Plan Review Notes
Plan Review Notes For Permit 06040957
Permit Number 06040957
Review Stop B
Sequence Number 1
Notes
Date Text
2006-06-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06040957
 ADD: 525 OKEECHOBEE BLVD
 CONT: CENTEX CONSTRUCTION
 TEL: (954)214-9415
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ---CITY PLACE OFFICE TOWER---
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) LANDSCAPE PLANS ARE MISSING THE
 SIGNATURE, DATE AND RAISED SEAL.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 3)LANDSCAPE ARCHITECT DSBOCA IS MISSING:
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 4) ROBERT J. MCNAMARA PE SEAL INDICATES
 THE WORD "CERTIFICATE" SEE:
 RULE 61G155-23.001(1) F.A.C.
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS HAS CLEANED UP THE APPEARENCE
 OF THE SEAL BY ELIMINATING OBSOLETE
 CONTENT AND CHANGING THE WORD
 "CERTIFICATE" TO "LICENSE". A GRACE
 PERIOD RAN THROUGH DEC. 31,2005.
  
 5) ROBERT J. MCNAMARA PE SIGNATURE IS A
 COPY OR STAMP.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
  
 6) COMMENT# 5 OF FOUNDATION PERMIT,
 BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) COMMENT# 7 FROM FOUNDATION PERMIT,
 WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
  
 8) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S,
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 9) DISCREPANCY BETWEEN THE SKETCH OF
 SURVEY AND THE TAX MAPS AS FAR AS THE
 PROPERTY LINE. TAX MAPS INDICATE LOT 2
 ACTUALLY WRAPPING AROUND THE WEST SIDE
 OF THE "B BLOCK PARKING GARAGE" AND A
 3'-0" SEPERATION BETWEEN THE EXISTING
 PARKING GARAGE AND LOT# 2 JUST TO THE
 SOUTH OF PARKING GARAGE. SUBMIT NOT A
 SCKETH BUT AN ACTUAL SURVEY OF THE
 PROPERTY LINE.
  
 10A) DEPENDING ON THE LOCATION OF THE
 NORTH PROPERTY LINE (SURVEY) TWO PERMIT APPLICATIONS,
 PERMITS AND ASSOCIATED
 FEES, MAY BE NECESSARY. IT APPEARS THAT
 THE ELEVATOR WHICH IS AN ADDITION TO THE
 FIVE STORY PARKING GARAGE AND THE
 GENERATOR JUST TO THE WEST OF THE
 PARKING GARAGE ARE LOCATED ON ANOTHER
 PROPERTY.
  
 10B) ADDITIONAL INFORMATION REQUIRED, IT
 APPEARS THERE ARE (3) GENERATORS, ONE
 LOCATED IN THE NEW 16 STORY OFFICE TOWER
 ROOM# 126 AND THE (2) GENERATOR LOCATED
 WEST OF THE NEW PARKING GARAGE ELEVATOR,
 WHAT IS THESE GENERATORS TO POWER?
  
 11) PROVIDE RATIONALE FOR PARKING GARAGE
 LEVELS 2-5 TO USE ELEVATOR 7 & 8 TO THE
 FIRST FLOOR AND TRANSFER TO ELEVATORS
 1-6 TO GAIN ACCESS TO THE OFFICE TOWER
 SECTION OF BUILDING?
  
 12A) A1.02-A1.05 DISABLED PARKING SPACES 11-4.6.2(1)
 ALL SPACES MUST BE
 LOCATED ON AN ACCESSIBLE ROUTE NO LESS
 THAN 44 INCHES (1118 MM)WIDE SO THAT
 USERS WILL NOT BE COMPELLED TO WALK OR
 WHEEL BEHIND PARKED VEHICLES.
  
 12B) THERE ARE (2) ISSUES ABOVE THE
 FIRST IS A 44" CONTINIOUS ACCESSIBLE
 PATH THE AREA MARKED AS A PATHWAY IN
 FRONT OF THE ELEVATORS IS APPROXIMATELY
 24".
 THE SECOND ISSUE IS THE DISABLED ARE
 COMPLLLED TO WALK OR WHEEL BEHIND PARKED VEHICLES.
  
 13)A1.01 THE EXIT PASSAGE WAY # 122
 DOESN'T TAKE YOU FROM THE EXIT DISCHARGE
 TO THE PUBLIC WAY. A0.22 THE LIFE SAFETY
 PLAN DOESN'T PROVIDE ANY INFORMATION
 ONCE YOU LEAVE THE PROTECTED EXIT.EXIT
 DISCHARGE. THAT PORTION OF A MEANS OF
 EGRESS SYSTEM BETWEEN THE TERMINATION OF
 AN EXIT AND A PUBLIC WAY.
  
 13A) THE MEANS OF EGRESS 44" FOR EXIT
 PASSAGE WAY# 122 STOPS ON EACH SIDE OF
 THE ENTRY FEATURE AREA, SEE CURB LINE.
 NEITHER THE LIFE SAFETY NOR THIS SHEET
 PROVIDES A CONTINIOUS PATH TO THE PUBLIC
 WAY.
  
 13B) A1.01 LOCATED JUST TO THE WEST OF
 THE MAIN ENTRY PLANS INDICATE A
 HANDICAPPED RAMP BUT TOTALLY MISS THE
 REQUIRED PASSENGER LOADING ZONE.
 11-4.1.2(5)(C) IF PASSENGER LOADING
 ZONES ARE PROVIDED, THEN AT LEAST ONE
 PASSENGER LOADING ZONE SHALL COMPLY WITH
 SECTION 11-4.6.6
 .
 11-4.1.2(5)(E) VALET PARKING. VALET
 PARKING FACILITIES SHALL PROVIDE A
 PASSENGER LOADING ZONE COMPLYING WITH
 SECTION 11-4.6.6 LOCATED ON AN
 ACCESSIBLE ROUTE TO THE ENTRANCE OF THE
 FACILITY. SECTION 11-4.1.2 (5)(A),
 SECTION 11-4.1.2 (5)(B), AND SECTION
 11-4.1.2 (5)(D) OF THIS SECTION DO NOT
 APPLY TO VALET PARKING FACILITIES.
  
