| Date |
Text |
| 2006-06-06 00:00:00 | |
| | ***************UNSAT *************** |
| | |
| | CITY PLACE OFFICE TOWER |
| | 525 OKEECHOBEE BLVD. |
| | |
| | |
| | |
| | *** PLEASE KNOW PLANS AND SUBMITTED |
| | PAPER WORK IS NOT COMPLETE AT THIS TIME |
| | FOR A COMPLETE AND SUFFICIENT REVIEW. |
| | PLEASE KNOW THERE MAY BE FURTHER |
| | COMMENTS ONCE ALL INFORMATION IS |
| | SUBMITTED. |
| | |
| | 1) NOTE: PLEASE KNOW, BEFORE |
| | RE-SUBMITTING PLANS. PLEASE COMPLETELY |
| | REMOVE ALL OLD/VOIDED SHEETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETED |
| | SETS FOR REVIEW AND STAMPING. PLEASE |
| | KNOW SINCE MANY OF THE COMMENTS BELOW |
| | AFFECT ALL OF THE SHEETS IN THE SETS, |
| | ONLY ONE ROLL OF OLD SETS SHOULD BE |
| | SUBMITTED FOR REFERENCE WHEN PLANS ARE |
| | BROUGHT BACK. THESE SHOULD BE LABELED |
| | "OLD/VOIDED". |
| | |
| | 2) NOTE: PLEASE SEE MISSING INFORMATION |
| | ON MANY OF THE TITLE BLOCKS ON PLANS. |
| | PLEASE SEE MISSING FIRM LICENSE NUMBERS |
| | WHICH ARE THE CERTIFICATE OF |
| | AUTHORIZATION NUMBERS FOR MORE THAN ONE |
| | FIRM. PLEASE SEE LANDSCAPE AND MEP |
| | ENGINEERING FIRMS. PLEASE ALSO SEE MANY |
| | SHEETS ARE MISSING THE PRINTED NAME AND |
| | LICENSE NUMBER FOR THE PERSON SIGNING |
| | AND SEALING SAID DOCUMENTS. |
| | PLEASE SEE THE FLORIDA ADMINISTRATIVE |
| | CODE 61G1-16.004 AND 61G15-23.002. |
| | FLORIDA STATUES 471.023, 481.219 |
| | |
| | 3) NOTE: PLEASE SEE OTHER SHEETS WHICH |
| | CONTAIN A "STAMP" FOR THE REQUIRED |
| | "ORIGINAL" SIGNATURE BY THE DESIGN |
| | PROFESSIONAL. PLEASE SEE "S" SHEETS. |
| | FLORIDA STATUES 471.025 |
| | PLEASE ALSO SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH RESPECT TO THE SEAL |
| | CONTAINING THE WORDING OF "CERTIFICATE" |
| | WHICH IS NOT LONGER ACCEPTED. |
| | FAC 61G1-16.001 |
| | |
| | 4) NOTE: PLEASE SEE PLANS SHALL CONTAIN |
| | THE FOLLOWING MIN CODES REFERENCED AND |
| | LISTED ON PLANS FOR DESIGN. |
| | THE ARCHITECTURAL LISTS THE 2004 FBC. |
| | PLEASE LIST: |
| | 2002 NFPA-70 NATIONAL ELECTRICAL CODE |
| | 2003 NFPA-101 LIFE SAFETY CODE |
| | 2003 NFPA-20 FIRE PUMPS |
| | 2002 NFPA-110 EMERGENCY AND. |
| | STANDBY POWER SYSTEMS. |
| | NFPA-72 2002 |
| | THESE ARE REQUIRED AT A MIN. |
| | |
| | 5) NOTE: PLEASE SUBMIT ALL MANUFACTURES |
| | SPECS/CUT SHEETS FOR THE FOLLOWING. |
| | GENERATOR(S), ATS SWITCHES, FIRE PUMP, |
| | FIRE PUMP CONTROLLER, FUEL TANK, |
| | PARALLELING SWITCH GEAR AND OTHER |
