Plan Review Notes
Plan Review Notes For Permit 06040957
Permit Number 06040957
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-06 00:00:00 
 ***************UNSAT ***************
  
 CITY PLACE OFFICE TOWER
 525 OKEECHOBEE BLVD.
  
  
  
 *** PLEASE KNOW PLANS AND SUBMITTED
 PAPER WORK IS NOT COMPLETE AT THIS TIME
 FOR A COMPLETE AND SUFFICIENT REVIEW.
 PLEASE KNOW THERE MAY BE FURTHER
 COMMENTS ONCE ALL INFORMATION IS
 SUBMITTED.
  
 1) NOTE: PLEASE KNOW, BEFORE
 RE-SUBMITTING PLANS. PLEASE COMPLETELY
 REMOVE ALL OLD/VOIDED SHEETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETED
 SETS FOR REVIEW AND STAMPING. PLEASE
 KNOW SINCE MANY OF THE COMMENTS BELOW
 AFFECT ALL OF THE SHEETS IN THE SETS,
 ONLY ONE ROLL OF OLD SETS SHOULD BE
 SUBMITTED FOR REFERENCE WHEN PLANS ARE
 BROUGHT BACK. THESE SHOULD BE LABELED
 "OLD/VOIDED".
  
 2) NOTE: PLEASE SEE MISSING INFORMATION
 ON MANY OF THE TITLE BLOCKS ON PLANS.
 PLEASE SEE MISSING FIRM LICENSE NUMBERS
 WHICH ARE THE CERTIFICATE OF
 AUTHORIZATION NUMBERS FOR MORE THAN ONE
 FIRM. PLEASE SEE LANDSCAPE AND MEP
 ENGINEERING FIRMS. PLEASE ALSO SEE MANY
 SHEETS ARE MISSING THE PRINTED NAME AND
 LICENSE NUMBER FOR THE PERSON SIGNING
 AND SEALING SAID DOCUMENTS.
 PLEASE SEE THE FLORIDA ADMINISTRATIVE
 CODE 61G1-16.004 AND 61G15-23.002.
 FLORIDA STATUES 471.023, 481.219
  
 3) NOTE: PLEASE SEE OTHER SHEETS WHICH
 CONTAIN A "STAMP" FOR THE REQUIRED
 "ORIGINAL" SIGNATURE BY THE DESIGN
 PROFESSIONAL. PLEASE SEE "S" SHEETS.
 FLORIDA STATUES 471.025
 PLEASE ALSO SEE ANY COMMENTS FROM OTHER
 TRADES WHICH RESPECT TO THE SEAL
 CONTAINING THE WORDING OF "CERTIFICATE"
 WHICH IS NOT LONGER ACCEPTED.
 FAC 61G1-16.001
  
 4) NOTE: PLEASE SEE PLANS SHALL CONTAIN
 THE FOLLOWING MIN CODES REFERENCED AND
 LISTED ON PLANS FOR DESIGN.
 THE ARCHITECTURAL LISTS THE 2004 FBC.
 PLEASE LIST:
 2002 NFPA-70 NATIONAL ELECTRICAL CODE
 2003 NFPA-101 LIFE SAFETY CODE
 2003 NFPA-20 FIRE PUMPS
 2002 NFPA-110 EMERGENCY AND.
 STANDBY POWER SYSTEMS.
 NFPA-72 2002
 THESE ARE REQUIRED AT A MIN.
  
 5) NOTE: PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR THE FOLLOWING.
 GENERATOR(S), ATS SWITCHES, FIRE PUMP,
 FIRE PUMP CONTROLLER, FUEL TANK,
 PARALLELING SWITCH GEAR AND OTHER
 ASSOCIATE SWITCHGEAR.
 PLEASE KNOW, NONE OF THESE WERE
 SUBMITTED AND UNABLE TO VERIFY MANY
 ITEMS FOR CODE COMPLIANCE AT THIS TIME.
 PLEASE BE SURE ALL EQUIPMENT SHEETS
 /SPECS CONTAIN LISTINGS FROM A NRTL.
  