 11-4.6.6 PASSENGER LOADING ZONES.
 PASSENGER LOADING ZONES SHALL PROVIDE AN
 ACCESS AISLE AT LEAST 60 INCHES (1525
 MM) WIDE AND 20 FEET (6096 MM) LONG
 ADJACENT AND PARALLEL TO THE VEHICLE
 PULL-UP SPACE (SEE FIGURE 11-10 ). IF
 THERE ARE CURBS BETWEEN THE ACCESS AISLE
 AND THE VEHICLE PULL-UP SPACE, THEN A
 CURB RAMP COMPLYING WITH SECTION 11-4.7
 SHALL BE PROVIDED. VEHICLE STANDING
 SPACES AND ACCESS AISLES SHALL BE LEVEL
 WITH SURFACE SLOPES NOT EXCEEDING 1:50
 (2 PERCENT) IN ALL DIRECTIONS.
  
 13C) ALTHOUGH THE EXISTING PARKING
 GARAGE SHOULD BE UNDER A SEPERATE PERMIT
  
 COMMENTS WILL BE ADDRESSED AT THIS TIME
 UNDER THIS PERMIT. ONCE THE PASSENGER
 LOADING ZONE IS PROVIDED AND ACCESS
 AISLE AND CROSS WALK AND CURB CUT
 LEADING TO THE ELEVATOR TOWER NEEDS TO
 BE ADDRESSED, MAKING THIS AN ACCESSIBLE
 ELEMENT.
  
 13D)NOTE: THE CODE SUMMARY OF THE "B"
 BLOCK PARKING GARAGE INDICATES A
 BUILDING TYPE "IB" WHEREAS THE RETAIL
 STORES AND PARKING STRUCTURE ARE
 CONSIDERED ONE STRUCTURE NOT (2)
 INDIVDUAL BUILDINGS, THEY WERE PERMITTED
 THIS WAY FOR PHASING ONLY. AGAIN
 DEPENDING ON THE LOCATION OF THE
 PREOPERTY LINE THERE MAY BE ISSUES WITH
 THE PARKING GARAGE ADDITION OF THE
 ELEVATOR AND TABLE 602!
  
 13E)THE EXIT PASSAGEWAY 122 HAS A 2 HR
 RATING LEADING UPTO DOOR 122A WITH A
 1 1/2 HR FIRE RATING.THE LIFE SAFETY
 PLAN ENDS THE FIRE RATING OF THE
 SURROUNDINGWALLS AND DOOR 120A TO THE
 FIRE PUMP ROOM(SHEET A2.01B) THERE IS NO
 RATING. TRUE YOU HAVE REACHED THE
 EXTERIOR OF THE BUILDING BUT THERE IS
 FIRE DANGER FROM THE FIRE PUMP ROOM AND
 THE WALLS JUST TO THE LEFT AS WELL AS
 THE WALLS TO THE RIGHT WHERE THE FIRE
 PUMP ROOM IS SITUATED. THIS IS SIMILAR
 TO A EXIT COURT ALTHOUGH THERE IS STILL
 A CEILING OVER THE PATH OF TRAVEL.
  
 13F) E1.01A INDICATES OVERHEAD
 CONDUCTORS PASSING DIRECTLY OVER THE
 EXIT PASSAGEWAY 122.1019.1.2
 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH
 AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT
 FOR REQUIRED EXIT DOORS, EQUIPMENT AND
 DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE
 DEPARTMENT COMMUNICATION AND ELECTRICAL
 RACEWAY SERVING THE EXIT ENCLOSURE AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M 2 ). SUCH
 PENETRATIONS SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 712 . THERE
 SHALL BE NO PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 13G) IT APPEARS THAT THERE IS (2) SETS
 OF CARD READERS TO GAIN ENTRANCE TO THE
 PARKING GARAGE. THE FIRST AT THE FOOT OF
 THE RAMP AND A SECOND SET INDICATED ON
 A1.02? PROVIDE DETAILS?
  
 14) A2.01A PLANS INDICATE SECURITY
 TURNSTILES, 11-4.13.2 REVOLVING DOORS
 AND TURNSTILES . 11-413.2(1)
 TURNSTILES SHALL NOT BE THE ONLY MEANS
 OF PASSAGE AT AN ACCESSIBLE ENTRANCE OR
 ALONG AN ACCESSIBLE ROUTE. AN ACCESSIBLE
 GATE OR DOOR SHALL BE PROVIDED ADJACENT
 TO THE TURNSTILE OR REVOLVING DOOR AND
 SHALL BE SO DESIGNED AS TO FACILITATE
 THE SAME USE PATTERN.
  
 15) A2.01A WALL DETAIL 8B OR 8C SEE UL
 LISTING U415 MISSING ITEM# 7
 CEMENTITIOUS BACKER UNITSSYSTEM "D" NOM
 1/2 OR 5/8". PROVIDE ADDITIONAL INFO. ON
 SCHEDULE SHEET A).31
  
 16) A2.01 WALL DETRAIL# 1 INDICATES THE
 USE OF A 2 HR RATED BLOCK UL LISTING
 U-905, THE FIVE LISTED BLOCK
 MANUFACTURERS WILL BE THE MANUFACTURERS
 THE BLOCK IS TO BE PURCHASED FROM.
 OTHERWISE PROVIDE THEEQUIVALENT
 THICKNESS FROM THE BLOCK MANUFACTURER
 FROM WHICH THE BLOCK WILL BE PRODUCED,
 SEE TABLE 721.3.2. 721.3.2 CONCRETE
 MASONRY WALLS.
 THE FIRE-RESISTANCE RATING OF WALLS AND
 PARTITIONS CONSTRUCTED OF CONCRETE
 MASONRY UNITS SHALL BE DETERMINED FROM
 TABLE 721.3.2 . THE RATING SHALL BE
 BASED ON THE EQUIVALENT THICKNESS OF THE
 MASONRY AND TYPE OF AGGREGATE USED.
  