| | ASSOCIATE SWITCHGEAR. |
| | PLEASE KNOW, NONE OF THESE WERE |
| | SUBMITTED AND UNABLE TO VERIFY MANY |
| | ITEMS FOR CODE COMPLIANCE AT THIS TIME. |
| | PLEASE BE SURE ALL EQUIPMENT SHEETS |
| | /SPECS CONTAIN LISTINGS FROM A NRTL. |
| | |
| | 6) NOTE: PLEASE SEE PLANS SEEM TO |
| | INDICATE THE 2000KW GENERATORS LOCATED |
| | ON A SEPARATE PROPERTY. PLEASE KNOW, |
| | PROPERTY LINES MAY CHANGE, SEPARATE |
| | PERMIT MAY BE REQUIRED ALSO IF INDEED |
| | THESE ARE ON SEPARATE PROPERTIES. THERE |
| | MAY ALSO BE THE POSSIBILITY OF EASEMENTS |
| | WHICH MAY NEED TO BE GRANTED. |
| | PLEASE ALSO SEE THE ELEVATOR TOWER BEING |
| | CONSTRUCTED NEXT TO THE PARKING GARAGE |
| | ALSO SEEM TO BE ON A SEPARATE LEGAL |
| | PROPERTY BEING FED FROM THE MAIN TOWER. |
| | PLEASE KNOW THIS MAY NOT BE POSSIBLE |
| | DEPENDING ON THE OUTCOME OR CHANGES IN |
| | PROPERTY LINES ETC. |
| | PLEASE SEE THE PROPOSED WORK IN CORRIDOR |
| | LOCATED AT THE "B" BLOCK GARAGE |
| | STRUCTURE WILL BE REQUIRED UNDER A |
| | SEPARATE PERMIT. |
| | ** PLEASE ALSO SEE BUILDING REVIEW |
| | COMMENTS FOR ABOVE AS MANY OF THESE |
| | ITEMS ARE TO BE PLACED IN BUILDING |
| | REVIEW AND MAY AFFECT PLANS SUBMITTED. |
| | |
| | 7) NOTE: PLEASE CLARIFY USE AND |
| | EQUIPMENT IN THE CATERING ROOM AS STATED |
| | ON 6TH FLOOR. PLEASE LIST ALL 15/20AMP |
| | 120V RECEPTS AS GFI/GFI PROTECTED AS PER |
| | 210.8B3. |
| | (KITCHENS IN OTHER THAN DWELLING UNITS) |
| | |
| | 8) NOTE: PLEASE SEE GATES ARE INDICATED |
| | AT TWO DIFFERENT LOCATIONS, HOWEVER |
| | ELECTRICAL TO THESE DO NOT SEEM TO BE |
| | COMPLETE AT THIS TIME. |
| | PLEASE PROVIDE INFORMATION FOR ACCESS |
| | AND EGRESS IN THE EVENT OF POWER FAILURE |
| | AND/OR OVER RIDE FOR THESE. PLEASE SEE |
| | FIRE REVIEW COMMENTS AS THIS MAY BE IN |
| | QUESTION. |
| | |
| | 8) NOTE: PLEASE SUBMIT COMPLETED PANEL |
| | SCHEDULES FOR ALL PANELS. THE PANELS ARE |
| | INDICATED ON E3.03 ARE NOT SUFFICIENT |
| | FOR REVIEW OF ALL SAID ELECTRICAL BRANCH |
| | CIRCUITS FOR OVERCURRENT PROTECTION, |
| | CONDUCTOR SIZES ETC. |
| | 215.5 |
| | MANY ITEMS CAN NOT BE REVIEWED AT THIS |
| | TIME. |
| | AN EQUIPMENT SCHEDULE AS SUBMITTED IS |
| | OK, HOWEVER THESE ITEMS SHOULD BE LISTED |
| | ON PANEL SCHEDULES TO BE SUBMITTED. |
| | |
| | 9) NOTE: PLEASE COMPLETE ALL THE |
| | CIRCUITING AND SWITCH LEGS ON PLANS AND |
| | LAYOUTS. PLEASE SEE MANY AREAS ARE LEFT |
| | TO FIGURE WHERE THESE DEVICES, OUTLETS, |
