Plan Review Notes
Plan Review Notes For Permit 06040957
Permit Number 06040957
Review Stop E
Sequence Number 18
Notes
Date Text
2008-05-16 12:07:50** DENIED**
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 ARE NOT COMPLIANT AT THIS TIME.
 PLEASE SEE THE FOLLOWING ITEMS WHICH NEED TO BE
 ADDRESSED.
  
 A) PLEASE BE SURE TO COMPLETE THE CERTIFICATE SHEETS
 WITH ALL DESIGNER INFORMATION, SIGNED, DATED AND SEALED
 AS REQUIRED UNDER FBC 13-103.1.1.1. THE PERSON LISTED
 AS THE PREPARER IS REQUIRED UNDER FLORIDA STATUTES AND
 FLORIDA BUILDING CODE TO BE A LICENSED ENGINEER. ALL
 INFORMATION IS CURRENTLY *BLANK* FOR THE RESPONSIBLE
 DESIGNER(S).
  
 B) PLEASE KNOW THAT ALL INFORMATION, BUILDING
 COMPONENTS, LIGHTING ETC ON PLANS NEEDS TO BE PLACED ON
 THE INPUT DATA REPORT. ALL INFORMATION ON PLANS NEEDS
 TO COORDINATE WITH THE UNKNOWN AND KNOWN ON THIS
 PROJECT. THE INPUT DATA REPORT WILL BE NOTED AS IDR FOR
 THE REMAINDER OF THIS COMMENT.
 FOR EXAMPLE:
  
 PLEASE SEE THE EXTERIOR LIGHTING ON THE PLANS/PROJECT
 DOES NOT CORRELATE WITH THE IDR. THE IDR SHOWS *ALL*
 OUTSIDE/EXTERIOR LIGHTING AS 32W FIXTURES. HOW IS THIS
 POSSIBLE WHEN THE FIXTURES ON THE PLANS ARE CLEARLY A
 MUCH HIGHER WATTAGE? ONE FIXTURE ALONE AS AN EXAMPLE IS
 FIXTURE *EN*. PLANS CLEARLY INDICATE THIS FIXTURE WITH
 A 150VA/WATT RATING. PLEASE SEE 13-415.2.ABC.1.1, .1.2
 AND .1.3. THE WATTAGE/VA RATING REQUIRED BY CODE TO BE
 USED IS THE RATING OF THE FIXTURE. THIS IS ONLY ONE
 FIXTURE AND THERE ARE SEVERAL OTHERS. PLEASE BE SURE
 THE FIXTURE COUNT OF *ALL* EXTERIOR FIXTURES ARE GONE
 OVER.
 THE LIGHTING FOR THE INTERIOR OF THE IDR ALSO DOES NOT
 COORDINATE. PLEASE TAKE A LOOK AT THE PARKING GARAGE
 FIXTURES AND WATTAGES. THESE DO NOT CORRELATE WITH THE
 NUMBER OF FIXTURES ON PLANS OR THE WATTAGES BASED ON
 THE *LATEST* REVISED PLANS SUBMITTED AND ON FILE WITH
 THIS DEPARTMENT.
 *** IMPORTANT, PLEASE SEE THE LIGHTING FOR ALL TENANTS
 UNDER PERMIT IN THIS BUILDING ALSO NEEDS TO COORDINATE
 WITH THE IDR.
  
 ** THESE ARE ONLY TWO EXAMPLES AND IS NOT AND
 EXHAUSTIVE LIST. THERE ARE MANY OTHERS.
 ** PLEASE SEE SOME FLOORS/ZONES AND THE INFORMATION ON
 THE IDRALSO NEED COORDINATING WITH THE PLANS.
 ** PLEASE ALSO SEE COMMENTS FROM BUILDING REVIEWER AS
 ALL BUILDING COMPONENTS ARE ALSO IN NEED OF
 COORDINATING. AS A *HEADS-UP FOR INFORMATION ONLY AND
 DOES NOT CONSTITUTE AS A BUILDING REVIEW: ONE EXAMPLE
 IS EXTERIOR DOORS.
  
 2) NOTE: PLEASE SEE THAT ALL KNOWN ELECTRICAL LOADS ON
 THE BASE BUILDING FOR TENANT SPACES NEEDS TO BE ON BASE
 BUILDING PLANS AND LOAD CALCULATIONS. THE FOLLOWING ARE
 TWO EXAMPLES ONLY. PLEASE BE SURE TO OBTAINED *ALL
 LATEST* REVISED LOADS ON TENANT SPACES. SOME OF THESE
 HAVE BEEN REVISED AS RECENTLY AS ONE WEEK BEFORE THIS
 REVIEW.
 PLEASE SEE TWO TENANTS ARE JB HANAUER AND NTECH. LOADS
 SUBMITTED AND SHOWN ON BOTH OF THESE TENANTS ARE HIGHER
 THAN THE LOADS SHOWN AND FIGURED INTO THE BASE BUILDING
 CALCULATIONS SUBMITTED.
 PLEASE KNOW THESE ARE TWO EXAMPLES ONLY AND ARE NOT A
 EXHAUSTED LIST.
  
 3) NOTE: PLEASE BE SURE THE METHODS OF CONTROLS ON THE
 IDR ARE COORDINATED WITH PLANS. PLEASE KNOW THERE MANY
 WHICH ARE SHOWN AS *MANUAL ON/OFF* WHEN IN FACT THE
 PLANS CLEARLY INDICATE AUTOMATED SYSTEMS AS REQUIRED BY
 FBC CHAPTER 13.
 FBC 106.1.2 FOR COORDINATION ALONG WITH CHAPTER 13.
  
 4) NOTE: PLEASE SEE A PREVIOUS REVIEW COMMENT FROM JAKE
 LEAHY MENTIONS A NEED TO VERIFY CHAPTER 13 COMPLIANCE
 WITH OUTSIDE LIGHTING.
 PLEASE SEE 13-415.1.ABC.1.4 FOR CONTROLS AND UPDATE.
 EXTERIOR LIGHTING COMPLIANCE WITH NOTE #1 IS ALREADY
 COMMENTED ON.
 1
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]