2008-02-12 10:30:52REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. NEW SHT P0.4A RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. RISER 3" DN AT COLUMN LINE K-3 NOT SHOWN,
 RISER 3" DN NEAR COLUMN LINE K1-L/2-3 NOT SHOWN, RISER
 3" DN AT COLUMN LINE L-8 NOT SHOWN & 4" DN NEAR COLUMN
 LINE K1-4/7-8 NOT SHOWN. ISOMETRIC FOR THE 12TH FLOOR
 ALSO SHOWS THE 14TH FLOOR. PLEASE CLARIFY. SEE COMMENT
 NUMBER 3 FROM PREVIOUS REVISION REVIEW DATED 12/17/07.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  