| | OR LIGHTING OUTLETS ARE BEING FED FROM |
| | AND/OR CONTROLLED. |
| | PLEASE CORRELATE WITH PANEL SCHEDULES TO |
| | BE SUBMITTED. |
| | 215.5 |
| | |
| | 10) NOTE: PLEASE CORRELATE ARCHITECTURAL |
| | PLANS WITH ELECTRICAL. PLEASE SEE FLOORS |
| | 6-14 ARE SHOWN CONTAINING A CORRIDOR TO |
| | MAIN ELECTRICAL ROOM ON EACH OF THESE |
| | FLOORS ON ELECTRICAL PLANS, HOWEVER |
| | ARCH DO NOT SHOW THESE CORRIDORS OF |
| | COMMON AREAS.? |
| | PLEASE SEE FLOORS 15 AND 16 ON BOTH A |
| | AND E?S DO NOT SHOW ANY CORRIDORS AND |
| | OBTAININGACCESS TO THE ELECTRICAL ROOM |
| | ON EACH OF THOSE FLOORS ARE ONLY THROUGH |
| | THE PROPOSED FUTURE TENANT SPACE. PLEASE |
| | KNOW IT IS NOT KNOWN AT THIS TIME IF |
| | THERE WILL BE ONE, TWO THREE OR MORE |
| | TENANTS ON EACH FLOOR AND ACCESS TO EACH |
| | TENANT'S ELECTRICAL PANEL(S) AND OVER |
| | CURRENT PROTECTION DEVICES MAY NOT BE |
| | THROUGH TENANT OCCUPANCY. PLEASE ALSO |
| | KNOW THE HOUSE POWER/COMMON AREAS MAY |
| | ALSO NOT BE ACCESSED THROUGH THE |
| | TENANT'S SPACE. |
| | PLEASE KNOW, EACH CORRIDOR AS SHOWN ON |
| | FLOORS 6-14 SHALL BE THE SAME ON ALL |
| | FLOORS AND SHOULD CORRELATE AS THE SAME |
| | ON ARCHITECTURAL SHEETS. |
| | 210.25, 215.5, 240.24 |
| | |
| | 11) NOTE: PLEASE PROVIDE EXIT/EGRESS |
| | LIGHTING TO THE PUBLIC RIGHT OF WAY. |
| | PLEASE SEE THE PUBLIC RIGHT OF WAY IS |
| | NOT DIRECTLY OUTSIDE THE STAIR #2 DOOR |
| | AND THE PUBLIC RIGHT OF WAY SEEMS TO BE |
| | LOCATED AROUND THE FRONT OF THE |
| | BUILDING. PLEASE SEE BUILDING REVIEW |
| | NOTES FOR EXIT CORRIDOR FOR STAIR #2. |
| | PLEASE SEE PLANS REDLINED FOR POSSIBLE |
| | CHANGE WHICH MAY BE OPTED FOR. |
| | NFPA-101 7.8, 7.9. |
| | |
| | 12) NOTE: PLEASE SEE CONDUITS AND |
| | FEEDERS FROM ATS #1 AND ATS #2 ARE BEING |
| | NOTED AS INSTALLED IN RATED EXIT |
| | CORRIDOR. |
| | PLEASE SEE THESE CONDUITS MAY NOT BE |
| | LOCATED AS SHOWN ON PLANS. |
| | THIS IS NOT SHOWN ON ARCHITECTURAL |
| | SHEETS AND THIS INFORMATION WAS GIVEN TO |
| | THE BUILDING REVIEWER. PLEASE SEE |
| | BUILDING NOTES. |
| | |
| | 13) NOTE: PLEASE CLARIFY ALL MAINS AND |
| | DISTRIBUTION EQUIPMENT CONTAINING ALL |
| | MAINS, GROUPING ETC PER 230.70, 230.72, |
| | 230.76, 230.79, AND 225.31-225.39 |
| | PLEASE KNOW, DUE TO THE INFORMATION OF |
| | THE SWITCH GEAR NOT SUBMITTED, SHOWN AND |
| | WHETHER OR NOT THESE CONTAIN MAINS, WITH |
| | MANUAL MEANS OF DISCONNECT LOCATED ON |