 6) NOTE: PLEASE SEE PLANS SEEM TO
 INDICATE THE 2000KW GENERATORS LOCATED
 ON A SEPARATE PROPERTY. PLEASE KNOW,
 PROPERTY LINES MAY CHANGE, SEPARATE
 PERMIT MAY BE REQUIRED ALSO IF INDEED
 THESE ARE ON SEPARATE PROPERTIES. THERE
 MAY ALSO BE THE POSSIBILITY OF EASEMENTS
 WHICH MAY NEED TO BE GRANTED.
 PLEASE ALSO SEE THE ELEVATOR TOWER BEING
 CONSTRUCTED NEXT TO THE PARKING GARAGE
 ALSO SEEM TO BE ON A SEPARATE LEGAL
 PROPERTY BEING FED FROM THE MAIN TOWER.
 PLEASE KNOW THIS MAY NOT BE POSSIBLE
 DEPENDING ON THE OUTCOME OR CHANGES IN
 PROPERTY LINES ETC.
 PLEASE SEE THE PROPOSED WORK IN CORRIDOR
 LOCATED AT THE "B" BLOCK GARAGE
 STRUCTURE WILL BE REQUIRED UNDER A
 SEPARATE PERMIT.
 ** PLEASE ALSO SEE BUILDING REVIEW
 COMMENTS FOR ABOVE AS MANY OF THESE
 ITEMS ARE TO BE PLACED IN BUILDING
 REVIEW AND MAY AFFECT PLANS SUBMITTED.
  
 7) NOTE: PLEASE CLARIFY USE AND
 EQUIPMENT IN THE CATERING ROOM AS STATED
 ON 6TH FLOOR. PLEASE LIST ALL 15/20AMP
 120V RECEPTS AS GFI/GFI PROTECTED AS PER
 210.8B3.
 (KITCHENS IN OTHER THAN DWELLING UNITS)
  
 8) NOTE: PLEASE SEE GATES ARE INDICATED
 AT TWO DIFFERENT LOCATIONS, HOWEVER
 ELECTRICAL TO THESE DO NOT SEEM TO BE
 COMPLETE AT THIS TIME.
 PLEASE PROVIDE INFORMATION FOR ACCESS
 AND EGRESS IN THE EVENT OF POWER FAILURE
 AND/OR OVER RIDE FOR THESE. PLEASE SEE
 FIRE REVIEW COMMENTS AS THIS MAY BE IN
 QUESTION.
  
 8) NOTE: PLEASE SUBMIT COMPLETED PANEL
 SCHEDULES FOR ALL PANELS. THE PANELS ARE
 INDICATED ON E3.03 ARE NOT SUFFICIENT
 FOR REVIEW OF ALL SAID ELECTRICAL BRANCH
 CIRCUITS FOR OVERCURRENT PROTECTION,
 CONDUCTOR SIZES ETC.
 215.5
 MANY ITEMS CAN NOT BE REVIEWED AT THIS
 TIME.
 AN EQUIPMENT SCHEDULE AS SUBMITTED IS
 OK, HOWEVER THESE ITEMS SHOULD BE LISTED
 ON PANEL SCHEDULES TO BE SUBMITTED.
  
 9) NOTE: PLEASE COMPLETE ALL THE
 CIRCUITING AND SWITCH LEGS ON PLANS AND
 LAYOUTS. PLEASE SEE MANY AREAS ARE LEFT
 TO FIGURE WHERE THESE DEVICES, OUTLETS,
 OR LIGHTING OUTLETS ARE BEING FED FROM
 AND/OR CONTROLLED.
 PLEASE CORRELATE WITH PANEL SCHEDULES TO
 BE SUBMITTED.
 215.5
  
 10) NOTE: PLEASE CORRELATE ARCHITECTURAL
 PLANS WITH ELECTRICAL. PLEASE SEE FLOORS
 6-14 ARE SHOWN CONTAINING A CORRIDOR TO
 MAIN ELECTRICAL ROOM ON EACH OF THESE
 FLOORS ON ELECTRICAL PLANS, HOWEVER
 ARCH DO NOT SHOW THESE CORRIDORS OF
 COMMON AREAS.?
 PLEASE SEE FLOORS 15 AND 16 ON BOTH A
 AND E?S DO NOT SHOW ANY CORRIDORS AND
 OBTAININGACCESS TO THE ELECTRICAL ROOM
 ON EACH OF THOSE FLOORS ARE ONLY THROUGH
 THE PROPOSED FUTURE TENANT SPACE. PLEASE
 KNOW IT IS NOT KNOWN AT THIS TIME IF
 THERE WILL BE ONE, TWO THREE OR MORE
 TENANTS ON EACH FLOOR AND ACCESS TO EACH
 TENANT'S ELECTRICAL PANEL(S) AND OVER
 CURRENT PROTECTION DEVICES MAY NOT BE
 THROUGH TENANT OCCUPANCY. PLEASE ALSO
 KNOW THE HOUSE POWER/COMMON AREAS MAY
 ALSO NOT BE ACCESSED THROUGH THE
 TENANT'S SPACE.
 PLEASE KNOW, EACH CORRIDOR AS SHOWN ON
 FLOORS 6-14 SHALL BE THE SAME ON ALL
 FLOORS AND SHOULD CORRELATE AS THE SAME
 ON ARCHITECTURAL SHEETS.
 210.25, 215.5, 240.24
  
 11) NOTE: PLEASE PROVIDE EXIT/EGRESS
 LIGHTING TO THE PUBLIC RIGHT OF WAY.
 PLEASE SEE THE PUBLIC RIGHT OF WAY IS
 NOT DIRECTLY OUTSIDE THE STAIR #2 DOOR
 AND THE PUBLIC RIGHT OF WAY SEEMS TO BE
 LOCATED AROUND THE FRONT OF THE
 BUILDING. PLEASE SEE BUILDING REVIEW
 NOTES FOR EXIT CORRIDOR FOR STAIR #2.
 PLEASE SEE PLANS REDLINED FOR POSSIBLE
 CHANGE WHICH MAY BE OPTED FOR.
 NFPA-101 7.8, 7.9.
  
 12) NOTE: PLEASE SEE CONDUITS AND
 FEEDERS FROM ATS #1 AND ATS #2 ARE BEING
 NOTED AS INSTALLED IN RATED EXIT
 CORRIDOR.
 PLEASE SEE THESE CONDUITS MAY NOT BE
 LOCATED AS SHOWN ON PLANS.
 THIS IS NOT SHOWN ON ARCHITECTURAL
 SHEETS AND THIS INFORMATION WAS GIVEN TO
 THE BUILDING REVIEWER. PLEASE SEE
 BUILDING NOTES.
  
 13) NOTE: PLEASE CLARIFY ALL MAINS AND
 DISTRIBUTION EQUIPMENT CONTAINING ALL
 MAINS, GROUPING ETC PER 230.70, 230.72,
 230.76, 230.79, AND 225.31-225.39
 PLEASE KNOW, DUE TO THE INFORMATION OF
 THE SWITCH GEAR NOT SUBMITTED, SHOWN AND
 WHETHER OR NOT THESE CONTAIN MAINS, WITH
 MANUAL MEANS OF DISCONNECT LOCATED ON
 THE OUTSIDE OF THE EQUIPMENT, GROUPED
 ETC. THE LOCATIONS OF SOME SERVICE
 EQUIPMENT CAN NOT REVIEWED FOR LOCATIONS
 AT THIS TIME.
  
 14) NOTE: PLEASE SEE THE EMERGENCY
 SYSTEMS ARE BEING SHOWN IN THE SAME
 EQUIPMENT AS THE NORMAL MAINS. PLEASE
 KNOW, THESE SHALL NOT BE LOCATED IN THE
 SAME EQUIPMENT AND SERVED BY THE SAME
 SERVICE.
 PLEASE REVISE SERVICE AS SHOWN.
 701.1, NFPA-110 CHAPTER 7 ETC
  
 15) NOTE: PLEASE SEE SOME AREAS AT THE
 EXIT TO THE STAIRS IN THE PARKING
 GARAGES WILL BE REQUIRED TO CONTAIN A
 BATTERY BACK UP FIXTURE OF SOME SORT
 DEPENDING ON THE OPERATION OF THE
 STAND-BY GENERATORS. PLEASE CLARIFY IF
 ORDER OF OPERATION OF THE GENERATORS AS
 WILL BE SO THAT OF THE SINGLE OCP AT THE
 800KW GEN TRIPS THE OTHER TWO STAND-BY
 GEN?S WILL COME ONLINE?
 PLEASE SEE 7.9.2.2
  
 16) NOTE: PLEASE A KNOW, A BATTERY BACK
 UP LT FIXTURE WILL BE REQUIRED IN MAIN
 ELECTRICAL ROOM(S), MAIN ELECTRICAL RM
 ON 5TH FLR, ELEVATOR EQUIPMENT ROOMS,
 FIRE PUMP ROOM, FIRE COMMAND ROOMAND
 GEN ROOM. PLEASE KNOW SOME OF THESE ARE
 SHOWN ALREADY AND DO NOT NEED TO BE
 ADDED, HOWEVER SOME ARE NOT.
 700.16,7.8.1.3,7.9.2.2 700.22 ETC.
  