 17) A2.01 ALL OF THE NON-RATED DRYWALL
 WALLS INDICATED ON A0.31 HAVE NO HEIGHT LIMITATIONS NOR
 SPACING, SEE T2506.2
 STEEL STUDS NON-LOAD BEARING, ASTM
 C-645.
  
 18A) A2.01B ROOM 115 THE DOOR SWING,
 SWINGS INTO THE CLEAR FLOOR SPACE OF THE
 LAVATORY.11-4.19.3 CLEAR FLOOR SPACE .
 A CLEAR FLOOR SPACE 30 INCHES BY 48
 INCHES (760 MM BY 1219 MM) COMPLYING
 WITH SECTION 11-4.2.4 SHALL BE PROVIDED
 IN FRONT OF A LAVATORY TO ALLOW FORWARD
 APPROACH. SUCH CLEAR FLOOR SPACE SHALL
 ADJOIN OR OVERLAP AN ACCESSIBLE ROUTE
 AND SHALL EXTEND A MAXIMUM OF 19 INCHES
 (485 MM) UNDERNEATH THE LAVATORY (SEE
 FIGURE 11-32 ).
  
 18B) PROVIDE CUT SECTION THROUGH SINK
 ROOM 118. 11-4.24.2 SINKS, HEIGHT. SINKS
 SHALL BE MOUNTED WITH THE COUNTER NO
 HIGHER THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 18C) EMERGENCY GENERATOR ROOM EXHAUST
 BLOWS DIRECTLY ON TO HANDICAPPED RAMPS
 LOCATED JUST EAST OF UNIT, IS THERE AIR DEFLECTION?
  
 18D) RESTROOM 103 IS MISSING THE
 REQUIRED CLEAR FLOOR SPACE 11-4.19.3.
  
 19) A1.06
 19A) PLANS INDICATE THIS PERMIT IS FOR A
 SHELL BUILDING, FLOORS TO BE BUILT OUT
 BY FUTURE TENANTS. LOOKING AT WORCST
 CASE OCCUPANT LOAD FOR THIS FLOOR THERE
 WILL BE PROBLEMS WITH THE CONFERENCE
 ROOM AND IF THE ROOF DECK IS CONSIDERED
 AN ASSEMBLY AREA. IF THE CONFERENCE ROOM
  
 IS FIGURED AT AN OCCUPANT LOAD OF 15SQ
 FT PER OCC= 309 OK FOR DOORS &
 STAIRWAYS.
 THE PROBLEM BEGINS IF THE CONFERENCE
 ROOM IS FIGURED AT A CONCENTRATION OF
 7SQ FT / OCC. OR IF THE ROOF AREA JUST
 WEST OF THE CONFERENCE ROOM WERE TO BE
 CONSIDERED AS PART OF THE ASSEMBLY AREA.
 THEN USING AN OCC LOAD OF 15 SQ FT /OCC
 THE LOAD FOR THE ROOFDECK ALONE IS 472+
 98( CONFERENCE ROOM) 211 (REMAINDER OF
 FLOOR) =781 OCC LOAD. NEITHER THE
 STAIRS NOR DOORWAYS WILL HANDLE THIS
 LOAD AS CONFIGURED.
  
 19B) IF PLANS ARE NOT RECONFIGURED TO
 HANDLE THIS ADDITIONAL OCCUPANT LOAD, A STIPULATION
 WILL BE PUT ON THE
 CERTIFICATE OF OCCUPANCYSTATING THAT
 THE ROOF DECK CAN NOT BE USED AS AN
 ASSEMBLY AREA. 110.2* W. P. B.
 ADMINISTRATIVE CODE, INFORMATION THAT IS
 REQUIRED FOR RECORD KEEPING & FOR
 CERTIFICATE OF OCCUPANCY:
 (F) ANY SPECIAL STIPULATIONS &
 CONDITIONS OF THE BUILDING PERMIT.
  
 19C) IF THE ROOFED AREA IS TO BE FIGURED
  
 AS AN ASSEMBLY AREA, THERE NEEDS TO BE
 ADDTTIONAL DOOR WAYS SINCE AN OCCUPANT
 LOAD GREATER THAN 50.1004.8 OUTDOOR
 AREAS.
 YARDS, PATIOS, COURTS AND SIMILAR
 OUTDOOR AREAS ACCESSIBLE TO AND USABLE
 BY THE BUILDING OCCUPANTS SHALL BE
 PROVIDED WITH MEANS OF EGRESS AS
 REQUIRED BY THIS CHAPTER. THE OCCUPANT
 LOAD OF SUCH OUTDOOR AREAS SHALL BE
 ASSIGNED BY THE BUILDING OFFICIAL IN
 ACCORDANCE WITH THE ANTICIPATED USE.
 WHERE OUTDOOR AREAS ARE TO BE USED BY
 PERSONS IN ADDITION TO THE OCCUPANTS OF
 THE BUILDING, AND THE PATH OF EGRESS
 TRAVEL FROM THE OUTDOOR AREAS PASSES
 THROUGH THE BUILDING, MEANS OF EGRESS
 REQUIREMENTS FOR THE BUILDING SHALL BE
 BASED ON THE SUM OF THE OCCUPANT LOADS
 OF THE BUILDING PLUS THE OUTDOOR AREAS. EXCEPTIONS: 1.
 OUTDOOR AREAS USED EXCLUSIVELY
 FOR SERVICE OF THE BUILDING NEED ONLY
 HAVE ONE MEANS OF EGRESS.
  