| | THE OUTSIDE OF THE EQUIPMENT, GROUPED |
| | ETC. THE LOCATIONS OF SOME SERVICE |
| | EQUIPMENT CAN NOT REVIEWED FOR LOCATIONS |
| | AT THIS TIME. |
| | |
| | 14) NOTE: PLEASE SEE THE EMERGENCY |
| | SYSTEMS ARE BEING SHOWN IN THE SAME |
| | EQUIPMENT AS THE NORMAL MAINS. PLEASE |
| | KNOW, THESE SHALL NOT BE LOCATED IN THE |
| | SAME EQUIPMENT AND SERVED BY THE SAME |
| | SERVICE. |
| | PLEASE REVISE SERVICE AS SHOWN. |
| | 701.1, NFPA-110 CHAPTER 7 ETC |
| | |
| | 15) NOTE: PLEASE SEE SOME AREAS AT THE |
| | EXIT TO THE STAIRS IN THE PARKING |
| | GARAGES WILL BE REQUIRED TO CONTAIN A |
| | BATTERY BACK UP FIXTURE OF SOME SORT |
| | DEPENDING ON THE OPERATION OF THE |
| | STAND-BY GENERATORS. PLEASE CLARIFY IF |
| | ORDER OF OPERATION OF THE GENERATORS AS |
| | WILL BE SO THAT OF THE SINGLE OCP AT THE |
| | 800KW GEN TRIPS THE OTHER TWO STAND-BY |
| | GEN?S WILL COME ONLINE? |
| | PLEASE SEE 7.9.2.2 |
| | |
| | 16) NOTE: PLEASE A KNOW, A BATTERY BACK |
| | UP LT FIXTURE WILL BE REQUIRED IN MAIN |
| | ELECTRICAL ROOM(S), MAIN ELECTRICAL RM |
| | ON 5TH FLR, ELEVATOR EQUIPMENT ROOMS, |
| | FIRE PUMP ROOM, FIRE COMMAND ROOMAND |
| | GEN ROOM. PLEASE KNOW SOME OF THESE ARE |
| | SHOWN ALREADY AND DO NOT NEED TO BE |
| | ADDED, HOWEVER SOME ARE NOT. |
| | 700.16,7.8.1.3,7.9.2.2 700.22 ETC. |
| | |
| | 17) NOTE: PLEASE SEE SOME ELECTRICAL |
| | ROOMS DOORS SEEM TO SWING INTO EITHER |
| | ELECTRICAL EQUIPMENT OR OTHER EQUIPMENT |
| | SHOWN ON PLANS. |
| | PLEASE SEE DOOR SWINGS ON SOME DOORS |
| | WILL BE REQUIRED TO SWING OUT (5TH FLOOR |
| | MAIN RM) . |
| | PLEASE SEE SOME ROOMS APPEAR TO SHOW |
| | EQUIPMENTIN THE MIN CLEARANCE AREAS |
| | REQUIRED PER 110.26. |
| | PLEASE ALSO PLACE NOTES ON PLANS AT |
| | LOCATION FOR MAIN ELECTRICAL ROOMS THAT |
| | ALL DOORS SHALL BE EQUIPMENT WITH SUCH |
| | ACCEPTED PANIC HARDWARE AND OPEN ON THE |
| | MEANS OF EGRESS WITH OUT ANY TRIPPING |
| | HAZARDS. |
| | PLEASE KNOW THIS WILL AFFECT DOOR |
| | SCHEDULE ON ARCHITECTURAL PLANS AND |
| | POSSIBLE DOOR SWINGS ON A SHEETS AS NOW |
| | SHOWN. |
| | |
| | 18) NOTE: PLEASE PROVIDE THE ELEVATION |
| | OF THE EM DISTRIBUTION SYSTEM AND |
| | EQUIPMENT. |
| | PLEASE SEE NFPA-110 7.2.3* WHICH |
| | REQUIRES THE ELEVATION TO MEET THE |
| | "SLOSH" PREDICTION LEVELS BASED ON A |
| | CATEGORY 4 STORM. |
| | THE ELEVATION FOR PROPERTY SHOULD BE OK, |
| | HOWEVER THIS ELEVATION IS REQUIRED TO BE |