 17) NOTE: PLEASE SEE SOME ELECTRICAL
 ROOMS DOORS SEEM TO SWING INTO EITHER
 ELECTRICAL EQUIPMENT OR OTHER EQUIPMENT
 SHOWN ON PLANS.
 PLEASE SEE DOOR SWINGS ON SOME DOORS
 WILL BE REQUIRED TO SWING OUT (5TH FLOOR
 MAIN RM) .
 PLEASE SEE SOME ROOMS APPEAR TO SHOW
 EQUIPMENTIN THE MIN CLEARANCE AREAS
 REQUIRED PER 110.26.
 PLEASE ALSO PLACE NOTES ON PLANS AT
 LOCATION FOR MAIN ELECTRICAL ROOMS THAT
 ALL DOORS SHALL BE EQUIPMENT WITH SUCH
 ACCEPTED PANIC HARDWARE AND OPEN ON THE
 MEANS OF EGRESS WITH OUT ANY TRIPPING
 HAZARDS.
 PLEASE KNOW THIS WILL AFFECT DOOR
 SCHEDULE ON ARCHITECTURAL PLANS AND
 POSSIBLE DOOR SWINGS ON A SHEETS AS NOW
 SHOWN.
  
 18) NOTE: PLEASE PROVIDE THE ELEVATION
 OF THE EM DISTRIBUTION SYSTEM AND
 EQUIPMENT.
 PLEASE SEE NFPA-110 7.2.3* WHICH
 REQUIRES THE ELEVATION TO MEET THE
 "SLOSH" PREDICTION LEVELS BASED ON A
 CATEGORY 4 STORM.
 THE ELEVATION FOR PROPERTY SHOULD BE OK,
 HOWEVER THIS ELEVATION IS REQUIRED TO BE
 STATED ON PLANS AND VERIFICATION THAT
 ALL REQUIRED EMERGENCY SYSTEMS ARE
 ABOVE.
 PLEASE SEE THAT "SLOSH", MEANS SEA,
 LAKE, OVERLAND, SURGES BY HURRICANES.
  
 19) NOTE: PLEASE COMPLETE FIXTURE
 SCHEDULES AND PLEASE CORRELATE ALL
 FIXTURES AS SHOWN ON PLANS WITH THE
 FIXTURES SCHEDULES SUBMITTED.
 215.5
  
 20) NOTE: PLEASE SEE RISER IS SHOWING
 GFI PROTECTION FOR SOME MAINS???
 PLEASE SEE GF (GROUND FAULT) PROTECTION
 IS REQUIRED PER 240.13, 230.95 ETC ,
 HOWEVER PLEASE SEE GFI PROTECTION IS
 PERSONNEL PROTECTION.
 PLEASE SEE PROTECTION IS ALSO BEING
 SHOWN ON ALL SECONDARY OVER CURRENT
 PROTECTION??
 PLEASE KNOW, THIS IS NOT REQUIRED FOR
 THIS STRUCTURE, CLASS AND OCCUPANCY, BUT
 HOWEVER IS PERMITTED.
 PLEASE ALSO SEE GF SEEMS TO BE SHOWN ON
 THE EM SIDE OF THE DISTRIBUTION
 SYSTEM(S) WHICH IS UNCLEAR. PLEASE SEE
 700.7D, 700.26, NFPA-110
 PLEASE SEE THE CODE IS CLEAR WHEN GROUND
 FAULT PROTECTION IS REQUIRED AND WHEN
 SENSING OF SUCH GROUND FAULTS ARE
 REQUIRED , HOWEVER PLEASE KNOW GROUND
 FAULT PROTECTION IS NOT IDEALON THE
 EMERGENCY SIDE DUE TO THE NATURE OF THE
 EMERGENCY DISTRIBUTIONSYSTEM AND THE
 NEED OF MAINTAINING CERTAIN SYSTEMS ON
 DURING AN EMERGENCY.PLEASE KNOW,
 SENSING OF THE GROUND FAULT WOULD BE
 NEEDED TO CORRECT ANY SITUATION IN SUCH
 EQUIPMENT. PLEASE KNOW, IT HAS BEEN
 DETERMINED BY THIS AHJ, THAT THE GF
 PROTECTION ON THE REQUIRED EM SYSTEMS
 SHOULD NOT BE PROVIDED AND ONLY SENSING
 FOR THE PURPOSE AS STATED AND REQUIRED.
  
