| Plan Review Notes For Permit 06040957 |
| Permit Number |
06040957 |
|
| Review Stop |
P |
| Sequence Number |
11 |
|
| Notes |
| Date |
Text |
| 2007-09-10 10:21:25 | REVISIONS DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | 1. SHT P1.01 RWL NOTE BY COL. LINE 1/F.9 INDICATES 3" | | | RWL UP TO CANOPY DRAIN & 3" COND. DOWN. PLEASE CLARIFY | | | AS CONDENSATE SHALL DRAIN OUT OF THE BUILDING | | | SEPARATELY FROM THE STORM WATER. SECTION 106.1.1. | | | | | | 2. SHT P1.01 4" DRAIN NEAR COL. LINE 5/H IS NOT | | | INDICATED WITH A CLOUD, NOR DOES IT HAVE A REVISION | | | NUMBER. ALSO THIS DRAIN LINE IS NOT INDICATED ON THE | | | UNDERGROUND PIPING. PLEASE INDICATE WHERE THIS NEW | | | DRAIN LINE CONNECTS TO THE UNDERGROUND BUILDING DRAIN | | | LINE. SECTION 106.1.2. PLEASE CLOUD AND NUMBER ALL | | | REVISIONS. | | | | | | 3. SHT P1.17 NOTE INDICATES A FLOOR DRAIN FOR INDIRECT | | | WASTE. FLOOR DRAINS ARE NOT APPROVED INDIRECT WASTE | | | RECEPTORS. A FLOOR SINK WILL BE REQUIRED PER SECTION | | | 802.3. PLEASE CHANGE NOTE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|