| | STATED ON PLANS AND VERIFICATION THAT |
| | ALL REQUIRED EMERGENCY SYSTEMS ARE |
| | ABOVE. |
| | PLEASE SEE THAT "SLOSH", MEANS SEA, |
| | LAKE, OVERLAND, SURGES BY HURRICANES. |
| | |
| | 19) NOTE: PLEASE COMPLETE FIXTURE |
| | SCHEDULES AND PLEASE CORRELATE ALL |
| | FIXTURES AS SHOWN ON PLANS WITH THE |
| | FIXTURES SCHEDULES SUBMITTED. |
| | 215.5 |
| | |
| | 20) NOTE: PLEASE SEE RISER IS SHOWING |
| | GFI PROTECTION FOR SOME MAINS??? |
| | PLEASE SEE GF (GROUND FAULT) PROTECTION |
| | IS REQUIRED PER 240.13, 230.95 ETC , |
| | HOWEVER PLEASE SEE GFI PROTECTION IS |
| | PERSONNEL PROTECTION. |
| | PLEASE SEE PROTECTION IS ALSO BEING |
| | SHOWN ON ALL SECONDARY OVER CURRENT |
| | PROTECTION?? |
| | PLEASE KNOW, THIS IS NOT REQUIRED FOR |
| | THIS STRUCTURE, CLASS AND OCCUPANCY, BUT |
| | HOWEVER IS PERMITTED. |
| | PLEASE ALSO SEE GF SEEMS TO BE SHOWN ON |
| | THE EM SIDE OF THE DISTRIBUTION |
| | SYSTEM(S) WHICH IS UNCLEAR. PLEASE SEE |
| | 700.7D, 700.26, NFPA-110 |
| | PLEASE SEE THE CODE IS CLEAR WHEN GROUND |
| | FAULT PROTECTION IS REQUIRED AND WHEN |
| | SENSING OF SUCH GROUND FAULTS ARE |
| | REQUIRED , HOWEVER PLEASE KNOW GROUND |
| | FAULT PROTECTION IS NOT IDEALON THE |
| | EMERGENCY SIDE DUE TO THE NATURE OF THE |
| | EMERGENCY DISTRIBUTIONSYSTEM AND THE |
| | NEED OF MAINTAINING CERTAIN SYSTEMS ON |
| | DURING AN EMERGENCY.PLEASE KNOW, |
| | SENSING OF THE GROUND FAULT WOULD BE |
| | NEEDED TO CORRECT ANY SITUATION IN SUCH |
| | EQUIPMENT. PLEASE KNOW, IT HAS BEEN |
| | DETERMINED BY THIS AHJ, THAT THE GF |
| | PROTECTION ON THE REQUIRED EM SYSTEMS |
| | SHOULD NOT BE PROVIDED AND ONLY SENSING |
| | FOR THE PURPOSE AS STATED AND REQUIRED. |
| | |
| | 21) NOTE: PLEASE KNOW, 4-POLE ATS |
| | SWITCHES ARE BEING SHOWN AS REQUIRED TO |
| | ACHIEVE THE CORRECT GROUND FAULT |
| | SENSING, HOWEVER THE GENERATORS DO NOT |
| | SEEM TO BE INDICATED A SEPARATELY |
| | DERIVED AS REQUIRED. |
| | 250.30, 250.50. |
| | |
| | 22) NOTE: PLEASE SEE THE GROUNDING |
| | ELECTRODE SYSTEM IS REQUIRED TO SHOW THE |
| | FOOTER/FOUNDATION STEEL AS PART OF THE |
| | GROUNDING ELECTRICAL SYSTEM. |
| | 250.50 |
| | |
| | 23) NOTE: PLEASE SEE A NOTE ON PLANS |
| | MENTIONS THAT A LIGHTNING PROTECTION |
| | SYSTEM WILL BE REQUIRED. |
| | PLEASE KNOW, THIS SYSTEM MAY ONLY BE |
| | INSTALLED BY A CERTIFIED LIGHTNING |
| | PROTECTION CONTRACTOR WHO CAN CERTIFY |
| | SUCH A SYSTEM UNDER UL 96 AND NFPA-780. |