 21) NOTE: PLEASE KNOW, 4-POLE ATS
 SWITCHES ARE BEING SHOWN AS REQUIRED TO
 ACHIEVE THE CORRECT GROUND FAULT
 SENSING, HOWEVER THE GENERATORS DO NOT
 SEEM TO BE INDICATED A SEPARATELY
 DERIVED AS REQUIRED.
 250.30, 250.50.
  
 22) NOTE: PLEASE SEE THE GROUNDING
 ELECTRODE SYSTEM IS REQUIRED TO SHOW THE
 FOOTER/FOUNDATION STEEL AS PART OF THE
 GROUNDING ELECTRICAL SYSTEM.
 250.50
  
 23) NOTE: PLEASE SEE A NOTE ON PLANS
 MENTIONS THAT A LIGHTNING PROTECTION
 SYSTEM WILL BE REQUIRED.
 PLEASE KNOW, THIS SYSTEM MAY ONLY BE
 INSTALLED BY A CERTIFIED LIGHTNING
 PROTECTION CONTRACTOR WHO CAN CERTIFY
 SUCH A SYSTEM UNDER UL 96 AND NFPA-780.
 THIS SHALL BE A SEPARATE PERMIT, WITH
 PLANS AND FEES.
 PLEASE KNOW HOWEVER A NOTE SHALL BE
 PLACE ON THESE ELECTRICAL PLANS ON ROOF
 TOP PLANS STATING; "ALL OR ANY LIGHTNING
 PROTECTION SYSTEMS SHALL BE INSTALLED
 PER NFPA-780 AND LISTED PER UL 96." THIS
 WORDING SHOULD BE TO THAT SAME AFFECT,
 BUT NOT REQUIRED TO BE STATED AS ABOVE.
 PLEASE KNOW, THIS AHJ DOES NOT ACCEPT
 ANY OTHER SYSTEM NOT ACCEPTED BY
 NFPA-780. PLEASE KNOW THERE ARE MANY
 SYSTEMS ON THE MARKET WHICH CLAIM TO
 "PREVENT" OR "DISSIPATE" LIGHTNING ETC
 WHICH ARE NOT PERMITTED.
  
 24) NOTE: PLEASE SEE 620.23 ABC AND
 620.24ABC FOR REQUIRED CIRCUITS AND
 CONTROLS.
 PLEASE SEE ALLCAN NOT BE VERIFIED AT
 THIS TIME.
  
 25) NOTE: PLEASE SEE 2004 FBC CHAPTER
 13.
 PLEASE SEE 13-413.1.ABC.1 FOR A WORST
 CASE SCENARIO TO BE PROVIDED FOR FEEDERS
 AND BRANCH CIRCUITS.
 PLEASE SEE 13-413.1.ABC.2.2.
 PLEASE SEE 13-415.1.ABC.1.1,
 13-415.1.ABC.1.2, 13-415.1.ABC.1.3 FOR
 LIGHTING AND CONTROLS FOR ALL AREAS.
 PLEASE SEE SOME EXCEPTIONS ARE
 PERMITTED.
 PLEASE SEE OUTSIDE AREAS , TANDEM WIRING
 ETC.
  