 19D) IF THE ROOF AREA IS CONSIDERED A
 ASSEMBLY AREA THE OCCUPANT LOAD FOR THE
 FLOOR WOULD BE APPROX 781 REQUIRING A
 THIRD EXIT. TABLE 1018.1.
  
 19E) A2.06 THIS COMMENT WILL HOLD TRUE
 FOR MORE DOORS THAN JUST THESE
 MENTIONED. S-1/A STAIRDOOR, S-2/A
 STAIRDOOR, 605A MECHANICAL & 606A
 EXECUTIVE VESTIBULE. ALL THESE DOORWAYS
 ARE APPROXIMATELY 21" DEEP. THE WAY THE
 DOORS ARE CONFIGURED A PERSON IN A
 WHEELCHAIR CAN NOT APPROACH THE DOORS
 WITH THE DOOR BEING RECESSED IN THE
 DOORWAY ON THE PULLSIDE. IT IS TRUE
 11-4.13.5 THAT DOOR OPENINGS MAY BE 24"
 DEEP, THE DOORWAY SHOWN AS AN EXAMPLE
 FIGURE 24 IS A CASED OPENING NO DOOR IS
 APPERANT.11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARENCES AT
 DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS
 SHOWN IN FIG. 25. THE FLOOR OR GROUND
 AREA WITH IN THE REQUIRED CLEARENCES
 SHALL BE CLEAR & LEVEL.
  
 20) A1.06- A1.16NOTE SEE ELETRICAL
 COMMENT FOR ELECTRICAL ROOM WITHIN
 TENANT SPACE. UNLESS TENANT OCCUPIES THE
 FULL FLOOR THIS IS A CODE ISSUE.
  
 21) SHEET A4.11 DETAIL# 4, AT VARIOUS
 LEVELS INDICATES EITHER PRECAST UNITS OR
  
 SPANDREL GLASS PANELS AT THE FLOOR
 LEVELS.
 21A) PRECAST PANELS INDICATE VARING
 HEIGHTS FROM THE FLOOR TO THE TOP OF
 PANEL, SOME ARRE 2'-0" OTHERS 2'-6", SEE
 A11.04 DESIGN # CEF 158 P, (G) THE
 CONCRETE WALL PANEL ARE TO BE A MINIMUM
 33" ABOVE THE FLOOR LEVEL.
  
 21B) SPANDREL GLASS PANELS ARE MISSING
 INSULATION AT GAGARGE LEVLE, SEE SHEET
 A11.04 DESIGN# CEJ 116 P NOTE "B" THAT
 THE 33" IS FROM THE FLOOR TOTHE BOTTOM
 OF THE TRANSOM.
  
 22) A4.12 SOUTH WALL SECTION A4.13 &
 A4.14 INDICATES THE USE OF EFIS TRIM ON
 THE EXTERIOR OF THE BUILDING.1406.2.2 ARCHITECTURAL
 TRIM. IN BUILDINGS OF TYPE
 I, II, III AND IV CONSTRUCTION THAT DO
 NOT EXCEED THREE STORIES OR 40 FEET (12
 192 MM) IN HEIGHT ABOVE GRADE PLANE,
 EXTERIOR WALL COVERINGS SHALL BE
 PERMITTED TO BE CONSTRUCTED OF WOOD
 WHERE PERMITTED BY SECTION 1405.4 OR
  
 OTHER EQUIVALENT COMBUSTIBLE MATERIAL.
 COMBUSTIBLE EXTERIOR WALL COVERINGS,
 OTHER THAN FIRE-RETARDANT-TREATED WOOD
 COMPLYING WITH SECTION 2303.2 FOR
 EXTERIOR INSTALLATION, SHALL NOT EXCEED
 10 PERCENT OF AN EXTERIOR WALL SURFACE
 AREA WHERE THE FIRE SEPARATION DISTANCE
 IS 5 FEET (1524 MM) OR LESS.
 ARCHITECTURAL TRIM THAT EXCEEDS 40 FEET
 (12 192 MM) IN HEIGHT ABOVE GRADE PLANE
 SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE
 SECURED TO THE WALL WITH METAL OR OTHER
 APPROVED NONCOMBUSTIBLE BRACKETS.
  
 23) A4.1.2 PLANS INDICATE USE OF MCM
 ( METAL COMPOSITE MATERIALS) SEE:
 1407.3 ARCHITECTURAL TRIM AND
 EMBELLISHMENTS.
 MCM USED AS ARCHITECTURAL TRIM OR
 EMBELLISHMENTS SHALL COMPLY WITH
 SECTIONS 1407.7 THROUGH 1407.13 .
 1407.10 TYPE I, II, III AND IV
 CONSTRUCTION.
 WHERE INSTALLED ON BUILDINGS OF TYPE I,
 II, III AND IV CONSTRUCTION, MCM SYSTEMS
 SHALL COMPLY WITH SECTIONS 1407.10.1
 THROUGH 1407.10.4 , OR 1407.11 .
  
 24) A4.14 DETAILS INDICATE A COVERED
 DROP OFF AREA WITH THE USE OF EFIS
 SYSTEM, PROVIDE REPORT WITH APPROVED
 HORIZONTAL USEAGE. RULE 9B-72 FL
 ADDMINISTRATIVE COVE.
  
 25) A4.15 FLOOR INSULATION THE 6TH FLOOR
 (LAST FLOOR ABOVE PARKING GARAGE),
 PROVIDE WHAT TYPE OF SPRAY ON FLOOR
 INSULATION WILL BE USED, ALSO WILL THIS
 BE THE SAME FIRE PROOFING MATERIAL
 REQUIRED FOR FLOORS AND BEAMS? IF SO
 DOES THIS MATERIAL HAVE FIRE RATING? 13-405.1.C.1.1.
 FOR FLOORS WITH BEAMS THAT EXTEND BELOW
 THE FLOOR SLAB, THE FLOOR SHALL BE
 INSULATED EITHER ON THE INTERIOR ABOVE
 THE SLAB OR ON THE EXPOSED FLOOR AND ALL
 EXPOSED SURFACES OF THE BEAMS THAT
 EXTEND 24 INCHES (610 MM) AND LESS BELOW
 THE EXPOSED FLOOR.
  