| | THIS SHALL BE A SEPARATE PERMIT, WITH |
| | PLANS AND FEES. |
| | PLEASE KNOW HOWEVER A NOTE SHALL BE |
| | PLACE ON THESE ELECTRICAL PLANS ON ROOF |
| | TOP PLANS STATING; "ALL OR ANY LIGHTNING |
| | PROTECTION SYSTEMS SHALL BE INSTALLED |
| | PER NFPA-780 AND LISTED PER UL 96." THIS |
| | WORDING SHOULD BE TO THAT SAME AFFECT, |
| | BUT NOT REQUIRED TO BE STATED AS ABOVE. |
| | PLEASE KNOW, THIS AHJ DOES NOT ACCEPT |
| | ANY OTHER SYSTEM NOT ACCEPTED BY |
| | NFPA-780. PLEASE KNOW THERE ARE MANY |
| | SYSTEMS ON THE MARKET WHICH CLAIM TO |
| | "PREVENT" OR "DISSIPATE" LIGHTNING ETC |
| | WHICH ARE NOT PERMITTED. |
| | |
| | 24) NOTE: PLEASE SEE 620.23 ABC AND |
| | 620.24ABC FOR REQUIRED CIRCUITS AND |
| | CONTROLS. |
| | PLEASE SEE ALLCAN NOT BE VERIFIED AT |
| | THIS TIME. |
| | |
| | 25) NOTE: PLEASE SEE 2004 FBC CHAPTER |
| | 13. |
| | PLEASE SEE 13-413.1.ABC.1 FOR A WORST |
| | CASE SCENARIO TO BE PROVIDED FOR FEEDERS |
| | AND BRANCH CIRCUITS. |
| | PLEASE SEE 13-413.1.ABC.2.2. |
| | PLEASE SEE 13-415.1.ABC.1.1, |
| | 13-415.1.ABC.1.2, 13-415.1.ABC.1.3 FOR |
| | LIGHTING AND CONTROLS FOR ALL AREAS. |
| | PLEASE SEE SOME EXCEPTIONS ARE |
| | PERMITTED. |
| | PLEASE SEE OUTSIDE AREAS , TANDEM WIRING |
| | ETC. |
| | |
| | 26) NOTE: PLEASE SEE MINIMUM LIGHTING |
| | FOR EGRESS ETC WILL BE REQUIRED INSIDE |
| | THE FUTURE TENANT BUILD OUT SPACES. THIS |
| | HAS ALSO BEEN CONFIRMED ALSO WITH THE |
| | FIRE MARSHAL?S OFFICE AND WILL BE |
| | REQUIRED. |
| | THESE SHOULD BE WIRED INTO THE HOUSE |
| | PANELS AT THIS TIME AND CAN BE REMOVED |
| | ONCE TENANT OCCUPANCY TAKES PLACE. |
| | PLEASE ALSO SEE EXIT LIGHTS. |
| | IF THESE AREAS ARE OCCUPIED AT ANYTIME |
| | FOR ANY REASON BEFORE A BUILD OUT HAS |
| | TAKEN PLACE AND THE POWER GOES OUT, |
| | MINIMUM LIGHTING SHALL BE PROVIDED TO |
| | DIRECT ANY SAID OCCUPANTS TO THE EXIT. |
| | NFPA-101,7.8,7.9 |
| | |
| | 27) NOTE: PLEASE SEE PREVIOUS NOTES |
| | ABOVE WHICH REQUESTED THE MANUFACTURES |
| | SPEC/CUT SHEETS FOR THE FIRE PUMP AND |
| | FIRE PUMP CONTROLLER. PLEASE KNOW, THE |
| | PLANS SHALL INDICATE THE OCP AND LOCKED |
| | ROTOR OCP. PLEASE SEE RISER NOW SEEMS TO |
| | INDICATE THE FPC TO BE LISTED ETC. |
| | PLEASE KNOW, IF THE FCP MEETS NFPA-20 |
| | FOR THE DISCONNECT MEANS RATED FOR THE |
| | LOAD SERVED LOCATE ON THE OUTSIDE OF THE |
| | EQUIPMENT AND CONTAINS THE OVER CURRENT |
| | PROTECTION SET AT LOCKED ROTOR AS |
| | REQUIRED BY 695.4B1 AND NFPA-20 |