 26) NOTE: PLEASE SEE MINIMUM LIGHTING
 FOR EGRESS ETC WILL BE REQUIRED INSIDE
 THE FUTURE TENANT BUILD OUT SPACES. THIS
 HAS ALSO BEEN CONFIRMED ALSO WITH THE
 FIRE MARSHAL?S OFFICE AND WILL BE
 REQUIRED.
 THESE SHOULD BE WIRED INTO THE HOUSE
 PANELS AT THIS TIME AND CAN BE REMOVED
 ONCE TENANT OCCUPANCY TAKES PLACE.
 PLEASE ALSO SEE EXIT LIGHTS.
 IF THESE AREAS ARE OCCUPIED AT ANYTIME
 FOR ANY REASON BEFORE A BUILD OUT HAS
 TAKEN PLACE AND THE POWER GOES OUT,
 MINIMUM LIGHTING SHALL BE PROVIDED TO
 DIRECT ANY SAID OCCUPANTS TO THE EXIT.
 NFPA-101,7.8,7.9
  
 27) NOTE: PLEASE SEE PREVIOUS NOTES
 ABOVE WHICH REQUESTED THE MANUFACTURES
 SPEC/CUT SHEETS FOR THE FIRE PUMP AND
 FIRE PUMP CONTROLLER. PLEASE KNOW, THE
 PLANS SHALL INDICATE THE OCP AND LOCKED
 ROTOR OCP. PLEASE SEE RISER NOW SEEMS TO
 INDICATE THE FPC TO BE LISTED ETC.
 PLEASE KNOW, IF THE FCP MEETS NFPA-20
 FOR THE DISCONNECT MEANS RATED FOR THE
 LOAD SERVED LOCATE ON THE OUTSIDE OF THE
 EQUIPMENT AND CONTAINS THE OVER CURRENT
 PROTECTION SET AT LOCKED ROTOR AS
 REQUIRED BY 695.4B1 AND NFPA-20
 10.4.2,10.4.2.2, 10.3.6, 10.4.4 ETC.
 PLEASE SEE RISER SHOWS AN ADDITIONAL
 800A DISCONNECT LOCATED AHEAD OF THE
 LISTED FPC? PLEASE VERIFY AND CLARIFY
 THIS.
  
 28) NOTE: PLEASE SEE FUEL IS REQUIRED
 PER NFPA-20 FOR A MINIMUM OF 8HRS AT
 100% FOR FIRE PUMP AND ALL OTHER
 ASSOCIATED LOADS, INCLUDING ETC.
 6-6.2
 UNABLE TO VERIFY DUE TO THE AMOUNT OF
 FUEL TANKS, GPH ETC NOT SUBMITTED FOR
 REVIEW AT THIS TIME.
  
 29) NOTE: PLEASE NOTE ON PLANS AND
 PLEASE SEE NFPA-110 7.9, PARTICULARLY
 7.9.3.1 FOR FUEL LINE TYPES.
  
 30) NOTE: PLEASE SEE MANY LOCATIONS ON
 RISER BREAKERS FOR SHELL AND FUTURE ARE
 NOTED AS ELECTRICALLY OPERATED. PLEASE
 CLARIFY IF THESE BREAKERS STILL CONTAIN
 A MANUAL MEANS OF DISCONNECT?
  
 31) NOTE: PLEASE VERIFY "MI" CABLES
 BEING SHOWN ON PLANS AND RISER IN MANY
 LOCATIONS. PLEASE KNOW, THIS IS ONLY A
 NOTE AS THIS INSTALLATION FOR MI CABLE
 IS NOT COMMON FOR THIS TYPE OF CABLE.
 THIS IS PERMITTED AND IS IN NO WAY A
 NOTE FOR CORRECTION. THIS IS ONLY NOTED,
 AS IF SHOWN ON PLANS, THIS WILL BE
 REQUIRED AND IN LIEU OF REVISING PLANS
 AT A LATER DATE CHANGES CAN BE MADE IF
 THESE ARE NOT INTENDED.
 PLEASE INDICATE THE CABLE DEGREE
 RATINGS.
  
 32) NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTORS ARE BEING SHOWN FROM THE
 GENERATORS.
 250.30
  
 33) NOTE: PLEASE INDICATE THE OCP AT THE
 GENERATORS.
 215.5
  
 34) NOTE: PLEASE SEE 445.13 FOR MIN
 SIZES OF THE FEEDERS FROM THE
 GENERATORS.
  
 35) NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR THE BUILDING SERVICES
 AND PANELS.
 PLEASE SEE
 220,220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO INDICATE ALL CONTINUOUS
 LOADS AND LARGEST MOTOR LOADS AT 125%.
 215.3,230.42 ETC.
  