 26) A4.21 DETAIL# 7, INDICATES A
 EXTERIOR SOFFIT DETAIL, NOTE SEE
 STRUCTURAL DRAWINGS FOR UPLIFT
 REQUIREMENTS, STRUCTURAL S0.01 LIGHT
 GAUGE STEEL FRAMING NOTE DOESN'T PROVIDE
  
 ANY REQUIREMENTS NOR SIZE, GAUGE OF
 STEEL, CONFIGURATION SPAN SPACING OR LOADING.2506.2
 STANDARDS.
 GYPSUM BOARD MATERIALS SHALL CONFORM TO
 THE APPROPRIATE STANDARDS LISTED IN
 TABLE 2506.2 AND CHAPTER 35 AND, WHERE
 REQUIRED FOR FIRE PROTECTION, SHALL
 CONFORM TO THE PROVISIONS OF CHAPTER 7 .
  
 27) A4.21 DETAIL# 1 IS A SECTION AT THE
 CORNICE, PLANS INDICATE MORE DETAILS SEE STRUCTURAL
 PLANS, WHERE? ADDITIONAL
 INFORMATION NEEDED.
 106.1.2 ADDITIONAL DATA. THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS,
 STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
  
 28) A5.81:
 28A) DETAIL# 1, CANOPY FROM OFFICE TOWER
 TO THE NEW ELEVATOR TOWER TO COMPLY WITH
 3104.5 & TABLE 602 @ PROPERTY LINE?
  
 28B) PLANS DO NOT INDICATE ON THE OFFICE
 TOWER CANOPY WHAT TYPE OF FENESTRATION
 SHALL BE USED.2405.2 ALLOWABLE GLAZING
 MATERIALS AND LIMITATIONS.
  
 28C) ARCHITECTURAL PLANS DO NOT INDICATE
 ENOUGH DETAILS NOR DOES THE STRUCTURAL
 PLANS. ADDITIONAL INFORMATION REQUIRED.
 106.1.2*ADDITIONAL DATA.
  
 28D) 2405.5 UNIT SKYLIGHTS.
 UNIT SKYLIGHTS SHALL BE TESTED AND
 LABELED AS COMPLYING WITH 101/I.S.2/NAFS
 VOLUNTARY PERFORMANCE SPECIFICATION FOR
 WINDOWS, SKYLIGHTS AND GLASS . THE LABEL
 SHALL STATE THE NAME OF THE
 MANUFACTURER, THE APPROVED LABELING
 AGENCY, THE PRODUCT DESIGNATION AND THE PERFORMANCE
 GRADE RATING AS SPECIFIED IN 101/I.S.2/NAFS. IF THE
 PRODUCT
 MANUFACTURER HAS CHOSEN TO HAVE THE
 PERFORMANCE GRADE OF THE SKYLIGHT RATED
 SEPARATELY FOR POSITIVE AND NEGATIVE
 DESIGN PRESSURE, THEN THE LABEL SHALL
 STATE BOTH PERFORMANCE GRADE RATINGS AS
 SPECIFIED IN 101/I.S.2/NAFS AND THE
 SKYLIGHT SHALL COMPLY WITH SECTION
 2405.5.2 . IF THE SKYLIGHT IS NOT RATED
 SEPARATELY FOR POSITIVE AND NEGATIVE
 PRESSURE, THEN THE PERFORMANCE GRADE
 RATING SHOWN ON THE LABEL SHALL BE THE
 PERFORMANCE GRADE RATING DETERMINED IN
 ACCORDANCE WITH 101/I.S.2/NAFS FOR BOTH
 POSITIVE AND NEGATIVE DESIGN PRESSURE,
 AND THE SKYLIGHT SHALL CONFORM TO
 SECTION 2405.5.1 .
  
 28E) LIGHT- TRANSMITTING PLASTICS: LIGHT-TRANSMITTING
 PLASTIC MATERIALS
 THAT MEET THE OTHER CODE REQUIREMENTS
 FOR WALLS AND ROOFS SHALL BE PERMITTED
 TO BE USED IN ACCORDANCE WITH THE OTHER
 APPLICABLE CHAPTERS OF THE CODE.
  
 2606.2 APPROVAL FOR USE.
 SUFFICIENT TECHNICAL DATA SHALL BE
 SUBMITTED TO SUBSTANTIATE THE PROPOSED
 USE OF ANY LIGHT-TRANSMITTING MATERIAL,
 AS APPROVED BY THE BUILDING OFFICIAL AND
 SUBJECT TO THE REQUIREMENTS OF THIS
 SECTION.
  
 2606.3 IDENTIFICATION.
 EACH UNIT OR PACKAGE OF
 LIGHT-TRANSMITTING PLASTIC SHALL BE
 IDENTIFIED WITH A MARK OR DECAL
 SATISFACTORY TO THE BUILDING OFFICIAL,
 WHICH INCLUDES IDENTIFICATION AS TO THE
 MATERIAL CLASSIFICATION.
  
