| 2007-08-12 13:57:35 | ** PROVISO ** |
| | |
| | CONDITIONS ISSUED FOR PLANS SUBMITTED, PERMIT FOR BASE |
| | BUILDING AND EQUIPMENT BEING INSTALLED. |
| | |
| | PLEASE SEE THE FOLLOWING SHEETS HAVE BEEN REDLINED WITH |
| | NOTES TO SEE *PROVISO* AS WILL BE ATTACHED TO THE SHEET |
| | E0.01. |
| | |
| | 1) NOTE: PLEASE SEE THAT REVISED GENERATOR SPECS/CUT |
| | SHEETS AND SUBMITTAL LETTER IS TO BE SUBMITTED. THIS |
| | HAS NOT BEEN SUBMITTED UNDER THE BASE BUILDING PERMIT |
| | AND WILL BE REQUIRED BEFORE ISSUANCE OF THE |
| | GENERATOR(S) PERMIT. |
| | RESPONSE MENTIONS THAT THE CONTRACTOR HAS ASSURED |
| | DESIGN THESE WERE SUBMITTED, HOWEVER THESE WERE NOT |
| | LOCATED ON THIS REVISION OR OTHER PREVIOUS REVISIONS AS |
| | SUBMITTED. THE DOCUMENTS AS SUBMITTED UNDER THE |
| | GENERATOR PERMIT APPLICATION WERE NOT COMPLETE. |
| | PLEASE KNOW THAT THE BI-FUEL UNITS WILL BE REQUIRED TO |
| | BE LISTED AND INDICATE EPA CERTIFICATION AS AGREED IN |
| | MEETING WITH DESIGN TEAM REPRESENTATIVE MR. DAVE ALLEN |
| | PE. |
| | NEC 110.3, 90.7. |
| | FBC 106.1.2 |
| | |
| | 2) NOTE: PLEASE SUBMIT REVISED ENERGY CALCULATIONS FOR |
| | BASE BUILDING AS THE TENANT BUILD OUTS WERE NOT PART OF |
| | THE BASE BUILDING AND THE ORIGINAL ASSUMPTIONS MAY NO |
| | LONGER BE USED ONCE A SPECIFIC DESIGN IS SET-FORTH. |
| | PLEASE REVISE ACCORDINGLY FBC 13-415.1.A, 13-415.1.B |
| | AND 13-415.1.C. |
| | 13-103.1.1.1 |
| | **THESE ARE REQUIRED TO BE REVISED, SUBMITTED, STAMPED |
| | AND ON-SITE FOR INSPECTOR BEFORE APPLYING FOR TCO ** |
| | |
| | |
| | 3) NOTE: PLEASE BE SURE TO REVISE ALL FLOOR LAYOUTS AND |
| | LOAD CALCULATIONS WITH THE SPECIFICS TO EACH FLOOR AND |
| | ALL LOADS FROM BUILD OUTS WITH KNOWN LOADS. |
| | PLEASE SEE THAT MANY FLOORS WILL BE REVISED DUE TO |
| | TENANT BUILD OUTS. |
| | **THESE ARE REQUIRED TO BE REVISED, SUBMITTED, STAMPED |
| | AND ON-SITE FOR INSPECTOR BEFORE APPLYING FOR TCO ** |
| | |
| | 4) NOTE: REDLINED NOTE ON E0.03, AS THE NOTE STILL |
| | STATES *ALL* DUCT BANKS ARE TO CONTAIN SAND* THIS IS |
| | NOT THE CASE AS SOME ARE CONCRETE ENCASED. |
| | NO CORRECTION IS NEEDED AS THIS WAS ONLY REDLINED AND |
| | NOTED. |
| | |
| | |
| | ** PLEASE KNOW THAT THE ABOVE NO WAY INDICATES THAT ALL |
| | OTHER TYPES OF REVISIONS SHOULD, NEED OR ONLY NEED BE |
| | SUBMITTED BEFORE TCO. THERE MAY BE SEVERAL CHANGES ON |
| | SITE WHICH WILL STILL BE REQUIRED TO BE SUBMITTED |
| | DURING THE PROJECT. |
| | |
| | **THE CONDITIONS WITH THE CONSTRUCTION BOARD OF APPEALS |
| | ARE REQUIRED TO BE MET FOR PROJECT FOR ALL AS APPLIED |
| | BY THE CONTRACTOR/OWNER/DEVELOPER FOR EACH FLOOR OF |
| | THIS BUILDING. |
| | |
| | |