| Plan Review Notes For Permit 06040955 |
| Permit Number |
06040955 |
|
| Review Stop |
P |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2009-09-02 17:59:28 | REVISION DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | | | | 1. SHT P-1 SANITARY RISER DIAGRAM AND PLUMBING PLAN | | | SHOW A DRY HORIZONTAL VENT UPSTREAM OF THE WATER | | | CLOSETS. SECTION 905.3. EVERY DRY VENT CONNECTING TO A | | | HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF | | | THE HORIZONTAL DRAIN PIPE. ONE W/C CAN CONNECT ON THE | | | VERTICAL RISE OF THE VENT TO CORRECT THE CODE | | | DEFICIENCY. | | | | | | 2. SHT P-1 SANITARY RISER DIAGRAM AND PLUMBING PLAN. A | | | CLEANOUT IS REQUIRED NEAR THE JUNCTION OF THE BUILDING | | | DRAIN AND THE BUILDING SEWER PER SECTION 708.3.5. AN | | | APPROVED TWO-WAY CLEANOUT SERVING BOTH THE SEWER AND | | | THE BLDG DRAIN IS APPROVED. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | | | | |
|