Plan Review Notes
Plan Review Notes For Permit 06040957
Permit Number 06040957
Review Stop B
Sequence Number 15
Notes
Date Text
2007-05-10 14:08:50BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT: CENTEX CONSTRUCTION
 TEL: (561)629-4174
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.REMOVE ALL
 VOID SHEETS FROM ALL PLANS AND PLACE ONE SET
 OF THEM LOOSELY ON TOP OF THE COLLATED PLANS
 TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2)SHEET A0.21INDICATES A PLANTER THAT PASSES OVER THE
 PROPERTY LINE.
 3202.2.2 ARCHITECTURAL FEATURES.
 COLUMNS OR PILASTERS, INCLUDING BASES AND MOLDINGS
 SHALL NOT PROJECT MORE THAN 12 INCHES (305 MM). BELT
 COURSES, LINTELS, SILLS, ARCHITRAVES, PEDIMENTS AND
 SIMILAR ARCHITECTURAL FEATURES SHALL NOT PROJECT MORE
 THAN 4 INCHES (102 MM).
  
 3) SHEET A1.06 THE 6TH FLOOR IS INDICATED AS A SINGLE
 FLOOR TENANT THE DOUBLE DOORS ON BOTH THE NORTH AND
 SOUTH SIDE SWING AGAINST THE EGRESS FOR OCCUPANT LOADS
 OF 50 OR MORE. 1008.1.2 DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS TRAVEL WHERE SERVING AN OCCUPANT
 LOAD OF 50 OR MORE PERSONS
  
 4) SHEET A3.01 REVISION # 10 AT THE 66'-0" LEVEL
 INDICATES A CHANGE IN THE TRIM, THIS SHEET INDICATES
 PRECAST CONCRETE CORNICE TYPICALBUT THE SECTION 4
 SHEET A4.11 INDICATES THE TRIM TO BE EFIS TYPE TRIM
 ABOVE AND BELOW THE 40' MARK TO DATE NO EFIS TRIM HAS
 BEEN SUBMITTED THAT MEET THE NON-COMBUSTIBILITY TEST.
 1406.2.2 ARCHITECTURAL TRIM.
 IN BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION
 THAT DO NOT EXCEED THREE STORIES OR 40 FEET (12 192 MM)
 IN HEIGHT ABOVE GRADE PLANE, EXTERIOR WALL COVERINGS
 SHALL BE PERMITTED TO BE CONSTRUCTED OF WOOD WHERE
 PERMITTED BY SECTION 1405.4 OR OTHER EQUIVALENT
 COMBUSTIBLE MATERIAL. COMBUSTIBLE EXTERIOR WALL
 COVERINGS, OTHER THAN FIRE-RETARDANT-TREATED WOOD
 COMPLYING WITH SECTION 2303.2 FOR EXTERIOR
 INSTALLATION, SHALL NOT EXCEED 10 PERCENT OF AN
 EXTERIOR WALL SURFACE AREA WHERE THE FIRE SEPARATION
 DISTANCE IS 5 FEET (1524 MM) OR LESS. ARCHITECTURAL
 TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN HEIGHT ABOVE
 GRADE PLANE SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE SECURED TO THE
 WALL WITH METAL OR OTHER APPROVED NONCOMBUSTIBLE
 BRACKETS.
 THE VARIANCE GRANTED BY THE CONSTRRUCTION BOARD OF
 ADJUSTMENT AND APPEAL WAS THAT YOU ONLY NEEEDED TO MEET
 THE CODE REQUIREMENT OF 703.4.
 703.4 NONCOMBUSTIBILITY TESTS.
  
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2 , 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE ? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 SHALL
 BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS.
  
 5) THE OTHER ISSUE THAT I SEE IS IN TERMINOLOGY DETAIL
 4 SHEET A4.11 REVISION# 10 IN THE GARAGE CEILING BEING
 STUCCO ON 5/8" DENSGLASS GOLD, IS THIS FINISH TRUELY
 STUCCO OR AN EFIS FINISH? 106.1.2* ADDITIONAL
 INFORMATION REQUIRED.
  