 2606.4 SPECIFICATIONS.
 LIGHT-TRANSMITTING PLASTICS, INCLUDING THERMOPLASTIC,
 THERMOSETTING OR
 REINFORCED THERMOSETTING PLASTIC
 MATERIAL, SHALL HAVE A SELF-IGNITION
 TEMPERATURE OF 650?F (343?C) OR GREATER
 WHERE TESTED IN ACCORDANCE WITH ASTM D
 1929; A SMOKE-DEVELOPED INDEX NOT
 GREATER THAN 450 WHERE TESTED IN THE
 MANNER INTENDED FOR USE IN ACCORDANCE
 WITH ASTM E 84, OR NOT GREATER THAN 75
 WHERE TESTED IN THE THICKNESS INTENDED
 FOR USE IN ACCORDANCE WITH ASTM D 2843
 AND SHALL CONFORM TO ONE OF THE
 FOLLOWING COMBUSTIBILITY
 CLASSIFICATIONS:
 CLASS CC1: PLASTIC MATERIALS THAT HAVE A
 BURNING EXTENT OF 1 INCH (25 MM) OR LESS
 WHERE TESTED AT A NOMINAL THICKNESS OF
 0.060 INCH (1.5 MM), OR IN THE THICKNESS
 INTENDED FOR USE, IN ACCORDANCE WITH
 ASTM D 635,
 CLASS CC2: PLASTIC MATERIALS THAT HAVE A
 BURNING RATE OF 2.5 INCHES PER MINUTE
 (1.06 MM/S) OR LESS WHERE TESTED AT A
 NOMINAL THICKNESS OF 0.060 INCH (1.5
 MM), OR IN THE THICKNESS INTENDED FOR
 USE, IN ACCORDANCE WITH ASTM D 635.
  
 2606.5 STRUCTURAL REQUIREMENTS.
 LIGHT-TRANSMITTING PLASTIC MATERIALS IN
 THEIR ASSEMBLY SHALL BE OF ADEQUATE
 STRENGTH AND DURABILITY TO WITHSTAND THE
 LOADS INDICATED IN CHAPTER 16 .
 TECHNICAL DATA SHALL BE SUBMITTED TO
 ESTABLISH STRESSES, MAXIMUM UNSUPPORTED
 SPANS AND SUCH OTHER INFORMATION FOR THE
 VARIOUS THICKNESSES AND FORMS USED AS
 DEEMED NECESSARY BY THE BUILDING
 OFFICIAL.
  
 2606.6 FASTENING.
 FASTENING SHALL BE ADEQUATE TO WITHSTAND
 THE LOADS IN CHAPTER 16 . PROPER
 ALLOWANCE SHALL BE MADE FOR EXPANSION
 AND CONTRACTION OF LIGHT-TRANSMITTING
 PLASTIC MATERIALS IN ACCORDANCE WITH
 ACCEPTED DATA ON THE COEFFICIENT OF
 EXPANSION OF THE MATERIAL AND OTHER
 MATERIAL IN CONJUNCTION WITH WHICH IT IS EMPLOYED.
  
 2606.7.4 FIRE SUPPRESSION SYSTEM.
 IN BUILDINGS THAT ARE EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1 , PLASTIC LIGHT-DIFFUSING
 SYSTEMS SHALL BE PROTECTED BOTH ABOVE
 AND BELOW UNLESS THE SPRINKLER SYSTEM
 HAS BEEN SPECIFICALLY APPROVED FOR
 INSTALLATION ONLY ABOVE THE
 LIGHT-DIFFUSING SYSTEM. AREAS OF
 LIGHT-DIFFUSING SYSTEMS THAT ARE
 PROTECTED IN ACCORDANCE WITH THIS
 SECTION SHALL NOT BE LIMITED.
  
 28F) THE CANOPY NORTH OF THE THE NEW
 ELEVATOR TOWER IS UNDER A DDIFFERENT
 PCN, SEPERATE PROPERTY REQUIRING A
 SEPERATE PERMIT.ARCHITECTURAL PLANS DO
 NOT INDICATE ENOUGH DETAILS NOR DOES THE STRUCTURAL
 PLANS. ADDITIONAL INFORMATION REQUIRED.106.1.2*
 ADDITIONAL DATA.
  
 28G) LIGHT- TRANSMITTING PLASTICS: LIGHT-TRANSMITTING
 PLASTIC MATERIALS
 THAT MEET THE OTHER CODE REQUIREMENTS
 FOR WALLS AND ROOFS SHALL BE PERMITTED
 TO BE USED IN ACCORDANCE WITH THE OTHER
 APPLICABLE CHAPTERS OF THE CODE.
  
 2606.2 APPROVAL FOR USE.
 SUFFICIENT TECHNICAL DATA SHALL BE
 SUBMITTED TO SUBSTANTIATE THE PROPOSED
 USE OF ANY LIGHT-TRANSMITTING MATERIAL,
 AS APPROVED BY THE BUILDING OFFICIAL AND
 SUBJECT TO THE REQUIREMENTS OF THIS
 SECTION.
  
 2606.3 IDENTIFICATION.
 EACH UNIT OR PACKAGE OF
 LIGHT-TRANSMITTING PLASTIC SHALL BE
 IDENTIFIED WITH A MARK OR DECAL
 SATISFACTORY TO THE BUILDING OFFICIAL,
 WHICH INCLUDES IDENTIFICATION AS TO THE
 MATERIAL CLASSIFICATION.
  
 2606.4 SPECIFICATIONS.
 LIGHT-TRANSMITTING PLASTICS, INCLUDING THERMOPLASTIC,
 THERMOSETTING OR
 REINFORCED THERMOSETTING PLASTIC
 MATERIAL, SHALL HAVE A SELF-IGNITION
 TEMPERATURE OF 650?F (343?C) OR GREATER
 WHERE TESTED IN ACCORDANCE WITH ASTM D
 1929; A SMOKE-DEVELOPED INDEX NOT
 GREATER THAN 450 WHERE TESTED IN THE
 MANNER INTENDED FOR USE IN ACCORDANCE
 WITH ASTM E 84, OR NOT GREATER THAN 75
 WHERE TESTED IN THE THICKNESS INTENDED
 FOR USE IN ACCORDANCE WITH ASTM D 2843
 AND SHALL CONFORM TO ONE OF THE
 FOLLOWING COMBUSTIBILITY
 CLASSIFICATIONS:
 CLASS CC1: PLASTIC MATERIALS THAT HAVE A
 BURNING EXTENT OF 1 INCH (25 MM) OR LESS
 WHERE TESTED AT A NOMINAL THICKNESS OF
 0.060 INCH (1.5 MM), OR IN THE THICKNESS
 INTENDED FOR USE, IN ACCORDANCE WITH
 ASTM D 635,
 CLASS CC2: PLASTIC MATERIALS THAT HAVE A
 BURNING RATE OF 2.5 INCHES PER MINUTE
 (1.06 MM/S) OR LESS WHERE TESTED AT A
 NOMINAL THICKNESS OF 0.060 INCH (1.5
 MM), OR IN THE THICKNESS INTENDED FOR
 USE, IN ACCORDANCE WITH ASTM D 635.
  
