| 2008-05-16 12:07:50 | ** DENIED** |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| | ARE NOT COMPLIANT AT THIS TIME. |
| | PLEASE SEE THE FOLLOWING ITEMS WHICH NEED TO BE |
| | ADDRESSED. |
| | |
| | A) PLEASE BE SURE TO COMPLETE THE CERTIFICATE SHEETS |
| | WITH ALL DESIGNER INFORMATION, SIGNED, DATED AND SEALED |
| | AS REQUIRED UNDER FBC 13-103.1.1.1. THE PERSON LISTED |
| | AS THE PREPARER IS REQUIRED UNDER FLORIDA STATUTES AND |
| | FLORIDA BUILDING CODE TO BE A LICENSED ENGINEER. ALL |
| | INFORMATION IS CURRENTLY *BLANK* FOR THE RESPONSIBLE |
| | DESIGNER(S). |
| | |
| | B) PLEASE KNOW THAT ALL INFORMATION, BUILDING |
| | COMPONENTS, LIGHTING ETC ON PLANS NEEDS TO BE PLACED ON |
| | THE INPUT DATA REPORT. ALL INFORMATION ON PLANS NEEDS |
| | TO COORDINATE WITH THE UNKNOWN AND KNOWN ON THIS |
| | PROJECT. THE INPUT DATA REPORT WILL BE NOTED AS IDR FOR |
| | THE REMAINDER OF THIS COMMENT. |
| | FOR EXAMPLE: |
| | |
| | PLEASE SEE THE EXTERIOR LIGHTING ON THE PLANS/PROJECT |
| | DOES NOT CORRELATE WITH THE IDR. THE IDR SHOWS *ALL* |
| | OUTSIDE/EXTERIOR LIGHTING AS 32W FIXTURES. HOW IS THIS |
| | POSSIBLE WHEN THE FIXTURES ON THE PLANS ARE CLEARLY A |
| | MUCH HIGHER WATTAGE? ONE FIXTURE ALONE AS AN EXAMPLE IS |
| | FIXTURE *EN*. PLANS CLEARLY INDICATE THIS FIXTURE WITH |
| | A 150VA/WATT RATING. PLEASE SEE 13-415.2.ABC.1.1, .1.2 |
| | AND .1.3. THE WATTAGE/VA RATING REQUIRED BY CODE TO BE |
| | USED IS THE RATING OF THE FIXTURE. THIS IS ONLY ONE |
| | FIXTURE AND THERE ARE SEVERAL OTHERS. PLEASE BE SURE |
| | THE FIXTURE COUNT OF *ALL* EXTERIOR FIXTURES ARE GONE |
| | OVER. |
| | THE LIGHTING FOR THE INTERIOR OF THE IDR ALSO DOES NOT |
| | COORDINATE. PLEASE TAKE A LOOK AT THE PARKING GARAGE |
| | FIXTURES AND WATTAGES. THESE DO NOT CORRELATE WITH THE |
| | NUMBER OF FIXTURES ON PLANS OR THE WATTAGES BASED ON |
| | THE *LATEST* REVISED PLANS SUBMITTED AND ON FILE WITH |
| | THIS DEPARTMENT. |
| | *** IMPORTANT, PLEASE SEE THE LIGHTING FOR ALL TENANTS |
| | UNDER PERMIT IN THIS BUILDING ALSO NEEDS TO COORDINATE |
| | WITH THE IDR. |
| | |
| | ** THESE ARE ONLY TWO EXAMPLES AND IS NOT AND |
| | EXHAUSTIVE LIST. THERE ARE MANY OTHERS. |
| | ** PLEASE SEE SOME FLOORS/ZONES AND THE INFORMATION ON |
| | THE IDRALSO NEED COORDINATING WITH THE PLANS. |
| | ** PLEASE ALSO SEE COMMENTS FROM BUILDING REVIEWER AS |
| | ALL BUILDING COMPONENTS ARE ALSO IN NEED OF |
| | COORDINATING. AS A *HEADS-UP FOR INFORMATION ONLY AND |
| | DOES NOT CONSTITUTE AS A BUILDING REVIEW: ONE EXAMPLE |
| | IS EXTERIOR DOORS. |
| | |
| | 2) NOTE: PLEASE SEE THAT ALL KNOWN ELECTRICAL LOADS ON |
| | THE BASE BUILDING FOR TENANT SPACES NEEDS TO BE ON BASE |
| | BUILDING PLANS AND LOAD CALCULATIONS. THE FOLLOWING ARE |
| | TWO EXAMPLES ONLY. PLEASE BE SURE TO OBTAINED *ALL |
| | LATEST* REVISED LOADS ON TENANT SPACES. SOME OF THESE |
| | HAVE BEEN REVISED AS RECENTLY AS ONE WEEK BEFORE THIS |
| | REVIEW. |
| | PLEASE SEE TWO TENANTS ARE JB HANAUER AND NTECH. LOADS |
| | SUBMITTED AND SHOWN ON BOTH OF THESE TENANTS ARE HIGHER |
| | THAN THE LOADS SHOWN AND FIGURED INTO THE BASE BUILDING |
| | CALCULATIONS SUBMITTED. |
| | PLEASE KNOW THESE ARE TWO EXAMPLES ONLY AND ARE NOT A |
| | EXHAUSTED LIST. |
| | |
| | 3) NOTE: PLEASE BE SURE THE METHODS OF CONTROLS ON THE |
| | IDR ARE COORDINATED WITH PLANS. PLEASE KNOW THERE MANY |
| | WHICH ARE SHOWN AS *MANUAL ON/OFF* WHEN IN FACT THE |
| | PLANS CLEARLY INDICATE AUTOMATED SYSTEMS AS REQUIRED BY |
| | FBC CHAPTER 13. |
| | FBC 106.1.2 FOR COORDINATION ALONG WITH CHAPTER 13. |
| | |
| | 4) NOTE: PLEASE SEE A PREVIOUS REVIEW COMMENT FROM JAKE |
| | LEAHY MENTIONS A NEED TO VERIFY CHAPTER 13 COMPLIANCE |
| | WITH OUTSIDE LIGHTING. |
| | PLEASE SEE 13-415.1.ABC.1.4 FOR CONTROLS AND UPDATE. |
| | EXTERIOR LIGHTING COMPLIANCE WITH NOTE #1 IS ALREADY |
| | COMMENTED ON. |
| | 1 |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |