOT MORE THAN SIX TIMES |
| | THE RATED CURRENT OF THE TRANSFORMER FOR TRANSFORMERS |
| | HAVING NOT MORE THAN 6 |
| | PERCENT IMPEDANCE AND NOT MORE THAN FOUR |
| | TIMES THE RATED CURRENT OF THE |
| | TRANSFORMER FOR TRANSFORMERS HAVING MORE |
| | THAN 6 PERCENT BUT NOT MORE THAN 10 |
| | PERCENT IMPEDANCE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 450.3 FOR THE MAXIMUM OCP |
| | FOR TRANSFORMERS TO BE AT 125%. PLEASE |
| | KNOW, WHEN THE OCP DOES NOT CORRELATE, |
| | AND THEN IT IS PERMITTED TO GO TO THE |
| | NEXT SIZE UP, HOWEVER IT IS NOT |
| | PERMITTED TO GO MORE THAN THE STANDARDS |
| | OCP PROTECTION DEVICES AS LISTED IN |
| | 240.6. |
| | PLEASE SEE TRANSFORMERS WHICH INDICATE |
| | THE OCP SET HIGHER THAN THE MAX 125%. |
| | 215.5 |
| | |
| | 41) NOTE: OK. LT POLES REMOVED. |
| | |
| | 42) NOTE: NO, COULD NOT LOCATE NOTES AS |
| | PREVIOUSLY REQUESTED ON PLANS. |
| | REQUIRED AT THIS TIME ON RECORD SET(S) |
| | OF PLANS. |
| | FBC 106.1.2, ETC AS NOTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW, IT WAS NOTED THAT THE |
| | RISER DIAGRAM SHEET CONTAINED A NOTED |
| | FOR SIGNAGE PER 230.2E. PLEASE KNOW |
| | HOWEVER SIGNAGE, MAPPING SHALL BE |
| | REQUIRED AT ALL OTHER LOCATIONS; HOWEVER |
| | MOST IMPORTANTLY BE REQUIRED IN FULL IN |
| | THE FIRE COMMAND RM. |
| | PLEASE PROVIDE A NOTE FOR THE SIGNAGE ON |
| | THE SHEET FOR THE FC ROOM. PLEASE NOTE |
| | THAT ALL LETTERING SHALL BE A MINIMUM OF |
| | 1? AND ON CONTRASTING BACKGROUND. |
| | |
| | 43) NOTE:NO, COULD NOT LOCATE THIS |
| | INFORMATION AND NOTES ON PLANS. |
| | REQUIRED AT THIS TIME ON RECORD SET(S) |
| | OF PLANS. |
| | FBC 106.1.2 ETC AS NOTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE NFPA-72 4.4.1.4.2.2 FOR THE |
| | REQUIRED DISCONNECTING MEANS FOR THE |
| | PRIMARY OF THE FIRE ALARM SYSTEM. |
| | PLEASE ALSO BE SURE ALL ITEMS ARE LISTED |
| | ON PLANS FOR THE FIRE COMMAND ROOM AS |
| | SET FORTH IN NFPA-10111.8, 11.8.5 |
| | |
| | 44) NOTE:SAME NOTE AS THE SAME WAS |
| | DONE ON THE REVIEW. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW MANY OF THE ABOVE ITEMS HAVE |
| | BEEN REDLINED ON ONE OF THE SETS OF |
| | SUBMITTED PLANS BUT IS IN NO WAY ALL |
| | POSSIBLE ITEMS AS MENTIONED ABOVE. |
| | |
| | 45) NOTE: OK, PLEASE DO THE SAME ON NEXT RESPONSE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THAT A TYPE WRITTEN RESPONSE |
| | FROM THE DESIGN TEAM FOR EACH OF THE |
| | ABOVE COMMENTS WILL HELP IN EXPEDITING |
| | THE NEXT REVIEW PROCESS. |
| | |
| | ******** NEW NOTES *********** |
| | |
| | 46) NOTE: PLEASE CORRELATE THE PARALLEL |
| | SWITCH GEAR RISER/ELEVATION SUBMITTED ON |
| | E3.03 WITH THAT OF THE OVERCURRENT |
| | PROTECTION DEVICES AS SHOWN AND LISTED |
| | ON RISER DIAGRAM. |
| | FBC 106.1.2 |
| | NOT ON PREVIOUS REVIEW AS INFORMATION ON |
| | SW GEAR WAS NOTE SHOWN. |
| | |
| | 47) NOTE: ** IMPORTANT ** |
| | PLEASE SEE FS 471.025 AND FAC |
| | 61G15-23.002 AS THESE REQUIRED UNDER |
| | FLORIDA LAW THAT THE ENGINEER OF RECORD |
| | HOLDING SAID LICENSE AND SEAL TO SIGN, |
| | DATE AND SEAL ALL SAID PLANS. PLEASE |
| | KNOW THAT THE SIGNING OF PLANS MAY NOT |
| | BE NOT BE DESIGNATED TO ANYONE OTHER |
| | THAN THE ENGINEER HOLDING SAID LICENSE. |
| | PLEASE SEE MECHANICAL, ELECTRICAL, |
| | PLUMBING AND FIRE ALARM (FA) SHEETS ARE |
| | NOW SIGNED WITH COMPLETELY DIFFERENT |
| | SIGNATURES THAN ON PREVIOUS SETS OF |
| | PLANS. IT IS KNOWN BY THIS OFFICE THAT |
| | AFTER SIGNING MANY SHEETS THAT A |
| | SIGNATURE WILL VARY, HOWEVER THESE ARE |
| | NOT EVEN CLOSE IN RESEMBLANCE OF ONE |
| | ANOTHER. |
| | PLEASE SUBMIT SIGNED, DATED AND SEALED |
| | LETTERS FOR LEGAL SIGNATURE |
| | VERIFICATION. PLEASE KNOW THESE LETTERS |
| | SHALL ALSO BE NOTARIZED AS LEGALLY |
| | REQUIRED IN THE STATE IN WHICH NOTARY IS |
| | HELD. IF THIS IS DONE IN THE STATE OF |
| | FLORIDA PLEASE SEE FS 117.05. |
| | PLEASE ALSO SUBMIT A PHOTO-COPY OF THE |
| | DRIVER?S LICENSE FOR SAID MEP DESIGNERS |
| | OF RECORD. PLEASE KNOW PERSONNEL |
| | INFORMATION SUCH AS THE DL # AND HOME |
| | ADDRESS MAY BE CROSSED OUT. |
| | *PLEASE KNOW ONE COMPLETE SET OF PLANS |
| | OF ORIGINAL SUBMITTED PLANS AND NEW SETS |
| | ARE BEING RETAINED BY THIS OFFICE. |
| | PLEASE ALSO KNOW THE "S" SHEETS OF ONE |
| | SET ARE ALSO BEING RETAINED BY THIS |
| | OFFICE. |
| | *PLEASE KNOW THESE PLANS MAY BE |
| | SUBMITTED TO THE FLORIDA BOARD OF |
| | PROFESSIONAL ENGINEERS AND THE STATE?S |
| | LEGAL COUNSEL TO THE BOARD FOR PIER |
| | REVIEW AND REVIEW OF SAID VIOLATIONS |
| | INCLUDING INFORMATION AND LICENSURE |
| | REQUIRED AS NOTED ON PREVIOUS REVIEW. |
| | NOTE #2 ABOVE. |
| | |
| | 48) NOTE: PLEASE SEE ENERGY CALCULATIONS |
| | ARE ALSO REQUIRED TO BE SIGNED, DATED |
| | AND SEALED BY THE RESPONSIBLE |
| | DESIGNER/ENGINEER OF RECORD. |
| | PLEASE SEE ALL SIGNATURES ON THESE |
| | CALCULATIONS AT THIS TIME DO NOT |
| | CORRELATE WITH THE SUBMITTED PLANS AS |
| | NOTED IN NOTE #47 ABOVE. |
| | PLEASE SEE THIS IS ALSO FOR THE |
| | ARCHITECT MR. MICHAEL ROSSIN AS THE |
| | SIGNATURES DO NOT CORRELATE. |
| | |
| | 49) NOTE: PLEASE SEE SHEET "S" |
| | SITE/SURVEY IS NOT VALID UNLESS SIGNED, |
| | DATED AND SEAL AS REQUIRED UNDER FS |
| | 4712.025, FAC 61G1-17 |
| | |
| | 50) NOTE: PLEASE SEE ATTACHED COPY OF |
| | FLORIDA STATUES 553.80(2)(B) WITH |
| | RESPECT TO DESIGN PROFESSIONALS AND |
| | REPEAT CODE COMPLIANT COMMENTS. PLEASE |
| | KNOW IF PLANS HAVE ANY OF THE SAME CODE |
| | COMPLIANT COMMENTS NOT ADDRESSED, A 4X |
| | FEE SHALL BE ASSESSED BASED ON PORTION |
| | OF PERMIT FEE ATTRIBUTED TO THE PLAN |
| | REVIEW. PLEASE KNOW THIS PLAN REVIEW |
| | POSTION IS 30% AND THIS WOULD BE TIMES |
| | FOUR. |
| | THIS IS ONLY GIVEN AS A NOTICE AT THIS |
| | TIME. |
| | |
| | PLEASE BE SURE TO ALL SEE ALL COMMENTS |
| | FROM ALL OTHER TRADES AND THEY MAY |
| | AFFECT ELECTRICAL PLANS AND DESIGN. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2006-07-22 00:00:00 | REVIEW IN PROGRESS, FOR COMPLETETION |
| 2006-07-17 00:00:00 | REVIEW IN PROGRESS |
| | ** REVIEW STOPPED. |
| | REVIEW TO CONTINUE ON 7/18 |
| | AS OF REVIEW TO THIS TIME, PLANS WILL BE |
| | GOING INTO A "F" STATUS WITH COMMENTS |
| | TO FOLLOW ONCE REVIEW HAS BEEN |
| | COMPLETED. |
| 2006-07-16 00:00:00 | ONE ROLL OF PLANS IN ELECTRIC FOR |
| | REVIEW ALONG WITH SPEC BOOKS, SUBMITTALS |
| | ETC IN BINDERS. |
| | REVIEW STOPPED, TO CONTINUE ON 7/17 |