 2606.5 STRUCTURAL REQUIREMENTS.
 LIGHT-TRANSMITTING PLASTIC MATERIALS IN
 THEIR ASSEMBLY SHALL BE OF ADEQUATE
 STRENGTH AND DURABILITY TO WITHSTAND THE
 LOADS INDICATED IN CHAPTER 16 .
 TECHNICAL DATA SHALL BE SUBMITTED TO
 ESTABLISH STRESSES, MAXIMUM UNSUPPORTED
 SPANS AND SUCH OTHER INFORMATION FOR THE
 VARIOUS THICKNESSES AND FORMS USED AS
 DEEMED NECESSARY BY THE BUILDING
 OFFICIAL.
  
 2606.6 FASTENING.
 FASTENING SHALL BE ADEQUATE TO WITHSTAND
 THE LOADS IN CHAPTER 16 . PROPER
 ALLOWANCE SHALL BE MADE FOR EXPANSION
 AND CONTRACTION OF LIGHT-TRANSMITTING
 PLASTIC MATERIALS IN ACCORDANCE WITH
 ACCEPTED DATA ON THE COEFFICIENT OF
 EXPANSION OF THE MATERIAL AND OTHER
 MATERIAL IN CONJUNCTION WITH WHICH IT IS EMPLOYED.
  
 2606.7.4 FIRE SUPPRESSION SYSTEM.
 IN BUILDINGS THAT ARE EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1 , PLASTIC LIGHT-DIFFUSING
 SYSTEMS SHALL BE PROTECTED BOTH ABOVE
 AND BELOW UNLESS THE SPRINKLER SYSTEM
 HAS BEEN SPECIFICALLY APPROVED FOR
 INSTALLATION ONLY ABOVE THE
 LIGHT-DIFFUSING SYSTEM. AREAS OF
 LIGHT-DIFFUSING SYSTEMS THAT ARE
 PROTECTED IN ACCORDANCE WITH THIS
 SECTION SHALL NOT BE LIMITED.
  
 29)A5.82/ A5.83
 ARCHITECTURAL PLANS DO
 NOT INDICATE ENOUGH DETAILS NOR DOES THE STRUCTURAL
 PLANS. ADDITIONAL INFORMATION REQUIRED.106.1.2*
 ADDITIONAL DATA.
  
 30)A5.92 NEW ELEVATOR TOWER:
 1406.2.2
 ARCHITECTURAL TRIM. IN BUILDINGS OF TYPE
 I, II, III AND IV CONSTRUCTION THAT DO
 NOT EXCEED THREE STORIES OR 40 FEET (12
 192 MM) IN HEIGHT ABOVE GRADE PLANE,
 EXTERIOR WALL COVERINGS SHALL BE
 PERMITTED TO BE CONSTRUCTED OF WOOD
 WHERE PERMITTED BY SECTION 1405.4 OR
 OTHER EQUIVALENT COMBUSTIBLE MATERIAL.
  
 31) A6.06 DETAIL# 2, THE HANDRAIL AT THE
 BOTTOM OF THE STAIRS MISSING HORIZONTAL
 EXTENTION.11-4.9.4(2)IF HANDRAILS
 ARE NOT CONTINUOUS, THEY SHALL EXTEND AT
 LEAST 12 INCHES (305 MM) BEYOND THE TOP
 RISER AND AT LEAST 12 INCHES (305 MM)
 PLUS THE WIDTH OF ONE TREAD BEYOND THE
 BOTTOM RISER. AT THE TOP, THE EXTENSION
 SHALL BE PARALLEL WITH THE FLOOR OR
 GROUND SURFACE. AT THE BOTTOM, THE
 HANDRAIL SHALL CONTINUE TO SLOPE FOR A
 DISTANCE OF THE WIDTH OF ONE TREAD FROM
 THE BOTTOM RISER; THE REMAINDER OF THE
 EXTENSION SHALL BE HORIZONTAL [SEE
 FIGURE 11-19 (C) AND FIGURE 11-19 (D)].
 HANDRAIL EXTENSIONS SHALL COMPLY WITH
 SECTION 11-4.4 .
  
 32A) A8.71 DETAIL# 8 INDICATES A TYPICAL
 RESTROOM DETAIL WHEREAS IT DEPICTS A
 BREAKROOM.
  
 32B) SAME DETAIL INDICATES A SINK HEIGTH
 OF 36" IN HEIGTH.
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 32C) DETAIL (1 & 2), PLEASE INDICATE THE
 CLEAR FLOOR SPACE REQUIREDFOR THE
 LAVATORY. 11-4.19.3 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE 30 INCHES BY 48
 INCHES (760 MM BY 1219 MM) COMPLYING
 WITH SECTION 11-4.2.4 SHALL BE PROVIDED
 IN FRONT OF A LAVATORY TO ALLOW FORWARD
 APPROACH. SUCH CLEAR FLOOR SPACE SHALL
 ADJOIN OR OVERLAP AN ACCESSIBLE ROUTE
 AND SHALL EXTEND A MAXIMUM OF 19 INCHES
 (485 MM) UNDERNEATH THE LAVATORY (SEE
 FIGURE 11-32 ).
  
 33) A10.16 /A1.16 PLANS INDICATE OPEN TO
 BELOW, SECTION A5.62 DETAIL 2 INDICATES
 THE ROOF LEDGE BUT NOT THE ACTUAL
 OPENING, TO WHERE?
  
