2007-03-19 12:44:14BUILDING PLAN REVIEW
 PERMIT:06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT: CENTEX
 TEL: (561) 629-4124
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ALUCOBOND REVIEW
 ACTION: DENIED
 3-19-07
 THE ISSUES WITH THE USE OF ALUCOBOND ON THIS PROJECT IS
 WITH THE WIND PRESSURES NOT FIRE RESISTANCY.
 THE FINAL CLADDING REPORT FROM RWDI REFRENCES FIGURE
 8,12,16 & 20 FOR THE DESIGN OF THE EYEBROW.
 IN REVIEWING THESE PRESSURES AGAIN I BELIEVE THERE IS A
 PROBLEM IN NOT MEETING THE STATED PRESSURES LISTED IN
 THE
 TEST REPORTMIAMI-DADE 00-0802.05. THE FLORIDA COVER
 SHEET BREAKS THE DESIGN PRESSURES OUT BY IF ALUCOBOND
 IS ATTACHED TO A STRUCTURE AND IF THE ALUCOBOND IS
 ATTACHED DIRECTLY TO A PLYWOOD BACKING. SEE THE
 ATTACHED DETAIL TAKEN FROM THE APPROVED PLANS WHERE
 THERE IS NO SOLID BACKING BEHIND THE ALUCOBOND PANEL
 WHICH IS TESTED TO 36PSF NOT NEARLY THE PRESSURES FOUND
 SHEET# 8 OF A RANGE FROM 70 TO 165.
  
 THE SECOND ISSUE WITH THIS SYSTEM WILLSTILL REQUIRE
 ADDITIONAL FASTENERS TO ACHIEVE THE PRESSURES FOUND AT
 THE ROOF TOP LEVELS, THE ENGINEER OF RECORD WILL NEED
 TO SUBMIT THIS INFORMATION
 NOTE ONE SET OF PRODUCT APPROVAL AND RWDI COVERSHEET
 ARE BEING RETAINED.
 PLEASE CONTACT THIS OFFICE IF THERE IS FURTHER
 ASSISTANCE REQUIRED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]