| 2007-12-17 17:18:30 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT P1.08 SANITARY PIPING ON THE REVISION IS UNCLEAR |
| | AS TO ITS INTENT. SOME AREAS STATE "EXISTING PHASE 1 4" |
| | SANITARY THAT IS NOT SHOWN ON PREVIOUS SHEETS. THERE IS |
| | PIPING THAT IS INDICATED AS RUNNING IN THE 11TH FLOOR |
| | CEILING BUT IS INDICATED AS "3IN WASTE DN (FD)AT |
| | TENANT'S 12 FLOOR. IF PIPING IS IN THE 11TH FLOOR, |
| | WOULDNT IT BE UP TO THE 12TH FLOOR? SOME RISERS NOT |
| | IDENTIFIED OR PIPE SIZES NOT SHOWN. NOTES INDICATE 4" |
| | DOWN TO TENANT'S 10TH FLOOR CEILINGAND PLUG FOR |
| | FUTURE EXTENTION. THESE LINES SHALL CONNECT TO THE |
| | SANITARY RISER AT THE TIME OF PIPE INSTALLATION.AREA |
| | AT JUNCTION OF COL K/4 SHOWS A THREE INCH LINE THAT IS |
| | INDICATED AS 3" W CAPPED FOR FUTURE,SHOWS A CAP THEN |
| | EXTENDS ON 1-1/2" STRAIGHT AND 3" OFF TO THE LEFT. ONE |
| | LINE SHOWS A NOTE 4"S DOWN, PLUG 6" ABOVE TENANT'S 12TH |
| | FLOOR. IF PIPING IS ON THE 11TH FLOOR THAN IT SHOULD BE |
| | SHOWN AS 4"S "UP" NOT DOWN. PLEASE CLARIFY.SECTION |
| | 106.1.1. |
| | |
| | 2.THIS REVISION IS ONLY SHOWN ON THE 11TH FLOOR, AND |
| | AS SUCH ONLY THE 11TH FLOOR SHALL BE REVISIED. PLEASE |
| | SUBMIT A REVISION FOR THE 11TH FLOOR ONLY ON A NEW |
| | SHEET, (MAYBE P1.08B). THAT WILL CLEAR UP ALL CONFUSION |
| | THAT HAVING INFORMATION FOR FOUR OTHER FLOORS THAT IS |
| | SHOWN ON SHT P1.08. SECTION 106.1.1. |
| | |
| | 3. SUBMIT A SANITARY RISER DIAGRAM THAT REFLECT THE |
| | CHANGES ON THE 11TH FLOOR. THIS SHALL SHOW THE |
| | CONNECTION ON THE 10TH FLOOR AND THE FUTURE PIPING UP |
| | THRU THE 12TH FLOOR AS WELL. SECTION 106.3.5.1.3. |
| | |
| | REVIEW BY KEN STEVENS |