| 2008-05-27 09:06:30 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SUPPLY INFORMATION OR PROVIDE THE |
| | FOLLOWING DETAILS/CORRECTIONS. |
| | |
| | A) FINAL REPORT FOR CIRCUIT BREAKER ENCLOSURE: PLEASE |
| | COORDINATE AIC RATINGS AS LISTED FOR BREAKER AT |
| | GENERATOR/OUTPUT AND CIRCUIT BREAKER WITH PLANS |
| | SUBMITTED AND ON FILE. PLEASE ALSO SEE THE ORIGINAL |
| | GENERATOR SPECS INDICATE A AIC RATING HIGHER THAN WHAT |
| | IS NOTED IN REPORT. |
| | PLEASE ALSO OBTAIN AT LEAST ONE COPY WHICH CONTAINS AN |
| | ORIGINAL SIGNATURE TO BE PLACED IN FILE OF PROJECT AT |
| | THE CITY. 110.3, 90.7, FBC 106.1.2, 106.5 |
| | |
| | B) FINAL REPORT FOR EXHAUST FAN CONTROL PANEL. |
| | PLEASE OBTAIN AT LEAST ONE COPY WHICH CONTAINS AN |
| | ORIGINAL SIGNATURE TO BE PLACED IN FILE OF PROJECT AT |
| | THE CITY. 110.3, 90.7, FBC 106.1.2, 106.5 |
| | |
| | C) FINAL REPORT FORMODIFIED 3000A TRANSFER SWITCH: |
| | PLEASE PROVIDE CORRECTIONS ON ITEMS IN SECTION 7 OF UL |
| | REPORT. PLEASE LIST DATES, TIMES, VERIFICATION WHEN AND |
| | HOW THESE ITEMS WERE ADDRESSED. THE ITEMS WHICH WERE |
| | ADDRESSED PRIOR TO THE FINAL UL REPORT NEED ONLY TO BE |
| | VERIFIED IN FIELD AS THESE ARE ITEMS LISTED AS |
| | *CORRECTED*. |
| | PLEASE SEE THERE ARE ITEMS SUCH AS WIRING ON SHARP |
| | EDGES WHICH DOES NOT STATE WHETHER OR NOT THESE |
| | CORRECTIONS WERE MADE OR VERIFIED. |
| | PLEASE ALSO OBTAIN AT LEAST ONE COPY WHICH CONTAINS AN |
| | ORIGINAL SIGNATURE TO BE PLACED IN FILE OF PROJECT AT |
| | THE CITY. 110.3, 90.7, FBC 106.1.2, 106.5 |
| | |
| | D) FINAL REPORT FOR MODIFIED 4000A TRANSFER SWITCH: |
| | PLEASE OBTAIN AT LEAST ONE COPY WHICH CONTAINS AN |
| | ORIGINAL SIGNATURE TO BE PLACED IN FILE OF PROJECT AT |
| | THE CITY. 110.3, 90.7, FBC 106.1.2, 106.5 |
| | |
| | E) FINAL REPORT FOR BI-FUEL ASSEMBLY ADDED TO UL LISTED |
| | 2200 DIESEL GENERATOR. |
| | PLEASE KNOW THE APPROVAL OF THIS PRODUCT IS NOT BY THIS |
| | OFFICE. COMPLIANCE WITH LISTING STANDARD, NFPA-70, AND |
| | NFPA-110 IS THE RESPONSIBILITY OF THE ENGINEER OF |
| | RECORD, ELECTRICAL CONTRACTOR, GAS CONTRACTOR AND |
| | GENERAL CONTRACTOR OF PROJECT. THIS OFFICE WILL ONLY |
| | VERIFY ITEMS AS NOTED IN REPORT ARE IN FACT LISTED AS |
| | STATED. PLEASE ALSO OBTAIN AT LEAST ONE COPY WHICH |
| | CONTAINS AN ORIGINAL SIGNATURE TO BE PLACED IN FILE OF |
| | PROJECT AT THE CITY. 110.3, 90.7, FBC 106.1.2, 106.5 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |