| Plan Review Notes For Permit 06040957 |
| Permit Number |
06040957 |
|
| Review Stop |
M |
| Sequence Number |
12 |
|
| Notes |
| Date |
Text |
| 2007-10-11 08:43:32 | **************PROVISO**************** | | | | | | 1. H1.07 THRU H1.16: VAV BOX HAS BEEN ADDED TO HVAC | | | SYSTEM TO CONDITION EXEC. VESTIBULE. THIS BOX DOES NOT | | | HAVE AN EQUIPMENT DESIGNATION ON FLOOR PLAN. ALSO, THE | | | VAV SCHEDULE ON H0.02 HAS NOT BEEN REVISED TO SHOW THIS | | | NEW SIZE VAV. PLEASE REVISE BOTH PAGES, PROVIDING | | | MISSING INFORMATION AND SHOWING COORDINATION BETWEEN | | | FLOOR PLANS AND EQUIPMENT SCHEDULES. FBC 106.1.1, | | | 106.1.3 | | | | | | 2. H1.07 THRU H1.16: RISER 8 HORIZONTAL DUCTS ARE NOT | | | SHOWN TO HAVE REQUIRED OPENING PROTECTIVES WHERE THEY | | | PENETRATE THE SHAFT WALL AT EACH LEVEL. RATHER, THE FSD | | | IS SHOWN AT A WALL ON THE OTHER SIDE OF THE SERVICE | | | VESTIBULE. PLEASE REVISE PLANS TO SHOW HOW THE SHAFT | | | RATING IS TO BE MAINTAINED IN ACCORDANCE WITH FBC,M | | | 607.5.5.1. | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|