 6) SHEET A4.12 DETAIL# 1 COMPOSITE ALUMINIUM PANEL
 SYSTEM AT ROOF,A BUILDING PROVISO TO DATE HAS NOT BEEN
 SATISFIED:
 PERMIT:06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT: CENTEX
 TEL: (561) 629-4124
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ALUCOBOND REVIEW
 ACTION: DENIED
 3-19-07
 THE ISSUES WITH THE USE OF ALUCOBOND ON THIS PROJECT IS
 WITH THE WIND PRESSURES NOT FIRE RESISTANCY.
 THE FINAL CLADDING REPORT FROM RWDI REFRENCES FIGURE
 8,12,16 & 20 FOR THE DESIGN OF THE EYEBROW.
 IN REVIEWING THESE PRESSURES AGAIN I BELIEVE THERE IS A
 PROBLEM IN NOT MEETING THE STATED PRESSURES LISTED IN
 THE
 TEST REPORTMIAMI-DADE 00-0802.05. THE FLORIDA COVER
 SHEET BREAKS THE DESIGN PRESSURES OUT BY IF ALUCOBOND
 IS ATTACHED TO A STRUCTURE AND IF THE ALUCOBOND IS
 ATTACHED DIRECTLY TO A PLYWOOD BACKING. SEE THE
 ATTACHED DETAIL TAKEN FROM THE APPROVED PLANS WHERE
 THERE IS NO SOLID BACKING BEHIND THE ALUCOBOND PANEL
 WHICH IS TESTED TO 36PSF NOT NEARLY THE PRESSURES FOUND
 SHEET# 8 OF A RANGE FROM 70 TO 165.
  
 THE SECOND ISSUE WITH THIS SYSTEM WILLSTILL REQUIRE
 ADDITIONAL FASTENERS TO ACHIEVE THE PRESSURES FOUND AT
 THE ROOF TOP LEVELS, THE ENGINEER OF RECORD WILL NEED
 TO SUBMIT THIS INFORMATION
 NOTE ONE SET OF PRODUCT APPROVAL AND RWDI COVERSHEET
 ARE BEING RETAINED.
 PLEASE CONTACT THIS OFFICE IF THERE IS FURTHER
 ASSISTANCE REQUIRED.
  
 7) SHEET A4.14 DETAIL # 3 THE MINIMUM VERTICAL CLEAR
 DISTANCE FOR VAN ACCESSIBLE PARKING IS NOT 96" BUT 98"
 11-4.6.5.
  
 8)SHEET A4.14 DETAILREVISION# 10 INCLUDES A
 SKYLIGHT PLEASE PROVIDE PRODUCT APPROVALS FOR SKYLIGHT
 AND ADDITIONAL INFORMATION ON THE CURBING AND
 ATTACHMENT TO CURB .
  
 9)SHEET A4.21 DETAIL # 1 IS A DETAIL OF THE FRAMING
 FOR THE MCM PANELS REFERS TO STRUCTURAL SHEET S1.17
 DETAIL 1 DOES NOT PROVIDE THE HORIZONTAL FRAMING MEMBER
 INFORMATION
 AS SHOWN ON THE ARCHITECTURAL PLAN. THE SAME S DETAIL
 SHOWN S5.03 AND NO HORIZONTAL FRAMING MEMBERS ARE
 SHOWN?
  
 10) A2.16 ELEVATOR VESTIBULE 1606INDICATES WALL TYPE 6A
 WHICH IS A 1HR RATED WALL BUT DOOR # A1606 ON THE DOOR
 SCHEDULE A8.11INDICATE A REVISION AND THE DOOR RATING
 WAS REMOVED.
  
 11) THERE ARE MANY SHEETS THAT DO NOT INDICATE ANY
 CHANGES BUT WERE SUBMITTED AS A REVISION, PLEASE
 PROVIDE ADDITIONAL INFORMATION WHY THESE SHEETS WERE
 PROVIDED?
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  