2007-05-08 14:22:05BUILDING PLAN REVIEW
 PERMIT:06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT: CENTEX
 TEL: (561) 629-4124
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 EFIS TRIM REVIEW: DENIED
  
 THE CONSTRUCTION BOARD OF ADJUSTMENT AND APPEALS
 GRANTED THE USE OF EFIS TRIM AS IS STATED IN THE 2004
 FBC, SECTION 1406.2.2,THAT THE PETIONER WOULD STILL
 NEED TO PROVIDE A PRODUCT THAT MEETS THE REQUIREMENTS
 OF 703.4 THE NON-COMBUSTIBILITY TEST.
  
 703.4 NONCOMBUSTIBILITY TESTS.
  
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2 , 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 SHALL
 BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS.
  
 THE BOARD REFRENCED ASTM E-84 AS THE STANDARD, THIS
 STANDARD IS TO BE USED WITH COMPOSITE TYPE MATERIALS,
 THAAT IS PUT TOGETHER, OR FORMED FROM DISTINCT PARTS. I
 DO NOT BELIEVE THE EFIS TRIM SYSTEM CAN MEET THIS
 CRITERIA, IT WOULD APPEAR THAT THE NON-COMBUSTIBILITY
 TEST FOR ELEMENTARY MATERIALS ASTM E-136 WOULD BE THE
 TEST REQUIRED FOR THE EFIS TYPE TRIM SYSTEM.
  
 IN THE E-136 REPORT RESULTS (8)
 8.1) REPORT THE MATERIAL AS PASSING THE TEST IF AT
 LEAST THREE OF THE FOUR TEST SPECIMENS MEET THE
 FOLLOWING CONDITIONS:
 8.1.1) THE RECORDED TEMPERATURE OF THE SURFACE AND
 INTERIOR THERMOCOUPLES DO NOT AT ANY TIME DURING THE
 TEST RISE MORE THAN 54 DEGREES ABOVE THE STABILIZED
 TEMPERATURE MEASURED AT T2 PRIOR TO THE TEST. 8.1.2)
 THERE IS NO FLAMING FROM THE SPECIMEN AFTER THE FIRST
 30 SECONDS, AND
 8.1.3) WHEN THE WEIGHT LOSS OF THE SPECIMENDURING THE
 TESTING EXCEEDS 50%, THE RECORDED TEMPERATURE OF THE
 SURFACE AND INTERIOR THERMOCOUPLES DO NOT AT ANY TIME
 DURING THE TEST RISE ABOVE THE FURNACE AIR TEMPERATURE
 AT THE BEGINNING OF THE TEST, AND THERE IS NO FLAMING
 OF THE SPECIMEN.
  
 THE REPORT SUBMITTED IS A TEST FOR FLAMMABILITY, NOT OF
 COMBUSTIBILITY, THE OTHER ISSUE WITH THIS REPORT IS
 THERE IS NO REFERENCE TO EITHERTHE ASTM E-136 OR ASTM
 E-84.
 IN THE TEST RESULTS THE REPORT STATES THERE WAS MOLTEN
 EXPANDED POLYATRRENE DROPLETS FALLING FROM THE TEST
 SPECIMEN. THIS WOULD BE PUTTING THE FIRE FIGHTERS AT
 GREAT RISK!
 THIS IS WHY THE TEST HAS TO INDICATE
 NON-COMBUSTIBILITY!
  
 THE OTHER ISSUE WILL BE TO HAVE THIS PRODUCT PASS THE
 REVIEW THE PLANS WILL ALSO HAVE TO REFLECT THE PRODUCT
 THAT IS BEING PROPOSED, A REVISION. IF THE REVISION IS
 TO INCLUDE THE MOLDING BEING ADHERRED TO THE WALL OR IF
 THE MOLDING IS TO BE PINNED, THEN AGAIN THE DESIGN
 PROFESSIONALS WILL INDICATE THE TYPE OF FASTENING
 SYSTEM TO BE USED. THE BACK UP DATA WILL BE NEEDED FOR
 REVIEW AS WELL.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 PLAN REVIEW II - BUILDING
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]