Plan Review Notes
Plan Review Notes For Permit 06040957
Permit Number 06040957
Review Stop M
Sequence Number 13
Notes
Date Text
2007-11-10 15:33:21REVISION #: 23
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 REVISION FOR H0.02, H1.16, H1.17, H2.04
 REVISION FOR SMOKE CONTROL NARRATIVE AND RATIONAL
 ANALYSIS.
  
 NO EXCEPTION IS TAKEN TO THE REVISIONS ON H0.02, H1.16
 AND H1.17. HOWEVER, THESE PLANS WILL NOT BE
 INCORPORATED INTO THE PERMIT SET PRIOR TO ACCEPANCE OF
 THE SMOKE CONTROL SEQUENCE WHICH GOVERNS THE
 FUNCTIONALITY OF THE NEWLY ADDED EQUIPMENT.
 1. ON PG H2.04 THE SEQUENCE CONTAINS CONFLICTING
 INSTRUCTIONS.
 IN SEQUENCE (B) FOR FLOORS 6 THROUGH 16, SUBSECTION (E)
 INDICATES THAT FLOORS 15 AND 16 ARE STILL BEING TREATED
 AS INDIVIDUAL ZONES RATHER THAN ONE ZONE. THIS DOES NOT
 CORRELATE WITH ACTIONS CALLED FOR UNDER SEQUENCE (C)
 FOR THE 14TH FLOOR AND IT IS IN CONFLICT WITH SEQUENCE
 (D) WHICH DOES CALL FOR THE 15TH AND 16TH FLOORS TO BE
 TREATED AS ONE ZONE.
  
 2. THE NARRATIVE/ANALYSIS CONTAINS SIMILAR CONFLICTING
 INFORMATION. ON PAGE 3, PARAGRAPH 4 INDICATES THAT THE
 16TH FLOOR WILL BE TREATED AS AN INDIVIDUAL SMOKE ZONE.
 PARAGRAPH 5 EXPLAINS THAT FLOORS 15 AND 16 ARE ONE
 ZONE.
  
 ONCE THE CONFLICTING INFORMATION IS REMOVED AND/OR
 CORRELATED IN THE NARRATIVE AND ON THE PLANS, THE
 ADJUSTMENTS BEING MADE TO TREAT FLOORS 15 AND 16 AS ONE
 SMOKE ZONE MAY BE IN ORDER, DEPENDIG ON HOW THESE
 COMMENTS ARE ADDRESSD. PLEASE MAKE THE NECESSARY
 CORRCTIONS AND CLARIFICATIONS, THEN RESUBMIT.
  