Plan Review Notes
Plan Review Notes For Permit 06040955
Permit Number 06040955
Review Stop P
Sequence Number 6
Notes
Date Text
2009-09-02 17:59:28REVISION DENIED
 REFERENCE:
 FBC-2004 PLUMBING
  
 1. SHT P-1 SANITARY RISER DIAGRAM AND PLUMBING PLAN
 SHOW A DRY HORIZONTAL VENT UPSTREAM OF THE WATER
 CLOSETS. SECTION 905.3. EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE. ONE W/C CAN CONNECT ON THE
 VERTICAL RISE OF THE VENT TO CORRECT THE CODE
 DEFICIENCY.
  
 2. SHT P-1 SANITARY RISER DIAGRAM AND PLUMBING PLAN. A
 CLEANOUT IS REQUIRED NEAR THE JUNCTION OF THE BUILDING
 DRAIN AND THE BUILDING SEWER PER SECTION 708.3.5. AN
 APPROVED TWO-WAY CLEANOUT SERVING BOTH THE SEWER AND
 THE BLDG DRAIN IS APPROVED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  