 34) S0.01
 34A) PLANS INDICATE THE DESIGN TO ASCE
 7-02 BUT THE PRESSURES INDICATED DO NOT
 ILLUSTRATE THE PRESSURES FOR WIND ZONES
 1,2 AND 3 FOR THE ROOF ZONES AND ZONES 4
 & 5 FOR THE INTERIOR WALL AND WALL END
 ZONES. 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 34B)FL BLD CODE 1609.1.4: COMPONENTS
 & CLADDING, PROVIDE 2 COPIES(3 IF
 THRESH- OLD OR RESIDENT INSPECTOR) OF
 PRODUCT TESTING REPORTS,MISSING REPORTS
 ARE AS FOLLOWS:
 A) FIXED WINDOWS
 B) STOREFRONT WINDOWS/SPANDREAL
 C) SKYLIGHTS
 D) MULLIONS
 E) EXTERIOR METAL DOORS SINGLE/ PAIRS
 F) EXTERIOR GLAZED DOORS
 G) ROLL UP DOORS
 H) WALL LOUVERS
 I) EFIS EXTERIOR INSULATION FINISH
 SYSTEM/ DENSEGLASS
 J) ROOF ASSEMBLIES
  
 35)1009.5.3 STAIR IDENTIFICATION.
 AN APPROVED SIGN SHALL BE LOCATED AT
 EACH FLOOR LEVEL LANDING IN ALL ENCLOSED
 STAIRWAYS OF BUILDINGS FOUR OR MORE
 STORIES IN HEIGHT. THE SIGN SHALL
 INDICATE THE FLOOR LEVEL AND THE
 AVAILABILITY OF ROOF ACCESS FROM THAT
 STAIRWAY AND AN IDENTIFICATION OF THE
 STAIRWAY. THE SIGN SHALL ALSO STATE THE
 FLOOR LEVEL OF AND DIRECTION TO EXIT
 DISCHARGE. THE SIGN SHALL BE LOCATED
 APPROXIMATELY 5 FEET (1524 MM) ABOVE THE
 FLOOR LANDING IN A POSITION WHICH IS
 READILY VISIBLE WHEN THE DOOR IS IN THE
 OPEN OR CLOSED POSITION. THE FLOOR LEVEL DESIGNATION
 SHALL ALSO BE TACTILE IN
 ACCORDANCE WITH CHAPTER 11 .
  
 36) PROVIDE ADDITIONAL INFORMATION
 INDICATING COMPLIANCE WITH:
 1019.1.8 SMOKEPROOF ENCLOSURES.
 IN BUILDINGS REQUIRED TO COMPLY WITH
 SECTION 403 OR 405, EACH OF THE EXITS OF
 A BUILDING THAT SERVES STORIES WHERE THE
 FLOOR SURFACE IS LOCATED MORE THAN 75
 FEET (22 860 MM) ABOVE THE LOWEST LEVEL
 OF FIRE DEPARTMENT VEHICLE ACCESS OR
 MORE THAN 30 FEET (9144 MM) BELOW THE
 LEVEL OF EXIT DISCHARGE SERVING SUCH
 FLOOR LEVELS SHALL BE A SMOKEPROOF
 ENCLOSURE OR PRESSURIZED STAIRWAY IN
 ACCORDANCE WITH SECTION 909.20 .
  
 1019.1.8.1 ENCLOSURE EXIT.
 A SMOKEPROOF ENCLOSURE OR PRESSURIZED
 STAIRWAY SHALL EXIT INTO A PUBLIC WAY OR
 INTO AN EXIT PASSAGEWAY, YARD OR OPEN
 SPACE HAVING DIRECT ACCESS TO A PUBLIC
 WAY. THE EXIT PASSAGEWAY SHALL BE
 WITHOUT OTHER OPENINGS AND SHALL BE
 SEPARATED FROM THE REMAINDER OF THE
 BUILDING BY 2-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION.
  
 37) PLANS DO NOT PROVIDE INFORMATION AS
 TO ENCLOSED PARKING GARAGES: 406.4.2
 VENTILATION.
 A MECHANICAL VENTILATION SYSTEM SHALL BE
 PROVIDED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL .
  
 38) ELEVATORS 7&8:
  
 38A) 3003.6.1 VENTS. HOISTWAYS OF ELEVA-
 TORS SERVING MORE THAN 3 FLOORS SHALL BE
 PROVIDED WITH MEANS OF VENTING SMOKE AND
 HOT GASES TO THE OUTER AIR IN CASE OF
 FIRE.
  
 38B) 3003.6.2 VENTS SHALL BE LOCATED
 BELOW THE FLOOR OR FLOORS AT THE TOP OF
 THE HOISTWAY, AND SHALL BE EITHER DIR-
 ECTLY TO THE OUTER AIR OR THROUGH NON-
 COMBUSTIBLE DUCTS TO THE OUTER AIR.
  
 39) NORTH ELEVATOR:
 39A)3003.6.1 VENTS. HOISTWAYS OF
 ELEVA- TORS SERVING MORE THAN 3 FLOORS
 SHALL BEPROVIDED WITH MEANS OF VENTING
 SMOKE AND HOT GASES TO THE OUTER AIR IN
 CASE OF FIRE.
  
 39B) 3003.6.2 VENTS SHALL BE LOCATED
 BELOW THE FLOOR OR FLOORS AT THE TOP OF
 THE HOISTWAY, AND SHALL BE EITHER DIR-
 ECTLY TO THE OUTER AIR OR THROUGH NON-
 COMBUSTIBLE DUCTS TO THE OUTER AIR.
  
 40)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 NOTE: WITH THE RESPONCE COMMENTS FROM
 THIS REVIEW, ADDITONAL COMMENTS MAY
 APPEAR ON THE NEXT REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]


Account Summary | Usage Policy | Privacy Policy