| | 10.4.2,10.4.2.2, 10.3.6, 10.4.4 ETC. |
| | PLEASE SEE RISER SHOWS AN ADDITIONAL |
| | 800A DISCONNECT LOCATED AHEAD OF THE |
| | LISTED FPC? PLEASE VERIFY AND CLARIFY |
| | THIS. |
| | |
| | 28) NOTE: PLEASE SEE FUEL IS REQUIRED |
| | PER NFPA-20 FOR A MINIMUM OF 8HRS AT |
| | 100% FOR FIRE PUMP AND ALL OTHER |
| | ASSOCIATED LOADS, INCLUDING ETC. |
| | 6-6.2 |
| | UNABLE TO VERIFY DUE TO THE AMOUNT OF |
| | FUEL TANKS, GPH ETC NOT SUBMITTED FOR |
| | REVIEW AT THIS TIME. |
| | |
| | 29) NOTE: PLEASE NOTE ON PLANS AND |
| | PLEASE SEE NFPA-110 7.9, PARTICULARLY |
| | 7.9.3.1 FOR FUEL LINE TYPES. |
| | |
| | 30) NOTE: PLEASE SEE MANY LOCATIONS ON |
| | RISER BREAKERS FOR SHELL AND FUTURE ARE |
| | NOTED AS ELECTRICALLY OPERATED. PLEASE |
| | CLARIFY IF THESE BREAKERS STILL CONTAIN |
| | A MANUAL MEANS OF DISCONNECT? |
| | |
| | 31) NOTE: PLEASE VERIFY "MI" CABLES |
| | BEING SHOWN ON PLANS AND RISER IN MANY |
| | LOCATIONS. PLEASE KNOW, THIS IS ONLY A |
| | NOTE AS THIS INSTALLATION FOR MI CABLE |
| | IS NOT COMMON FOR THIS TYPE OF CABLE. |
| | THIS IS PERMITTED AND IS IN NO WAY A |
| | NOTE FOR CORRECTION. THIS IS ONLY NOTED, |
| | AS IF SHOWN ON PLANS, THIS WILL BE |
| | REQUIRED AND IN LIEU OF REVISING PLANS |
| | AT A LATER DATE CHANGES CAN BE MADE IF |
| | THESE ARE NOT INTENDED. |
| | PLEASE INDICATE THE CABLE DEGREE |
| | RATINGS. |
| | |
| | 32) NOTE: PLEASE SEE EQUIPMENT GROUNDING |
| | CONDUCTORS ARE BEING SHOWN FROM THE |
| | GENERATORS. |
| | 250.30 |
| | |
| | 33) NOTE: PLEASE INDICATE THE OCP AT THE |
| | GENERATORS. |
| | 215.5 |
| | |
| | 34) NOTE: PLEASE SEE 445.13 FOR MIN |
| | SIZES OF THE FEEDERS FROM THE |
| | GENERATORS. |
| | |
| | 35) NOTE: PLEASE SUBMIT COMPLETE LOAD |
| | CALCULATIONS FOR THE BUILDING SERVICES |
| | AND PANELS. |
| | PLEASE SEE |
| | 220,220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO INDICATE ALL CONTINUOUS |
| | LOADS AND LARGEST MOTOR LOADS AT 125%. |
| | 215.3,230.42 ETC. |
| | |
| | 36) NOTE: PLEASE INDICATE THE GUTTER |
| | SIZES ON RISER. THIS IS REQUIRED AT THIS |
| | TIME BASED ON THE MINIMUM DIMENSIONS |
| | REQUIRED FOR TURNING RADIUS AND BASED ON |
| | THE CONDUCTORS/FEEDERS ARE SHOWN ON |
| | RISER. |
| | 368,215.5 |
| | |
| | 37) NOTE: PLEASE INDICATE AND SHOW ALL |
| | ATTACHMENT LOCATIONS FOR THE |
| | TRANSFORMERS AS SHOWN ON RISER. PLEASE |
| | SEE 250.50,250.30,250.66 ETC. |
| | |
| | 38) NOTE: PLEASE PROVIDE A ONE-LINE |