 36) NOTE: PLEASE INDICATE THE GUTTER
 SIZES ON RISER. THIS IS REQUIRED AT THIS
 TIME BASED ON THE MINIMUM DIMENSIONS
 REQUIRED FOR TURNING RADIUS AND BASED ON
 THE CONDUCTORS/FEEDERS ARE SHOWN ON
 RISER.
 368,215.5
  
 37) NOTE: PLEASE INDICATE AND SHOW ALL
 ATTACHMENT LOCATIONS FOR THE
 TRANSFORMERS AS SHOWN ON RISER. PLEASE
 SEE 250.50,250.30,250.66 ETC.
  
 38) NOTE: PLEASE PROVIDE A ONE-LINE
 GROUND RISER ON RISER DIAGRAM OR
 SEPARATE SHEET. 250.58, 215.5
  
 39) NOTE: PLEASE CORRELATE ALL OCP
 DEVICES FOR PANELS ON RISER AND PANELS
 SCHEDULE WHEN SUBMITTED. PLEASE SEE SOME
 OF THIS ON RISER DOES NOT CORRELATE AT
 THIS TIME WITH PANELS AS NOTED.
 215.5
  
 40) NOTE: PLEASE SEE 450.3 FOR THE
 MAXIMUM OCP FOR TRANSFORMERS TO BE AT
 125%. PLEASE KNOW, WHEN THE OCP DOES NOT
 CORRELATE, AND THEN IT IS PERMITTED TO
 GO TO THE NEXT SIZE UP, HOWEVER IT IS
 NOT PERMITTED TO GO MORE THAN THE
 STANDARDS OCP PROTECTION DEVICES AS
 LISTED IN 240.6.
 PLEASE SEE TRANSFORMERS WHICH INDICATE
 THE OCP SET HIGHER THAN THE MAX 125%.
 215.5
  
 41) NOTE: PLEASE PROVIDE ANY WIND
 LOADING ON LIGHT POLES OUTSIDE. PLEASE
 KNOW, THE RATINGS SHALL BE BASED ON FBC
 2004 140MPH. THESE CALCULATIONS WILL BE
 REVIEWED BY THE STRUCTURAL REVIEWER WHEN
 SUBMITTED.
  
 42) NOTE: PLEASE KNOW, IT WAS NOTED THAT
 THE RISER DIAGRAM SHEET CONTAINED A
 NOTED FOR SIGNAGE PER 230.2E. PLEASE
 KNOW HOWEVER SIGNAGE, MAPPING SHALL BE
 REQUIRED AT ALL OTHER LOCATIONS; HOWEVER
 MOST IMPORTANTLY BE REQUIRED IN FULL IN
 THE FIRE COMMAND RM.
 PLEASE PROVIDE A NOTE FOR THE SIGNAGE ON
 THE SHEET FOR THE FC ROOM. PLEASE NOTE
 THAT ALL LETTERING SHALL BE A MINIMUM OF
 1" AND ON CONTRASTING BACKGROUND.
  
 43) NOTE: PLEASE SEE NFPA-72 4.4.1.4.2.2
 FOR THE REQUIRED DISCONNECTING MEANS FOR
 THE PRIMARY OF THE FIRE ALARM SYSTEM.
 PLEASE ALSO BE SURE ALL ITEMS ARE LISTED
 ON PLANS FOR THE FIRE COMMAND ROOM AS
 SET FORTH IN NFPA-10111.8, 11.8.5
  
 44) NOTE: PLEASE KNOW MANY OF THE ABOVE
 ITEMS HAVE BEEN REDLINED ON ONE OF THE
 SETS OF SUBMITTED PLANS BUT IS IN NO WAY
 ALL POSSIBLE ITEMS AS MENTIONED ABOVE.
  
 45) NOTE: PLEASE SEE THAT A TYPE WRITTEN
 RESPONSE FROM THE DESIGN TEAM FOR EACH
 OF THE ABOVE COMMENTS WILL HELP IN
 EXPEDITING THE NEXT REVIEW PROCESS.
  
 PLEASE BE SURE TO ALL SEE ALL COMMENTS
 FROM ALL OTHER TRADES AND THEY MAY
 AFFECT ELECTRICAL PLANS AND DESIGN.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS OR
 COMMENTS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
2006-06-05 00:00:00REVIEW IN PROGRESS
2006-06-02 00:00:00ONE ROLL OF PLANS AND ONE SET OF BOOKS
 IN ELECTRICAL FOR REVIEW.