| | GROUND RISER ON RISER DIAGRAM OR |
| | SEPARATE SHEET. 250.58, 215.5 |
| | |
| | 39) NOTE: PLEASE CORRELATE ALL OCP |
| | DEVICES FOR PANELS ON RISER AND PANELS |
| | SCHEDULE WHEN SUBMITTED. PLEASE SEE SOME |
| | OF THIS ON RISER DOES NOT CORRELATE AT |
| | THIS TIME WITH PANELS AS NOTED. |
| | 215.5 |
| | |
| | 40) NOTE: PLEASE SEE 450.3 FOR THE |
| | MAXIMUM OCP FOR TRANSFORMERS TO BE AT |
| | 125%. PLEASE KNOW, WHEN THE OCP DOES NOT |
| | CORRELATE, AND THEN IT IS PERMITTED TO |
| | GO TO THE NEXT SIZE UP, HOWEVER IT IS |
| | NOT PERMITTED TO GO MORE THAN THE |
| | STANDARDS OCP PROTECTION DEVICES AS |
| | LISTED IN 240.6. |
| | PLEASE SEE TRANSFORMERS WHICH INDICATE |
| | THE OCP SET HIGHER THAN THE MAX 125%. |
| | 215.5 |
| | |
| | 41) NOTE: PLEASE PROVIDE ANY WIND |
| | LOADING ON LIGHT POLES OUTSIDE. PLEASE |
| | KNOW, THE RATINGS SHALL BE BASED ON FBC |
| | 2004 140MPH. THESE CALCULATIONS WILL BE |
| | REVIEWED BY THE STRUCTURAL REVIEWER WHEN |
| | SUBMITTED. |
| | |
| | 42) NOTE: PLEASE KNOW, IT WAS NOTED THAT |
| | THE RISER DIAGRAM SHEET CONTAINED A |
| | NOTED FOR SIGNAGE PER 230.2E. PLEASE |
| | KNOW HOWEVER SIGNAGE, MAPPING SHALL BE |
| | REQUIRED AT ALL OTHER LOCATIONS; HOWEVER |
| | MOST IMPORTANTLY BE REQUIRED IN FULL IN |
| | THE FIRE COMMAND RM. |
| | PLEASE PROVIDE A NOTE FOR THE SIGNAGE ON |
| | THE SHEET FOR THE FC ROOM. PLEASE NOTE |
| | THAT ALL LETTERING SHALL BE A MINIMUM OF |
| | 1" AND ON CONTRASTING BACKGROUND. |
| | |
| | 43) NOTE: PLEASE SEE NFPA-72 4.4.1.4.2.2 |
| | FOR THE REQUIRED DISCONNECTING MEANS FOR |
| | THE PRIMARY OF THE FIRE ALARM SYSTEM. |
| | PLEASE ALSO BE SURE ALL ITEMS ARE LISTED |
| | ON PLANS FOR THE FIRE COMMAND ROOM AS |
| | SET FORTH IN NFPA-10111.8, 11.8.5 |
| | |
| | 44) NOTE: PLEASE KNOW MANY OF THE ABOVE |
| | ITEMS HAVE BEEN REDLINED ON ONE OF THE |
| | SETS OF SUBMITTED PLANS BUT IS IN NO WAY |
| | ALL POSSIBLE ITEMS AS MENTIONED ABOVE. |
| | |
| | 45) NOTE: PLEASE SEE THAT A TYPE WRITTEN |
| | RESPONSE FROM THE DESIGN TEAM FOR EACH |
| | OF THE ABOVE COMMENTS WILL HELP IN |
| | EXPEDITING THE NEXT REVIEW PROCESS. |
| | |
| | PLEASE BE SURE TO ALL SEE ALL COMMENTS |
| | FROM ALL OTHER TRADES AND THEY MAY |
| | AFFECT ELECTRICAL PLANS AND DESIGN. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| 2006-06-05 00:00:00 | REVIEW IN PROGRESS |
| 2006-06-02 00:00:00 | ONE ROLL OF PLANS AND ONE SET OF BOOKS |
| | IN ELECTRICAL FOR REVIEW. |